This type is generally used in daikin and macqualy. But other manufacturers are using the same concept.
@TheChillerGuysHub2 күн бұрын
@@UATechnicalSolutions thanks brother!
@sonusomarajan17356 күн бұрын
How check igbt ( York Yvaa )
@luckywetland7 күн бұрын
Thank you
@UATechnicalSolutions7 күн бұрын
Welcome
@MuhammadIrfan-wl7gn8 күн бұрын
I need Trane RTAF level 4 setting details. Please do the needful
@sadikthebasicmaster46899 күн бұрын
What is the standard odp?
@UATechnicalSolutions6 күн бұрын
For carrier 06T compressor at least 650kpa. It is measured by subtracting suction pressure from oil pressure. If you are checking the oil filter performance than the difference between discharge pressure and oil pressure should not be more than 100kpa
@UATechnicalSolutions6 күн бұрын
For carrier 06T compressor at least 650kpa. It is measured by subtracting suction pressure from oil pressure. If you are checking the oil filter performance than the difference between discharge pressure and oil pressure should not be more than 100kpa
@sadikthebasicmaster46895 күн бұрын
@@UATechnicalSolutions 30xa same?
@shaikjuned71213 күн бұрын
Man humble request Can you make a video for 30xa and 30xb chiller control wiring diagram how to read
@UATechnicalSolutions13 күн бұрын
Sure will be uploaded and notified to you.
@shaikjuned71213 күн бұрын
Man your amazing ❤️
@miyankaja25718 күн бұрын
Can you please tell the 30xa chiller how to check the parameters and what is the purpose example delta T and oat
@UATechnicalSolutions16 күн бұрын
Please click the link for the requested video ( 30xa chiller how to check parameters and operate the display) kzbin.info/www/bejne/i5aaZXypnbmCn6M
@UATechnicalSolutions16 күн бұрын
Delta T is the difference in between Entering and leaving water temperature. on which chiller performance can be assessed. most commonly if the chiller is working at 100% and the delta T is 5 degree Celsius its consider as good chiller performance
@UATechnicalSolutions16 күн бұрын
OAT is short for out door air temperature ( which is the ambient air temperature)
@raneeshpp4u22 күн бұрын
How to solve low temperature (W66) warning alarm? same vfd
@thamban.kkelambeth165923 күн бұрын
very nice explanation for new HVAC TECHNICIAN Thank you
@arianagandhi763425 күн бұрын
thanks
@DJ.ANKIT.KASHYAP.SAIDPURKHURD25 күн бұрын
Sir smd jinar ka kese pta kre Kitne volt ka hai
@UATechnicalSolutions25 күн бұрын
Smd per uska model number likha hota hy. Wo model number google per dall kar uska data sheet main sub detail mil jay ga. Jaisa k volt . Amps . Ac ya dc
@albyben7Ай бұрын
@UATechnicalSolutions, could you help me for 30HXC? I have a Moxa 2-wire RS485 to USB converter, and the Prodialog 4 basic board has a CCN board. Will it communicate with RS485?
@UATechnicalSolutions29 күн бұрын
Yes it supports the rs485
@joshuamorris2784Ай бұрын
Very useful, what if you didn't have a diffuser? Asking in relation to centrifugal propeller design for aircraft application.
@UATechnicalSolutionsАй бұрын
Air Craft engineering is far different than HVAC cant say anything for air craft
@Rodj12341Ай бұрын
I noticed that DIP switch #3 was off on these, which relates to the communication speed to the indoor units. If this was a new install and all of the indoor units are 4th gen units, how come you have DIP switch #3 off? Having it on will allow the units to communicate faster and more reliable. If needed, I can give you the procedure for setting it as it has a few steps involved to fully switch it to gen 4 mode.
@manudarpan9849Ай бұрын
That's really a good video with this video I easily understood centrifugal compressor....thank you so much for this video ❤
@wesameldinelshafey3032Ай бұрын
Great 🎉
@nigelchew1890Ай бұрын
Whata wrong with using the terms anode and cathode?
@UATechnicalSolutionsАй бұрын
Both terms can be used. There is nothing wrong. Simple terms make it easy to understand for beginners. Our target is to convey the knowledge in easiest possible way . Thanks for your comment
@nigelchew1890Ай бұрын
@@UATechnicalSolutions OK.
@abushahma1857Ай бұрын
Thanks 👍 for information
@UATechnicalSolutionsАй бұрын
Welcome
@abdulkarim-ku2tgАй бұрын
Thank you for the video, can we adjust the superheat for the outdoor
@UATechnicalSolutionsАй бұрын
Sure it can be adjusted . We will uploaded the video regarding the request
@Sohelkhalifa-l7kАй бұрын
Hi I can't connect to my chiller via winloader can you help me to get the connection manager app
@UATechnicalSolutionsАй бұрын
Sorry connection manager is not available with us
@sujithasanka7384Ай бұрын
Thank you.❤
@UATechnicalSolutionsАй бұрын
Welcome
@Sohelkhalifa-l7kАй бұрын
Thank you very much. I would like to know how to connect the main board to the computer and how to configure the Prodialog controller for Chiller Carrier 30G/30H.
@UATechnicalSolutionsАй бұрын
You will need rs485 to usb converter . To connect with computer. Also the video is sent to you via mail on how to install and connect . The software for the board is not available with us . Although if you have another chiller with the same model you can copy the software from there and install on the new display panel.
@muzaffar1982Ай бұрын
30xa chiller, problem generate suction pressure transducers alarm again and again ,after remove another fix but same problem generate,what cause please tell me
@UATechnicalSolutionsАй бұрын
hi, 1:Check the transducer cable if it is good and not having any partial contact. 2: check the connector on TCPM board re-terminate the wire in the connector and clean the pins on board. if the problem still exist change the TCPM board.
@muzaffar1982Ай бұрын
@@UATechnicalSolutions thank you sir very very for reply and support me
@muzaffar1982Ай бұрын
Sir now not coming suction transducer alarm but now generate other alarm like low ecnomizer pressure suction valve closed,once again reset after 10 second shutdown system A , compressor, system B compressor normally working
@naweedkhan7941Ай бұрын
Hello dear can you tell me which bearing number use in this compressor??
@MuhammadIrfan-wl7gnАй бұрын
Please upload the video how to programme Mother board.
@UATechnicalSolutionsАй бұрын
kzbin.info/www/bejne/l3m3YZStlLGcms0 Please click on the above link to watch the video on how to install the Program for All boards in Carrier 30XA and 30GX chiller
@MuhammadIrfan-wl7gnАй бұрын
The videos are so helpful. I would like to ask , is SCPM board need programming or no.
@UATechnicalSolutionsАй бұрын
Sure SCPM Board has a program. in the market its available with and without program installed. if you have SCPM with installed program than you just need to set the DIP switch settings and it will work. But if you have SCPM without program than you need to install the software first.
@sonusomarajan1735Ай бұрын
Plz upload chiller video carrier 30xa or York Yvaa/yciv
@UATechnicalSolutionsАй бұрын
Sure
@kamranhasnain5310Ай бұрын
Which parameters will be involved in COP of R-134a calculation ? When this refrigerant is used in the chiller i.e., Condenser temperature and pressure or Evaporator temperature and pressure???
@UATechnicalSolutionsАй бұрын
Please share your email address or you can contact us on [email protected] to have the answer of your question.
@aripakasanjaysagar2704Ай бұрын
Thank u for the best video
@UATechnicalSolutionsАй бұрын
Welcome
@JDJohnston9906753Ай бұрын
"How to remove AC condenser fan motor bearings with tools you don't own and then not put it back together again"
@UATechnicalSolutionsАй бұрын
here are some basic Tools we recommend to have before performing bearing replacement of any motor or pump. 1: Bearing Puller 2: set of mechanical screw driver 3: shifting spanner 4:snap ring plier 5: steel rod shell 6: hammer 7: anti rust
Very informative video… sir pls upload a video regarding Trane chiller RTAC Communication how it’s works.
@UATechnicalSolutions2 ай бұрын
Thanks, sure will be uploading soon
@manishgupta-ff4oj2 ай бұрын
Thank for nicely demonstrating.
@UATechnicalSolutions2 ай бұрын
You are welcome!
@hectortorres5422 ай бұрын
Thank you for the video
@UATechnicalSolutions2 ай бұрын
You're welcome
@sujon31302 ай бұрын
Pleaee Mark the gas suction & Discharge point, & how does conimizer work
@UATechnicalSolutions2 ай бұрын
Thanks for your request. Click on the link for economizer function and operation. kzbin.info/www/bejne/j5ynZptjmtl9hs0si=IG83UbrMgWBuLvuU Share your email address for the suction and discharge point explanation
@IgorBond2 ай бұрын
Большое Спасибо за предоставленный материал!
@UATechnicalSolutions2 ай бұрын
пожалуйста
@IgorBond2 ай бұрын
Большое Спасибо за предоставленный материал!!!
@AliBekn1bloger2 ай бұрын
🎉🎉🎉🎉🎉
@spicky29663 ай бұрын
nice...
@kevinmithnick99933 ай бұрын
I've seen some of those sensors can be calibrated. Have you tried that?
@UATechnicalSolutions3 ай бұрын
Generally there is no need for Calibration. As they come factory calibrated. Incase there is doubt of wrong output from sensor it can be tested on calibration tool.
@kevinmithnick99933 ай бұрын
Nice videos! Keep the good work! Are you planning any future videos on vsd?
@UATechnicalSolutions3 ай бұрын
Yes we are starting with carrier 30kav training course very soon.
@sonusomarajan17353 ай бұрын
How to check igbt York vsd chiller
@UATechnicalSolutions3 ай бұрын
What is the chiller model?
@patrikreksa10634 ай бұрын
Yes .. normal useful video ... No blabols... Just data strict .. Nice vid
@avithamosi20614 ай бұрын
Very helpful, thank you
@UATechnicalSolutionsАй бұрын
You're welcome!
@mohsinelotfi52984 ай бұрын
Quantity of oil 30xa 902
@UATechnicalSolutions4 ай бұрын
What is the tonage capacity of compressors?
@mohsinelotfi52984 ай бұрын
Medel number:06TUA483SW1C
@mohsinelotfi52984 ай бұрын
Reference oil of compressor plz
@UATechnicalSolutions4 ай бұрын
Synthetic oil sw220
@mohsinelotfi52984 ай бұрын
@@UATechnicalSolutions thank you
@derekprreira32144 ай бұрын
Hi Sir, In a carrier 30 XA chiller, when is there a need to replace an oil level switch ( float switch), can you please explain exactly. Regards Derek
@UATechnicalSolutions4 ай бұрын
Hello. The oil level switch works ok dry contact principal. If the oil level is good in the chiller oil level switch contact should be closer. In case oil level is ok and oil level switch contact is open then replace the switch
@derekprreira32144 ай бұрын
@@UATechnicalSolutions Sir, I appreciate your prompt help. I'm dealing with a 30XA0302 carrier chiller. I can't figure out the chiller tonnage as I'm new to it