I was wondering if changing my Generac battery every 2 years was too often? Interstate Batteries recommended changed every 2 years to be safe. I do run the generator every week for 5 minutes to keep everything lubricated and conditioned, battery included. Now, after watching your video, I will be changing my Interstate Battery every 2 years. The one time the generator will not start will be the time it is needed. My luck, a tropical storm or severe cold. "Better to be safe than sorry," as the old saying goes.
@duthiepowerservices6 ай бұрын
We're glad you found our video helpful! "Better safe than sorry" is definitely an adage by which we abide.
@RMalai6 ай бұрын
Hello, should the generator be locked-out during the purification process? if yes, why? if not why not. thank you
@duthiepowerservices6 ай бұрын
It is advisable not to run the unit during the fuel tank cleaning or polishing service. During the cleaning process, the diesel fuel is agitated while extracting water and debris, causing any existing contaminants in the tank to become suspended and sucked into the engine's fuel supply. This poses a significant risk of clogging the filters or causing damage to internal fuel system components. It is best to keep the unit in the off position or locked out during any fuel tank maintenance procedures. After completion, it should also be kept offline for an additional 30 minutes. This will allow any residual particulates that may have been missed during cleaning to settle back to the bottom of the tank, minimizing potential risks to the system.
@RMalai6 ай бұрын
@@duthiepowerservices Wow! thank you for responding with clarity and reasoning. Very valuable answer.
@matthewellis30048 ай бұрын
Thank you. Wondering what is involved with the decommissioning and transporting of a 200KW Diesel Generator form California to Washington please? Thanks for the info.
@duthiepowerservices8 ай бұрын
Thanks for watching! Your question is best answered by a professional who performs an onsite assessment, but here are a few important steps to take: inform AQMD and/or the City of removal, drain all fluids including fuel, oil, and coolant, disconnect and /or remove batteries, disconnect all conductors from generator and ATS (depending on whether the ATS is staying or going), arrange truck transport, installation and permitting in new location. Keep in mind, it can also be difficult to move an older (used Generator) and get it permitted, depending on the location. We hope that's helpful!
@DeetjensMaintenance8 ай бұрын
Would exercising weekly on a 15-30 min basis be okay on Propane fueled Generator?
@duthiepowerservices8 ай бұрын
It's advisable to run the equipment long enough to reach engine operating temperature (with coolant temperature approaching 180 degrees Fahrenheit. For specifics on your engine, refer to your engine's operation manual). We recommend all customers run their equipment for at least 15 minutes weekly. This will exercise your unit for 13 hours per year just for monthly testing purposes. It's essential to adhere to the guidelines outlined in your operating permit, however. A longer runtime is more beneficial for the longevity of the unit by making sure all the internal components are lubricated with engine oil, it also ensures a fresh charge of fuel in the line to assist in starting, plus it helps you catch issues with your equipment in between power interruptions. For professional assistance, don't hesitate to reach out to us at www.duthiepower.com. Thanks for watching!
@jasonpalmere695 Жыл бұрын
can this process remove rust that formed on the bottom of the tank?
@trytogo Жыл бұрын
HELPFULL INFORMATION THANKS
@stephenlomo27382 жыл бұрын
Pls can one changeover switch be connected to 5 or more metres
@toseeqahmad72423 жыл бұрын
So please reply. Thank you
@toseeqahmad72423 жыл бұрын
Sir if we use 4 generators and 1 utility circuit and the standby is turned on step by step then what is the procedure and after running one generator in standby the other generator has to be run when the utility comes and so on The rest of the generator is also on, ie after running one generator, the other one will run. When the first one does not work, what will be its connection?
@kilogrammountain34533 жыл бұрын
So boring and its not a full detailed explanantion
@ivan328633 жыл бұрын
How to transfer. The mts
@ernestwalden38943 жыл бұрын
Wow weekly? I normally run it 1 every 2 months. Guess I better get mine running. But once a month be ok or why every week. Mine is a 9400 running watt Its like pushing a car around LOL
@Pk3_Garage3 жыл бұрын
I believe the generator he's referring to is a standby generator. Portable generators, should be exercised every month or two., for about 15 to 30 min. under load.
@robertlane66754 жыл бұрын
Very informative!
@carlwilson86727 күн бұрын
Not!
@nickcats91715 жыл бұрын
Does it turn on automatically when temps are low or do you turn it on manually? Or is it always on all year around?
@e_nh5 жыл бұрын
if the both power source are genertor ?? Then How ATS Work on two generator without any time delay during switching process.
@e_nh5 жыл бұрын
@@duthiepowerservices thank you for your feedback. But as it possible if source second should start 5 mint or so before source 1 turn off by using timers or through programming . Do you have any idea ???
@yahushaking43676 жыл бұрын
To restore the breakers do I need to shut down the ats?