Пікірлер
@patrickjamono9329
@patrickjamono9329 12 күн бұрын
Why does a pump controlled by a danfoss vlt experience speed fluctuations when started?
@LoisCaffee-o2p
@LoisCaffee-o2p 24 күн бұрын
Breitenberg Bypass
@mdalimran8530
@mdalimran8530 Ай бұрын
How to solve it frequency converter switch one site
@KennethHernandez-m5x
@KennethHernandez-m5x Ай бұрын
8388 Ashton Meadows
@musvarisimbarashe8076
@musvarisimbarashe8076 2 ай бұрын
Thank you so much
@paulikass
@paulikass 3 ай бұрын
Very useful information, thanks for the video 👍👍
@WaseemAlhazm
@WaseemAlhazm 4 ай бұрын
FC102N showing the earth's fault, . During removing the cable it does not show the earth fault when we are connecting the motor cable it starts showing the earth fault. We checked the cable and motor and found it normal. Then what is the actual reason and what is the solution.
@Rahulraj-x8w
@Rahulraj-x8w 6 ай бұрын
At 5:16, you spoke about high voltage frequency pulses that can find pass to ground through the smallest pinholes of insulation. How can we confirm this is the case? Will a Megger test or insulation resistance test be able to detect such minor pinhole leaks?
@romainesmith3120
@romainesmith3120 7 ай бұрын
Good day..... How does the full service log (M26) would affect the operation/function of the drive?
@senthilvelan6728
@senthilvelan6728 7 ай бұрын
Dear sir , have problem for fc202 inverter setting pls advice following issue Tunnel thruster Remote operation 0-5V Rotation forward & reverse
@davonbryan4310
@davonbryan4310 8 ай бұрын
How to change to English language
@erbayerbay4338
@erbayerbay4338 9 ай бұрын
It works again after a power outage and when it comes back on. How can I stop this?
@ZawNyeinSoe
@ZawNyeinSoe 9 ай бұрын
What does P/N mean on the VFD drive?
@md.billalhossainmondal6956
@md.billalhossainmondal6956 10 ай бұрын
Video not clear
@uisobarikij9704
@uisobarikij9704 11 ай бұрын
I want 2 vfd drive danfonce
@automesinmechatronic5206
@automesinmechatronic5206 11 ай бұрын
Warning 66 low temperatur please solution?
@nazrulrz2112
@nazrulrz2112 Жыл бұрын
Short circuit a16
@MehediHasan-z7m
@MehediHasan-z7m Жыл бұрын
Thanks
@sabbirmunna6498
@sabbirmunna6498 Жыл бұрын
Nice...
@sudharathna
@sudharathna Жыл бұрын
What’s the sensitivity or min earth leakage current for the vfd to cause earth fault alarm or trip
@TJ0516
@TJ0516 Жыл бұрын
Thanks
@emmanmiclat7839
@emmanmiclat7839 Жыл бұрын
Question: can we program a timer settings? how?
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@InstrumentCalibration
@InstrumentCalibration Жыл бұрын
Good Stuff !
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
Appreciate it!
@rico2207
@rico2207 Жыл бұрын
Great video
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
Happy you enjoyed it!
@wahyunugraha8245
@wahyunugraha8245 Жыл бұрын
Sir How to change analog input voltage to current mode? Because 6-11 and 6-12 is missing.
@tddedertijs5756
@tddedertijs5756 Жыл бұрын
There are dipswitches when you take off the display. Switch from "U" to "I" and your done.
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@kamalosama4277
@kamalosama4277 Жыл бұрын
Thanks danfoss you make my life easy ❤❤
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
Happy to help!
@loogeshm7966
@loogeshm7966 Жыл бұрын
Nice video and how to monitor encoder pulses in lcp
@tariqpervez8385
@tariqpervez8385 Жыл бұрын
Dear Sir ,could you guide me regarding danfoss FC202 .Alarm earth fault 13 (A14),Sir how can resolve this fault .hope you will help me ,waiting your prompt response .
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@suhailjamadar7267
@suhailjamadar7267 Жыл бұрын
Sir i have danfoss fc102 VFD in which in there is input supply voltage but i am not getting an output. Please help out to know an issue in it. Thank you
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@MastrooBendict
@MastrooBendict Жыл бұрын
Great video! Very helpfull and simple
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
We are happy you enjoyed the video!
@RajeshKumar-uh7mr
@RajeshKumar-uh7mr Жыл бұрын
Hello sir vlt 2900 Run command after Err 14
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@Bosanac_99
@Bosanac_99 Жыл бұрын
I cannot find what type of sinus vawe filter (serial output filter) is recommanded for Micro FC51? Please, any recommendations?
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@Solo_Traveller_07
@Solo_Traveller_07 Жыл бұрын
Uncrewing section not work properly till M/c continuosly run 15/20 minutes. After 15/20 minutes machine work properly and Uncrewing section work properly. When uncrewing section not work then display shown "Uncrewing drive faulty". When such type problem created then we press continuously reset button. Drive alarm showing current limit A59 Please help
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@jhonnybellohidalgo4417
@jhonnybellohidalgo4417 2 жыл бұрын
in the fc101 models they do not have common current sensors, apparently the measurement is taken through the dc bus, because in my case I have an fc101 and the alarm 16 short circuit persists, having already measured the igbt module correctly
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@suhailjamadar7267
@suhailjamadar7267 2 жыл бұрын
Hello sir Please upload all faults and warnings, methods of rectification and solutions videos.
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@மண்புழு87
@மண்புழு87 2 жыл бұрын
Watching your video helps to improve my skills life.thank you very much sir
@Hi-CHOICE
@Hi-CHOICE Жыл бұрын
எப்படி சரி செய்வது alarm 14 m
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@ashleyjones3995
@ashleyjones3995 2 жыл бұрын
The reference 3-01 on my drive is set rpm, and all references are in rpm, how do I set this to HZ?
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@sanishahzad9552
@sanishahzad9552 2 жыл бұрын
37kw ka inverter mil jay FC 302
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@zpc8536
@zpc8536 2 жыл бұрын
Hello!!! For the power of the motor. Should I choose the higher or lower value? What s the impact of this parameter on the function of the motor fan? Thank you!
Жыл бұрын
The value is according to motor plate data. One of the main fuctions of the VFD is protect the motor and for this, you have to set the rigth values of the motor, if you put a highier value, the VFD will not have any problem but the motor will get damage soon. I recommend do the AMA for a better perfomance and better protection of your motor.
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@thailottery1986
@thailottery1986 2 жыл бұрын
I have vlt microdrive this one running without motor when connected the motor shows alaram 16 pls send solution
@shashikumar3113
@shashikumar3113 2 жыл бұрын
Replaced IGBT module ......
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@wasimansari-rt5ik
@wasimansari-rt5ik 2 жыл бұрын
I have Danfoss drive 5 hp its not working in auto mode in manual mode motor runs and even speed varies by operating potentio meter situated on drive what could be the reason
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@wasimansari-rt5ik
@wasimansari-rt5ik 2 жыл бұрын
I have Danfoss drive 5 hp its not working in auto mode in manual mode motor runs and even speed varies by operating potentio meter situated on drive what could be the reason
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@InstrumentCalibration
@InstrumentCalibration 2 жыл бұрын
What is the full form for VLT ?
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@raoulboumi4043
@raoulboumi4043 2 жыл бұрын
I have an alarm on my danfoss vlt internal MCO error[A199] Please how can i solve it
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@suhailjamadar7267
@suhailjamadar7267 2 жыл бұрын
AL-048 Gate drive voltage fault What's the solution for this alarm. Please help me out
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@humbulanimathisa9004
@humbulanimathisa9004 2 жыл бұрын
I cant save the changes, every time it just go back. Could this mean the drive is looked?
@DanfossdrivesNA
@DanfossdrivesNA Жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@ducnghiabk2007
@ducnghiabk2007 2 жыл бұрын
Dear Sir. We have one drive fc 302 earth fault 2 when it starting. We have checked earth connection motor cable ok. But we can not reset this fault? ( Please help or bypass this fault?)
@DanfossdrivesNA
@DanfossdrivesNA 2 жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@shashikumar3113
@shashikumar3113 2 жыл бұрын
Replaced motor out put CTs
@ndukwudaniel5339
@ndukwudaniel5339 2 жыл бұрын
Pls i don't knw hw to get in touch with your company I need a clear explanation on my inverter AKD 500 Because is displaying alram 14
@DanfossdrivesNA
@DanfossdrivesNA 2 жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@gajananr.maneshirol2710
@gajananr.maneshirol2710 2 жыл бұрын
Sir on disply shows some frequency when start...But motor not start....what possibility ?
@DanfossdrivesNA
@DanfossdrivesNA 2 жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
@hakimshajime8245
@hakimshajime8245 2 жыл бұрын
Why some of vfd can run manually on the spot when switch to manual mode but some of vfd cannot..no response in manual mode
@DanfossdrivesNA
@DanfossdrivesNA 2 жыл бұрын
For installation, start-up, programming and troubleshooting assistance please email: [email protected] or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)