My atv610 is running perfectly. But once you stop, it will show OSF Error and cannot start agin without reseting the drive. Why is that?
@eeebackbenchersКүн бұрын
thanks for comment brother ! see multiple reason behind this. First thing OSF stands for " Mains overvoltage fault " it will be happended due to :- • Line voltage is too high: • Disturbed line supply and power quality issues( check harmonics level).
@NidhinKandempathКүн бұрын
@@eeebackbenchers but then it should show before starting also right? It is happening only after stopping the pump. Also other 4 pumps doesn't have this issue.
@eeebackbenchers4 күн бұрын
Just copy paste the below link in your browser and you get the manual of type of SEO i.e. DN4-SEO, DN3-SEO & DN2-SEO : ebgorg.my.site.com/slk/s/global-search/SEEOM%20manual
@bestrelaxingmusic3124 күн бұрын
Hello sir motor overload pr trip hoti hai to reset ka option hi nahi milta fir supply on off kr ke hi trip nikalna padta hai
@eeebackbenchers4 күн бұрын
kzbin.info/www/bejne/bWTLiYWVab6okNUsi=LecuEIk_zlnybYPY - in this video you will found how reset the fault
@santoshpatra934315 күн бұрын
Very nice
@eeebackbenchers15 күн бұрын
Thanks brother
@ROHITKUMAR-uc9ju19 күн бұрын
Sir mujhe iss drive m Start stop push button and speed up and down ka wiring and parameter chahiye sx2000 ka
@eeebackbenchers17 күн бұрын
Do one thing refer manual of description box and you will get the example of wiring ( simple connect common terminal with desired terminal with NO PUSH BUTTON) you will also get reference video on channel
@kamallodh568619 күн бұрын
❤ very good information
@eeebackbenchers18 күн бұрын
Thanks brother for you comment , it means lots to me . Thanks again
@ROHITKUMAR-uc9ju19 күн бұрын
Or sir up and down wiring diagram v chahiy
@eeebackbenchers18 күн бұрын
At time 05:22 please refer page and you will get the terminal details with speed up and down parameter , still any doubt comment me back with terminal no where you want to speed up and down
@ROHITKUMAR-uc9ju19 күн бұрын
Please sir send me this manual
@sudh304kapoor18 күн бұрын
Manual already in description box please find
@eeebackbenchers18 күн бұрын
Refer description box
@pacifierappu28 күн бұрын
Oct alarm how to solve
@eeebackbenchers14 күн бұрын
sorry for late replay. An over current trip - (OCT) over voltage trip - (OVT)
@skylabreddymaddikunta7170Ай бұрын
SIR,WHEN WE KEPT THE AUTO MODE IMMEDIATELY 2NO CAPACITOR RUNNING.NO LOAD PURPOSE.BUT I HAVE NO NEEC.HOW CAN REMOVE THIS ONE
@eeebackbenchersАй бұрын
Bhai ,message is not clear to me but as I understand you taking about when you put auto mode selection from panel selector switch when 02 contactor ON immediately. If this case , then wiring problem is confirm . In this case you also verify that when contactor ON and Apfc respective LED should not ON
@HQdocumentaryАй бұрын
When target power factor is not reached although all the capacitor steps have been connected, so what the problem is?
@eeebackbenchersАй бұрын
Simply means selected capacitor bank are not sufficient to compensate system inductive power. Need to add more capacitor in this case
@HQdocumentaryАй бұрын
@eeebackbenchers but another controller showed pf has been reched!
@skylabreddymaddikunta7170Ай бұрын
SIR,4040 ENERGY METER CAN SHOWN THE KWH CONSTANTLY
@eeebackbenchersАй бұрын
yes. DETAILS OF PARAMETERS : V, A, F, PF, kW, kVA, Run hours, kWh (EB and DG), Old energy, Site selectable kWh / kVAh
@santhoshr53Ай бұрын
Plz provide password for the kit
@eeebackbenchersАй бұрын
already revert.
@santhoshr53Ай бұрын
What is password for maintenance plz share
@eeebackbenchersАй бұрын
bhai to perform the test , no password is required. what is purpose to get maintenance password.
@santhoshr53Ай бұрын
Memory card showing error
@santhoshr53Ай бұрын
That's why password is required
@santhoshr53Ай бұрын
Possible to share urs contact no
@santhoshr53Ай бұрын
Can i get urs contact no
@kamaleshmakal8283Ай бұрын
Please tell me what is used of START and RESET ?
@eeebackbenchersАй бұрын
Thanks for comment brother, * 1NO contact assigned to start button ( you can use as per you control circuit requirement like as a start command). * Reset is used to reset the fault. 1NO- Alarm 1NC- TRIP Hope its clear now.
@jahedbarbhuiya2666Ай бұрын
Relay run me Ja nahi raha hai sir
@eeebackbenchersАй бұрын
Kya error aa raha hai
@naushadmohammad2784Ай бұрын
Master and slave 2 controller ke leye kon sa sattings karna hoga. With aingle ct
@eeebackbenchersАй бұрын
Hello sir , I never tried this so unable to comment on this .
I have 2 same meter, not able to enter programming mode, pressing auto manual button doesnt allowing to enter any mode check
@eeebackbenchersАй бұрын
Thanks for comment but I never face such problem I think you should contact to Epcos only
@mdsartajsiddiquee5269Ай бұрын
Good emformecan sir ji aap ka video se aasani se samjh me aata hai 🎉🎉🎉
@eeebackbenchersАй бұрын
Thankyou bhai
@fazlasarfaraz2627Ай бұрын
Undc aa raha etasmart 6r me how to solve this problem
@eeebackbenchersАй бұрын
Bhai Undc ( under current) Matlab ct se sufficient current nahi aa raha . Check ct output at Apfc end
@irfanshah9690Ай бұрын
Really me pf velu settings karne K bad pf velu display per km btarahi he.is lie koi solutions btaen plz site per phasa hoa hon
@eeebackbenchersАй бұрын
Pf value kam Kaha Bata raha hai Matlab setting main enter karne ke baad ya view setting main ya , actual of kam dikka raha hai
@sudh304kapoorАй бұрын
Share your number if still there is problem I will call you
@kingofthemagicАй бұрын
How to open DI1 . For forward
@eeebackbenchersАй бұрын
Thanks for comment , please note the digital input DI1 is assigned to : * ( forward) in 2- wire control * (Drive running) in 3- wire control Or do factory setting by default it s forward
@maqsoodahmed8043Ай бұрын
super explaination
@eeebackbenchersАй бұрын
Thankyou dost
@RaoTechEasy2 ай бұрын
Mera APFC panel EK MINUT KE ANDAR UNDC aa rha hai phir undc off ho rha hai yani bar bar on ho rha hai capacitor . 5 amp current me
@eeebackbenchers2 ай бұрын
It seems like some ct connections are loose , also check ct current output it should be higher then min. Requirement . You can also also refit the ct connector of apfc
@krupacarriers84732 ай бұрын
nice information
@eeebackbenchers2 ай бұрын
Thanks
@krupacarriers84732 ай бұрын
Sir, my L&T dual source energy meter WL4040 in not uploading daily energy readings.. please guide me.
@eeebackbenchers2 ай бұрын
RISHABH Digital Meter programming manual :- rishabh.co.in/uploads/product/Operating_Manual_Eine+_DC_DPM_48x96_Rev_G.pdf
@jahedbarbhuiya26662 ай бұрын
Relay earth fault me trip karta hai to kya karna hai sir
@eeebackbenchers2 ай бұрын
Check faulty history and check tripping value , if set value is low the increase it If cbct used then check power cable pass though it properly And last if ct secondly used then check ct secondary polarity
@PappukrSahu2 ай бұрын
Thank u sir 🙏🙏🙏
@eeebackbenchers2 ай бұрын
Thank you to also for appreciating the efforts .
@eeebackbenchers3 ай бұрын
L&T MTX Release Manual in pdf( Common for BCH BTX release & Elmeasure FLS release). corpwebstorage.blob.core.windows.net/media/35489/omega-matrix-releases-acb-users-manual.pdf
@ROHITKUMAR-uc9ju3 ай бұрын
Expert mode 1 ki programming batiye 12 and 13 point ki phase angle kitna rakna h
@eeebackbenchers3 ай бұрын
Hello Please note you don’t need to change any parameter in expert mode 1 and expert mode-2 You can keep 12 and 13 by default
@pankajs7973 ай бұрын
0com आ रहा है और ऑटो मे कोई भी कैपेस्टर ऑन नहीं हो रहा है क्या प्रॉब्लम है
@eeebackbenchers3 ай бұрын
Over compensation ( ocom) : means your power factor already in leading state hence it will not switch on any cap bank
@pankajs7973 ай бұрын
@@eeebackbenchers फिर तो अलार्म नही आना चाहिए ना
@eeebackbenchers3 ай бұрын
Programming/Setting manual of SIEMENS Multifunction meter PAC3220 /PAC3120. cache.industry.siemens.com/dl/files/307/109767307/att_1000707/v1/MAN_L1V30425208F-01_en_en-US.pdf
@gauravsharma-gc4cp3 ай бұрын
Sir my vfd faukt reset not done from keypad always use power on/off Plz help how to enable fault key for reset vfd
@eeebackbenchers3 ай бұрын
Thanks for comment check following setting Main menu /complete setting/command and REf./stop Key enable /All. Try this and second reason may be your fault is permanent hence it is not resetting from DI , in such case it will reset only via Drive power ON-Off. Please try if it work , please update.
@gauravsharma-gc4cp3 ай бұрын
Hello sir Mere pas same vfd hai but usme fault reset nhi hota key se Hmesha power on/off krna pdta h Plz help
@eeebackbenchers3 ай бұрын
Already revert
@dilkhushkumaryadav82103 ай бұрын
Sir atv 360 all putting but vfd not starting
@eeebackbenchers3 ай бұрын
Do one thing first Go and check io status and verify that all the IO are healthy or not as per command given. Second thing Check drive should be ready to start mode mean to say check there is no fault or any warning in this drive hmi will show red led. I think after check these points drive should be start if still not working please contact to Schneider’s customer care
@vickyrajput66023 ай бұрын
Ithd alarm aa raha hai
@eeebackbenchers3 ай бұрын
Current harmonics is higher than 25% You should you detuned reactor or do harmonics study on your plan for better result
Hi thx Gr8 inputs. Pl. advice can we test MTX3.0 MCCB using this test kit or we need communication module n display module n power pack also. Thx
@eeebackbenchers3 ай бұрын
Good question, as per my knowledge mtx3.0 connector not comes along with universal kit . Secondly there is separate testing kit for MTX AND ITRP Mccb release And last if you don’t have dedicated testing kit then you need communication module and display module.
@rajeshparmar69443 ай бұрын
Thx a lot for reply can you please share name model of testkit suitable for LSIG setting MTX 3.0 of MCCB. Thx n Regards Rajesh
@eeebackbenchers3 ай бұрын
@@rajeshparmar6944 Sir this kit is not available in open market ( mean to say not for sale) , only available for L&T Service team , if you want to test our MTX3.O you can contact with L&T ( CIC customer care)
@sudh304kapoor3 ай бұрын
I will check all the connector of universal kit if any possibility to check MTX 3.0 then I will check n update u If you get any chance to test then please check and inform
@skloverboy18624 ай бұрын
Sir aap class karvate hai kya
@eeebackbenchers4 ай бұрын
Thanks for comment brother , right now I don’t have such setup If you have any doubt on any topic feel free to comment I will try to resolve the same.
@MDTANVEERALAM-c7g4 ай бұрын
Thanks sir
@eeebackbenchers4 ай бұрын
Welcome
@JITENDRAKUMAR-zm9mv4 ай бұрын
Nlp fault ko kese htayenge
@eeebackbenchers4 ай бұрын
Basically NLP(No line power) hence it is a warning not fault. Secondly you can check following points 1. Check input supply 2. In drive parameter check main voltage ( in term of dc it should be around 600 V - actual line 400x1.5 ) calculate accordingly. And hard reset the drive If still problem presist call drive expert
@susantakar31934 ай бұрын
Frequency setting remote me kaise hota hai please help me
@eeebackbenchers4 ай бұрын
To do change frequency we have to programming accordingly and we can change frequency in remote via DI and AI
@inaa28234 ай бұрын
What is frame
@eeebackbenchers4 ай бұрын
Basically all the switchgear companies sell product frame wise Frame stands for standard dimensions If I say FRAME -1 , means all the rating ( 630 /800) which comes under FRAME 1 have standard size/dimension Similar for upper 3-4 rating frame 2 And then for upper rating frame 3 it also have 2 or 03 rating Rating range change as per manufacturer but concept remains same. Hope it’s clear now
@sanjeevrai31374 ай бұрын
Very nice. ❤❤❤
@eeebackbenchers4 ай бұрын
Thankyou so much sir for appreciating.
@AmitPatel-q2j4 ай бұрын
Schneider atv 600 programming
@eeebackbenchers4 ай бұрын
Noted , actually programming pattern is almost same in both the drives . If drive arranged some where I will make video.