Hi, is it a fail if you put a 13 amp fuse in. We was given two 13 Amos and one 3 amp fuse. And no specification.
@headsup4sparkies2 ай бұрын
Typically a heating system would need the fuse connection unit (FCU) to be fitted with a 3 Amp fuse. FCU’s come with a 13 Amp fuse as standard
@joeraby13703 ай бұрын
Hi very helpful video! I have my am2 coming up and just wanted to know at what stage do I carry out the phase rotation test at the main switch? The motor and commando are fine as they can be done with everything closed up and on but from what I've seen the test of the main supply seems to come after RCD and functional but by that stage you would have the board cover back on?
@headsup4sparkies2 ай бұрын
My understanding is that the phase sequence test is only carried out at the motor terminals as a functional test.
@joeraby13702 ай бұрын
@headsup4sparkies thanks for the reply I did also have to do the phase sequence of the main supply. I passed the AM2 anyways
@johnwestern2 ай бұрын
@@joeraby1370Thanks for the feedback - good to know. Well done for passing your AM2 👏🏻🏅- Now you’re qualified, your skilled journey begins - keep striving for the best as our industry is ever changing.
@snipercwf3 ай бұрын
The best steel conduit tutorial on KZbin.
@headsup4sparkies3 ай бұрын
Thank you
@mohammadshirifeshki40183 ай бұрын
Thank you.
@philbayman99644 ай бұрын
Another awesome video. Love them. Thank you!
@philbayman99644 ай бұрын
Awesome video and I love how you do your animations. Brilliant top tips … very helpful! Thank you!
@headsup4sparkiesАй бұрын
🙏
@chandsharif35054 ай бұрын
Wow its a virtual learning platform. I hope, there are lots of things can be learnt from your video. And waiting for trunking work how to bend 90, 45, Bridge and so on
@azadsmail85 ай бұрын
Hi nice vid but I noticed that the highest reading is PEFC 950.3 this one should be doubled and recorded not the PSCC am I right? THANKS
@headsup4sparkies4 ай бұрын
Hi … When testing between Line and Neutral (PSCC), the voltage potential is 230V .. we double this to allow for the PSCC between Line conductors as these would have a potential of 400V. The maximum potential to earth (PEFC) is 230 so therefore is not doubled. You only double the highest PSCC value.
@alanmarriott92165 ай бұрын
How did you know where on former the 2nd mark had to go to bend?
@headsup4sparkies2 ай бұрын
All measurements when forming conduit, should progress from one end. The conduit is always placed in the former with the “measured end” under the stock. Then each mark should line up on the former at the “point of bend” which is were the conduit and former separate prior to bending. Some people do mark the formers, but this mark is unreliable as it alters depending on which hole you place the stock on. The exception to this is where the mark on the conduit is for the “back of bend”. Then you would follow the instructions as shown in the video.
@mykegyver761010 ай бұрын
You should voice an animated movie character. (I am not joking)
@captainkidd181110 ай бұрын
Art
@nevermind824 Жыл бұрын
Nice tip about scoring the conduit for the thread line.
@headsup4sparkies10 ай бұрын
Works for me 😀
@SigmaPotato327 Жыл бұрын
very nice
@lewiswebb1843 Жыл бұрын
Thanks mate, got my am2s this Monday and this is spot on 👍🏻
@pvegod14846 ай бұрын
Did you pass it mate? I’ve got mine in a couple week bricking it
@lewiswebb18436 ай бұрын
Yea passed 1st time mate 👍🏻 I’ll be honest, if your here looking up videos to pass then you’ll probably be one of the guys that will pass either 1st time or on a return attempt 👍🏻 good luck 🤞🏻
@jonathan_ansell Жыл бұрын
christ ! - kill the music and the avatar... then you've got a great video !
@monikacieminska5380 Жыл бұрын
Fantastic video. Thank you 👌😀
@headsup4sparkies Жыл бұрын
Glad you found this useful 😀
@AndrewBaker-z9r Жыл бұрын
Excellent video as always, thank you.
@headsup4sparkies Жыл бұрын
🙏 Thank you .. hope it has helped ..
@anowerhsahed1091 Жыл бұрын
Very good work
@Rossisearle Жыл бұрын
helpful but surely that Zdb your say is Ze because the is the 3 phase dno supply? is zdb would be at 2nd or 3nd distribution circuit ? ASKING
@headsup4sparkies Жыл бұрын
Hi … If the board is at the origin of supply - then Zdb and Ze would be the same. Ze recorded on certificate and Zdb recorded on schedule of test results. If there is a sub main between the origin and the board under test .. then Zdb is measured at board with earth disconnected - and Ze from origin recorded on the certificate.
@headsup4sparkies Жыл бұрын
The distribution board at the origin supplying the sub main, would also record this supply’s Zs on on it’s own schedule of test results, taken in the same manner but with the earth connected.
@headsup4sparkies Жыл бұрын
The board in the video is assumed not to be at the origin of supply … Hope this helps 👍🏻
@Rossisearle Жыл бұрын
@@headsup4sparkies right... So like a three phase distribution circuit?
@headsup4sparkies Жыл бұрын
Yes … we call them “Sub-Mains” when we distribute the supplies from DNO to distribution boards… and the circuits from there are “final sub-circuits” supplying current using equipment without further distribution.
@glenngray3351 Жыл бұрын
Hi I am having a few issues on identifying the types of wiring and reference method on the Generic schedule of circuit details. Can help or advise please?
@headsup4sparkies Жыл бұрын
This can be simple - or complex, depending on the variety of methods employed on the route. You can select the most used method on the route / the method with most detrimental effect .. or so on. The inspector should use engineering judgement to decide … this link to IET - Supporting BS7671 Appendix 4 .. might help electrical.theiet.org/media/1617/appendix-4-of-bs-7671.pdf
@detroutspinners9933 Жыл бұрын
Brilliant video, really appreciate the time taken to animate the test sequences as well. Helps to visualise what you’re doing so much better!
@headsup4sparkies Жыл бұрын
Thank you 🙏.., I’m glad you found this helpful 😀
@sports872 Жыл бұрын
Enjoyed the video. Would like to see more testing videos if possible.
Great video but how do you know when doing the 1st and 2nd bends on set where bend starts on former please!?
@headsup4sparkies Жыл бұрын
When the conduit is resting in the former, the bend will be at the point where the conduit and former separate (underneath) … I generally place my little finger underneath to “feel” where that point is - and try to get the mark in the conduit at that point.. However - you don’t have to get it exactly right, as you can simply adjust the depth of the set. To add depth, put a little more in each bend. To decrease the depth, take a little out of each bend. Making sure to adjust the existing bend and NOT putting and additional bend in. Some people attempt to “mark” the former on top at the “point of bend” but you often have to change the position of the “stock” to get the measured conduit mark where you need it - as soon as you do this, the mark on the former will now be in the wrong place. Try not to over think it - bending conduit is more of a knack than an exact science. The ability to manipulate the bends neatly is the main skill. Practice makes perfect 👌🏻
@Ste2023 Жыл бұрын
This brings bk memories of browsing.
@VM-MV2 жыл бұрын
thanks!! very useful video!
@headsup4sparkies2 жыл бұрын
Thank you …
@KeithWilliamMacHendry2 жыл бұрын
Excellent detail & instruction, thank you. 🙏🏻
@skabbymuff1112 жыл бұрын
Very informative, thank you. Subscribed.
@santhaariyarathna22622 жыл бұрын
Super
@MomentsWithBrandon2 жыл бұрын
Loved this vid, super simple and easy to understand compared to others, hope you release more content
@headsup4sparkies2 жыл бұрын
🙏
@gustavocervantes54352 жыл бұрын
Great video
@headsup4sparkies2 жыл бұрын
Thank you 😀
@MultiOutdoorman2 жыл бұрын
Fabulous presentation, excellent visuals too !.... If i might just contribute ? In my view, the purpose of the solar hot water system is to reduce the need for energy consumption ! The reason I mention this is because the solar needs to operate independently from the boiler . The D.H.W timer should be programmed to schedule a periodic " top up" of the storage tank to overcome any shortcomings of the solar performance during dull weather, and reduce legionella by bringing the water temperature up to a suitable level. My system for instance, runs twice daily to address water & / or heating, based on the Honeywell programmer settings. I also use an S-Plan too, using my combi boiler to provide heat, triggered by the room / cylinder stats leading eventually to the output of the microswitch in the zone valve(s). My kitchen hot tap still runs from the combi directly though ! It has worked a treat for about 6 years and i find the boiler hardly needs to run between May and end of September due output of the 8 square meters of thermal solar panels on our roof. The boiler is still timed to come on but the cylinder stat is usually open by that time so no heat is required. Winter time is another story ... but the boiler still only needs to heat lukewarm water already warmed in the bottom of the cylinder. I often wish i had a second tank in summertime as it often shuts the pump off and stagnates until somebody takes a midday shower. A "destrat" pump and a few controls help to maximise efficiency. Brill animation ... Thanks for sharing.
@headsup4sparkies2 жыл бұрын
Thank you very much for your contribution… this particular system is aimed at the AM2 requirements .. You are clearly experienced with these systems. From my own research, the only thing I can be sure of is that there is no such thing as a “typical” system.
@davidshanahan36932 жыл бұрын
Excellent tutorial.
@headsup4sparkies2 жыл бұрын
Thank you
@Roq-stone2 жыл бұрын
Very clear and easy to follow demonstration
@moali61962 жыл бұрын
Great video well informed
@17italyman2 жыл бұрын
where you had the running coupler and lock ring can you not just measure say half of the coupler so that when you tighten up the running coupler with the end you wont have any tread showing ?
@headsup4sparkies2 жыл бұрын
I’m afraid not .. the running coupler needs to run from one piece onto the next piece. Therefore it will always leave some thread behind it. The way it’s shown leaves half the thread on the existing piece, and puts half the thread on the new piece. Therefore leaving half the thread exposed on the back of the existing piece, with both ends electrically (earthing) and mechanically secure.
@17italyman2 жыл бұрын
@@headsup4sparkies ah yeah makes sense now thank you
@17italyman2 жыл бұрын
@@headsup4sparkies also the nipple part you threaded into the box is this something for the am2 that they will provide ?
@frog.n.toast29382 жыл бұрын
great video. keep posting
@fraserreid7192 жыл бұрын
Wasting 4 inch of pipe I would get battered by my tradesman back in the day 😂
@headsup4sparkies2 жыл бұрын
😂🤣
@highgatehandyman64792 жыл бұрын
Good lesson
@2010Mrturk2 жыл бұрын
I’ve hit subscribe but only 4 vids available. Can you do a vid on the DOL pls ?
@headsup4sparkies2 жыл бұрын
Actually working on Contactor and DOL video now .. once it is launched on the other platform it will be on here too
@TheGOLDRUSH8172 жыл бұрын
Where can I find that bending station
@headsup4sparkies2 жыл бұрын
Pretty much any UK electrical wholesaler … here’s a link from a quick search www.toolstop.co.uk/irwin-hilmor-el32-conduit-bending-machine-with-vice-and-20-25-32mm-formers-t113100d-p80043/
@jeremykemp37822 жыл бұрын
very good
@Tom-fu9cr2 жыл бұрын
great video. really useful
@albertwesleyable2 жыл бұрын
Came for the conduit, stayed for the music 🔥
@headsup4sparkies2 жыл бұрын
😂 … licence free rock n roll 😎
@xiakarimLive2 жыл бұрын
What is the name of this bender? Where can I buy it from?
@headsup4sparkies2 жыл бұрын
There are different names, but I think the most common in the UK is made by Hilmor .. here’s is an example link from a UK wholesaler .. www.tlc-direct.co.uk/Main_Index/Conduit_Steel_Index/Conduit_Bender/index.html?ad_position=&source=adwords&ad_id=414374435730&placement=&kw=&network=g&matchtype=&ad_type=&product_id=&product_partition_id=&version=finalurl_v3&gclid=Cj0KCQiAwqCOBhCdARIsAEPyW9lmDNmlUux6qJls7H9S6mp5RPNTMG9YdOS4OYPuVNj5bmCCiSHvCiQaAn33EALw_wcB
@williamcerdasbonilla2692 жыл бұрын
Exelente video amigo soy electrisista desde costa rica.... Yo para aser cambios de direccion o offset.. Tengo mi forma y se trata de tomar medida usar calculo con el teorema de pitagoras y centro marca dobladora y sale super biem amigo
@headsup4sparkies2 жыл бұрын
Gracias por tu bonito comentario. Me alegro de que te haya gustado mi vídeo. Diferentes naciones tienen diferentes formas de compensar. Creo que Estados Unidos también usa cálculos de Pitágoras. En Inglaterra, nuestras dobladoras no son muy precisas, por lo que las marcas fijas no funcionan tan bien para nosotros. Este método es más común en Inglaterra. Es fantástico para mí recibir mensajes tan lejos de mi casa. Muchas gracias.