Пікірлер
@daytonamann5618
@daytonamann5618 6 күн бұрын
The official method is to calculate any Zs because it is considered to be more accurate. IE it does not include parallel paths. If there is an RCD upstream, the test current is lowered, which means the result is not as accurate. When carrying out a "live" Zs test on a ring, you no longer have the "figure of Eight" cross-connection, so the readings will change as you measure at each socket. To summarise, the best way is to calculate Zs by adding R1+ R2 to the Ze. We also need to take into account the Electricity at Work Regulation 14 which states that you only work live when there is no alternative. Hope that helps. All the best for the AM2! SAM
@_mackenziie
@_mackenziie 7 күн бұрын
I have my am2 tomorrow, am I right in saying we only measure Zs for the ring and calculate the other readings because it’s a live test and we aren’t supposed to remove switches etc. whilst live?
@cglees
@cglees 2 ай бұрын
Great thank you
@TheDeno786
@TheDeno786 4 ай бұрын
This was helpful thank you .. i understand the cover shouldnt be off but that is obvious main concept was to prove isolation and how to do it
@daytona964
@daytona964 6 ай бұрын
Yes, that is correct. The Ze is the impedance at the board, but only if DB is at origin. The boards in the training establishment will include the internal wiring in the building, so are in fact a Zdb. An estimate of Pfc between two phases, is the highest current measured between phases and neutral and multiplied by 1.732 or root 3. To estimate the current if all three phases and neutral came together would be double the current between phase and neutral. Hope that helps, and do get in touch if you need further? Thanks for the question and happy testing.
@angelofranklin1
@angelofranklin1 6 ай бұрын
Good Vid thank you. Am I right in saying that at this distribution board the Ze is actually the Zdb and when advising about the current generally the x 1.73 is the fault for 2 phases and the x 2 is for short between all three phases ? please advise.
@GamerLozT
@GamerLozT 7 ай бұрын
couldnt follow. key now stuck up bum
@Death88758
@Death88758 7 ай бұрын
Quick and simple explanation thanks.
@rumpoh8039
@rumpoh8039 9 ай бұрын
YOU SHOULD BE BANNED. TEACHING BARE HANDS within inches of 3 phase terminals AND EXPOSING 'CROSS CHEST SHOCK HAZARD. YOU NEED TO BE REMOVED FROM TEACHING ANYONE.
@theholeymoley1
@theholeymoley1 11 ай бұрын
Very handy!
@daytona964
@daytona964 Жыл бұрын
The book suggests testing Phase to neutral(single-phase) and doubling the result to obtain a 3-phase value. Since making the video, I have started also measuring the Phase to earth which as you say, could be a higher reading as it is likely to include parallel paths. In other words, you are proceeding exactly as you would with a single-phase installation but doing 3 tests; one for each phase. This is useful if you have a single-phase board fed from the three-phase board. If this is the case, you would have all the info needed for PFC on the single-phase board, and for the three-phase PFC, you simply double the highest result. Let me know if you need further.
@user-cs9ch8ey9k
@user-cs9ch8ey9k Жыл бұрын
Could someone please put me right, I thought that the test carried out was not the the PFC as he only tested phase to neutral and not phase to earth which may have given a higher fault current which then would have been the PFC, it showed on the meter that only 2 probes was in use which was the line and neutral test probes, I do stand to be corrected.
@daytona964
@daytona964 Жыл бұрын
The book suggests testing Phase to neutral(single-phase) and doubling the result to obtain a 3-phase value. Since making the video, I have started also measuring the Phase to earth which as you say, could be a higher reading as it is likely to include parallel paths. In other words, you are proceeding exactly as you would with a single-phase installation but doing 3 tests; one for each phase. This is useful if you have a single-phase board fed from the three-phase board. If this is the case, you would have all the info needed for PFC on the single-phase board, and for the three-phase PFC, you simply double the highest result. Let me know if you need further.
@rizgar8121
@rizgar8121 Жыл бұрын
Dear Sir, the one-phase or three-phase isolation procedure (sequence) should be in more detail, this process you are explaining should be for everyone , you should explain the sequence of testing like Broun and Black, Broun and Grey, Black and grey, or L1 and L2, L2 and L3, L2 and L3, this very important for the beginners, and I hop you accept my comment.
@modeen3453
@modeen3453 Жыл бұрын
Wait do we lock off first? I thought we do that at the end once we proved it was isolated?
@Rossisearle
@Rossisearle Жыл бұрын
Great VT.. coming to do my 2391 in June with you guys
@TheZaaaander
@TheZaaaander Жыл бұрын
Breakers off? Shouldn’t they be left on
@uplightuk8924
@uplightuk8924 Жыл бұрын
Why? You’re testing out the top of the breaker so makes no difference if the breakers are off
@edgaraskairiukstis5348
@edgaraskairiukstis5348 Жыл бұрын
Out of interest what was the size of the breakers to compare the pfc calculations against? Otherwise a faultless video.
@Raj-ul9my
@Raj-ul9my Жыл бұрын
Dont use 500v in real life, it will fry up electrical equipment in a domestic home including loads and stuff, use 250v then do calculation as if it was a 500v test. This way you dont need to remove light bulbs and stuff
@ejazahmad6004
@ejazahmad6004 Жыл бұрын
Sir please send your whatsapp number
@wizardwithguns1
@wizardwithguns1 Жыл бұрын
Thank you!
@linossinkala7840
@linossinkala7840 Жыл бұрын
Thankyou sir ,wonderful
@tongtawee2514
@tongtawee2514 Жыл бұрын
Thank You your video make me confident to do Ze/PFC testing .
@calebbrookes7896
@calebbrookes7896 2 жыл бұрын
Do you have Todo it in the board or can you do it in any socket in the ring circuit?
@stevemullen3666
@stevemullen3666 2 жыл бұрын
Title is a bit misleading, I was hoping to see the test of a Radial circuit, not a Ring Final Circuit.
@ef7480
@ef7480 8 ай бұрын
It is a radial circuit as he only disconnected one line conductor (R1) and also you can have more than one socket outlet on a radial but the R1+R2 readings will rise and fall depending on which direction you test whereas a ring circuit should be the same reading at each socket outlet.....but you've probably got this by now.
@crashcenter76
@crashcenter76 2 жыл бұрын
Thanks very much I learn more from visual revision than I do the books so this was very helpful.
@shiamjad
@shiamjad 2 жыл бұрын
Thanks
@shiamjad
@shiamjad 2 жыл бұрын
Thanks for explaining it well
@Raj-ul9my
@Raj-ul9my 2 жыл бұрын
Great but switch off and lock-off first and always prove that your tester is working before and after use if not it might be faulty.
@tspirit99
@tspirit99 Жыл бұрын
Why does that matter as you are literally standing at the db?
@entergenericedgynamehere8751
@entergenericedgynamehere8751 Жыл бұрын
He did prove his tester, he proved it on the known supply
@jonnyprice2618
@jonnyprice2618 2 жыл бұрын
Maybe the ze would of been within .35 if you had nulled your leads 🤦🏻‍♂️🤣
@drpantastic1969
@drpantastic1969 2 жыл бұрын
Not good example to start with the cover off at least turn off first
@drpantastic1969
@drpantastic1969 2 жыл бұрын
What happens when the target figure is not met but connection are correct.r1.rn crossed?
@martinbarrett831
@martinbarrett831 2 жыл бұрын
Should show switching on meter
@ef7480
@ef7480 2 жыл бұрын
Always some teachers that can explain processes behind the subject better than others.
@wagabira
@wagabira 2 жыл бұрын
Thanks for the video but shouldn't you have tested your testing equipment before estarting ? What if you tester was faulty ? 🤔🤔
@mrpoo7651
@mrpoo7651 2 жыл бұрын
He did. He used the known source of supply 2:00 - 2:15 to test that the voltage indicator is working correctly
@wagabira
@wagabira 2 жыл бұрын
Yes he did, I just don't know if I would pass the course doing that way. I was told to test your tester with a proving unit before 🤔🤔
@mrpoo7651
@mrpoo7651 2 жыл бұрын
@@wagabira you can do both, prove it with the proving unit or a known use of supply. Both are recognised in city and guilds
@wagabira
@wagabira 2 жыл бұрын
@@mrpoo7651 , thanks 👍🏼
@wagabira
@wagabira 2 жыл бұрын
Good to know 👍🏼
@elabuelito85
@elabuelito85 2 жыл бұрын
DONT AGREE. Measuring phase to neutral shortcircuit is not going to give you three phase PFC even if you multiply by 1.73 or 2. You better have a look at schneider cahier technique 158 and compare the formulas for all shortcircuit types. you will see that you need to measure between two phases and multiply x1.16. Many mft meters support measuring between phases even if you select L-N test. For example fluke 1654B. The only place you could do that aprox x2 times (no x1,73) is subject to the neutral being the same size and length as the live, all the way upstream and if you are far away fron the transformer so the transformer windong impedance is much smaller than the cable. Things that you will never be 100% sure. Hope this comment helps you. And if you dont believe what i said and dont know how to check, think about it. If it was so easy as doubling it up you would get that info from the meter when you are doing LN tests.
@rossmurdoch1886
@rossmurdoch1886 3 жыл бұрын
Sorry no explanation of why the readings differ? No mention of Max Zs to prove readings are suitable? No mention in fact relating to disconnection times?
@Gameplay686
@Gameplay686 2 жыл бұрын
He actually mentioned all these things LOL
@willmurphy6663
@willmurphy6663 3 жыл бұрын
Thanks for this, but you need to show how to set the meter, and would be better using a more common megger
@ef7480
@ef7480 2 жыл бұрын
More common?
@mutazhasan5405
@mutazhasan5405 3 жыл бұрын
Thank you for this Video My question is if this test is Carried out for main low voltage panel with 2500 A breaker , so the main breaker should be off ? Right ?? And we will measure for the incoming point of the breaker which is live ? We did this as a safety procedure or just to take the exact reading for pfc and ze ?
@gregsmith5553
@gregsmith5553 3 жыл бұрын
Hi thanks for the Video. Can you tell me please why you had the Main Breaker turned off when doing your PSCC test? surely the main switch and breakers should be on ?
@MK-wf1eg
@MK-wf1eg 3 жыл бұрын
He tested it at the other pole of the breaker that's live. The installation beyond the main breaker is dead, before the main breaker its still live
@gregsmith5553
@gregsmith5553 3 жыл бұрын
@@MK-wf1eg I know that but to make sure you are getting all the Parallel paths the main switch and breakers should all be on.
@daytonamann5618
@daytonamann5618 3 жыл бұрын
Hi, The main switch is should in the "OFF position when carrying out a test of PFC because the we are looking for the worse case scenario: when the resistance is at it's lowest and the current will be at the highest. If the switch was on, you could theoretically get voltage drop which would change the reading. When the switch is off, you are still including parallel paths as long as the earthing conductor and all the extraneous-conductive-parts are connected to the MET via the equipotential bonding. Hope that helps..
@gregsmith5553
@gregsmith5553 3 жыл бұрын
@@daytonamann5618 So for the current to be at its highest you would need the main switch on! With the main switch off their is no current.
@daytonamann5618
@daytonamann5618 3 жыл бұрын
@@gregsmith5553 No; The bottom of the switch is live at all times, so the current is measured at that point. The installation is isolated and so there is no voltage in the actual system when the switch is off!
@persian_warrior1
@persian_warrior1 3 жыл бұрын
It was better if you show what you change the function on the meter to? Thank you
@danielsingh7211
@danielsingh7211 3 жыл бұрын
Great video
@simonoliver5327
@simonoliver5327 3 жыл бұрын
Thank you
@danielsmith4114
@danielsmith4114 3 жыл бұрын
I couldn't see what you were probing on to, in order to conduct the test and you didn't tell the viewer... ! Terrible video and a poor choice of cameraman.
@Gardenworld831
@Gardenworld831 3 жыл бұрын
Do some more videos I watch alot of videos and your presentation is very good
@Robert-ts2ef
@Robert-ts2ef 3 жыл бұрын
Could you please answer my question below to clear up the confusion for me which is why do you not get zero ohms between neutral and earth in the consumer unit if the neutral is ultimately connected to earth back at the supply transformer?
@daytonamann5618
@daytonamann5618 3 жыл бұрын
Hi Bernard, The neutral is isolated on the single-phase, so there is no connection between N-E when the isolator is switched off. You will get a short on insulation resistance in the 3-phase board on a TN system as the neutral is bolted direct to the neutral bar and so you have to then remove it to complete the test. Let me know if you need further?
@Robert-ts2ef
@Robert-ts2ef 3 жыл бұрын
@@daytonamann5618 cleared up my confusion, thanks.
@jaydenplaysguitar3896
@jaydenplaysguitar3896 3 жыл бұрын
Further explanation on how parallel paths lower impedance and raises the PFC would be great thanks
@proactivetechnicaltraining4431
@proactivetechnicaltraining4431 3 жыл бұрын
Hi Jayden thanks for the comments we discuss parallel paths during the associated classroom training courses
@Robert-ts2ef
@Robert-ts2ef 3 жыл бұрын
Excellent instruction but I have one question: The star side of a delta/star supply transformer has the neutral connected to the central point of the star which is earthed so why would you not show zero ohms from neutral to earth, or am I missing something? Thanks
@ayarottilsandeep545
@ayarottilsandeep545 3 жыл бұрын
Sir, that's a very good video, but I wish to know , how to select the applied voltage for single and 3 phase conductors. Is it that the the voltage applied must be twice the RMS value of nominal operatinal voltage??? Kindly reply
@Mr.Q852
@Mr.Q852 3 жыл бұрын
Selv-pelv systems= 250v 0.5ohms Up to 500v systems = 500v 1.0ohms Above 500v systems =1000v 1.0ohms
@paulwilliams8104
@paulwilliams8104 3 жыл бұрын
Test voltages are taken from the regs and are dependant on the circuit to be tested rather than RMS of supply. As a rule in domestic application and on standard circuits on 3 phase, that value is 500V. However to ensure you are testing IR appropriately for each circuit reference should be made to BS7671.
@hughjadiel2999
@hughjadiel2999 3 жыл бұрын
sorry to be off topic but does someone know of a way to log back into an Instagram account..? I somehow forgot the login password. I would appreciate any assistance you can offer me!
@ayarottilsandeep545
@ayarottilsandeep545 3 жыл бұрын
@@hughjadiel2999 isn't there an option of" Forget password ".there should be, I believe you can get the One Time Pass word on the registered number in Instagram. Please check, or please try
@kristianguillermo2795
@kristianguillermo2795 3 жыл бұрын
@Hugh Jadiel Instablaster ;)
@iraqviva7670
@iraqviva7670 3 жыл бұрын
What is the maximum ze we should not exceed
@proactivetechnicaltraining4431
@proactivetechnicaltraining4431 3 жыл бұрын
Depending on the earthing arrangement then for TN-C-S Ze must not exceed 0.35 ohms, for TN-S Ze must not exceed 0.8 ohms. For TT it can be as much as 200 ohms.
@RedaReda-uk9lm
@RedaReda-uk9lm 3 жыл бұрын
I watched all your videos