Kenapa barang ini sangat ringkih,kena short saja langsung mati casambinya ,output tidak keluar power
@j-mals8 ай бұрын
Hi, I've been watching your videos, which have been very helpful. Thank you. I was hoping you could help. I have managed to set up the bathroom lights to come on during the day when the sensor is triggered, but how do we stop them coming on at night at all? I thought when i set the scene up for them to only work during set hours, but it is still coming on after those hours, any thoughts? Thank you!
@CasamBee8 ай бұрын
You have two choices: 1. Keep your existing time-based scene and over-rule it with a timer that takes priority over it. Set up the timer to over-ride the lights’ output to 0% between the hours that you want the light to be off. 2. The option I would use… add a second option to your existing time-based scene and nude the hours you do not want the light to come on. E.g. 23.00-06.00. Set the our out for the light during these hours to 0%. So the light will be triggered, but it won’t actually turn on.
@chrissdavey Жыл бұрын
Very helpful 👌
@mohamedhizem7831 Жыл бұрын
Hi, I have just across your videos and I like the content quite a lot. Please keep up the great work
@CasamBee Жыл бұрын
Thank you!
@richardsalter-b3j Жыл бұрын
Hi, Do you know if it is possible to control luminaires with an enocean switch and a pir sensor?
@CasamBee Жыл бұрын
Yes, you can. But remember that the switch will always over-ride the PIR. See my other videos to see how they’re configured.
@meshstore_technologies Жыл бұрын
Good guide
@CasamBee Жыл бұрын
Thank you!
@pklijn Жыл бұрын
Great video! I was wondering, is this the vanilla Sonoff 4CHPRO or the special one from RB Technik? Could you share some information on how you connected it to Casambi?
@CasamBee Жыл бұрын
Apologies! This comment slipped by me un-noticed and I no longer have the device as it was just on loan.
@WicekCycex Жыл бұрын
Is it possible to control luminiare RGBW and dimming via google assistant using RB Technik 4CHPRO?
@CasamBee Жыл бұрын
It’s not possible to control colour changes, no. The device seems to be primarily designed for enabling scenes or devices in on/off states. You could set the Latching back to the factory settings and use repeated voice commands to start and stop the RB device ports in order to dim ip and down. But, to be honest, I think that will drive you crazy. You’re better off using it to simply turn devices on or off.
@WicekCycex Жыл бұрын
@@CasamBee thanks :)
@celestealbertini34652 жыл бұрын
excelente contenido, muchas gracias
@petersquire55172 жыл бұрын
Loving your tutorials. When using a CBU-TEd or CBU-ASD as a sensor, is there a fundamental reason for controlling the linger time at the sensor rather than within Casambi? The extreme case would have the sensor relay switching (potentially audibly) with every movement if it was set to a minimum?
@CasamBee2 жыл бұрын
You make a good point there with the sensor relay switching regularly. My thinking is/was just that it’s simply easier to control the linger time from a single source rather than mix two sources. For example, you could set the sensor relay to 15 seconds and then set Casambi to 15 seconds. That would give you 30 seconds linger but you just need to remember to add 15 to whatever value you set on the Casambi side. And, of course, you could set the Casambi side to 1 second and fully control the linger time from the relay sensor (potentiometer). Just use whichever method suits you best - there isn’t necessarily a right or wrong way.
@petersquire55172 жыл бұрын
Is there a difference in activation time on detection between a CBU-TED used as a sensor and say the CBU-CEFL Casambi sensor due to the TED being powered up? Hope that makes sense…
@CasamBee2 жыл бұрын
@@petersquire5517 I guess there might be from an electrical/electronics point of view, but nothing you’d notice in practice. A TED powers on pretty much instantly.
@petersquire55172 жыл бұрын
This may seem like a dumb question, but how do you configure a CBU-CEFL presence sensor to only turn a scene on when it is dark?
@CasamBee2 жыл бұрын
@@petersquire5517 A good question! Look for my video about controlling my porch light with a presence sensor. I don’t remember the video name, sorry. In short: first create a basic scene with the light(s) dimmed to 100%. Then create a time-based scene which only turns on the basic scene during sunset and sunrise. Then assign that time-based scene to your presence sensor as ‘presence only’.
@marktime612 жыл бұрын
Does this proposed configuration (which was working) change if the EnOcean switch that initiates this sequence/scene(s) is set up as dimmer for the lights? The reason for asking is the fan has stopped working which could be down to the electricians wiring or the fan (new) has failed. (Fan controlled by a CBU-Relay). So if the wiring was off the dimmer (TED) the fan may fail due to inductive load of dimmer? - Lights working fine still.
@CasamBee2 жыл бұрын
Try controlling the fan directly using the CBU-Relay on the Luminaires page. Is the relay in a position where you would be able to hear it click on/off? If it is and you can’t hear it, then it’s likely the relay at fault. If you can hear it click but the fan doesn’t spin, then your fan’s likely at fault - or the wiring connected to it. I’d really need to see your current switch configuration to comment more.
@marktime612 жыл бұрын
Many thanks for your response and its as I expected. Yes Relay clicks on demand so I think thats working as for fan it has a strange control wire connected to relay so will get the electrician back as they installed it. Just wanted to be half sure it’s not the Casambi kit or my Scene… before I pointed the finger. Its under warranty. :-)
@tommiballs2 жыл бұрын
Been waiting for a device to come out like this but for all that excessive money you still are restricted by predefined scenes! Casambi have fallen way behind the competition in terms of functionality and cost competitiveness. I'm going to take it all out and replace with another system.
@marktime612 жыл бұрын
What is the difference between a presence sensor and a movement sensor? Thanks
@CasamBee2 жыл бұрын
A very good question! And one that people get mixed up… In the lighting control industry, a presence sensor is a sensor that can detect motion and light. Whereas a motion sensor can only detect movement. It can’t be used to detect light too. And, admittedly, the tiny clear sensor in one of these latest videos was actually just a motion sensor but I might have referred to it as a presence sensor - I’m just so used to it.
@marktime612 жыл бұрын
Thanks for this video - very helpful. Whilst I have the basics working you didn't show making the scenes called in by the Master Scene/Animations so I have guessed those. Lights are easy but the fan which in my case is controlled by a Casambi relay is a little trickier to know what's going on. Further complicated (lengthy testing) due to the Fan having its own timeout (shower fan not desktop) of c.10 minutes. Trying to validate the steps and icon changes isn't obvious (Casambi App not you lol).. My question remaining I guess is what happens if the Presence setting is pressed twice as in my case (EO Switch) by mistake .. The lights goes out but The Fan continues for another cycle (20 mins). Thanks again for the basics.
@CasamBee2 жыл бұрын
That’s right. If the presence scene was pressed again, then your light comes on and the fan - and it’ll stay on until you turn them off. If you pressed the absence scene again (when everything was already off), then your light would stay turned off and the fan would spin for 20 mins (or whatever time you’ve set) before it eventually turned off by itself.
@marktime612 жыл бұрын
@@CasamBee So is there a way for the light not to go off in that use case to ensure user presses rocker in alternate direction to turn light off hence confirming Absence scene? Tks
@CasamBee2 жыл бұрын
@@marktime61 not really, no. This is because they’re not true latching switches (they’re technically push buttons). You could edit the ‘off’ animation so that it actually included x seconds of the light being on before it’s then turned off and the fan staying on for a while. But even that would still require pushing the correct (on) button again after a certain amount of time to keep the light on.
@marktime612 жыл бұрын
@@CasamBee Thanks. In practice its not really an issue I’ve realised as the fan is on until light goes off and the fan timeout cycle begins or restarts so amounts to the same end result:-)
@marktime612 жыл бұрын
Any idea why one device (iPad) doesn’t show edit in scenes screen? iPhone and another ipad do show edit scenes….. thanks
@CasamBee2 жыл бұрын
Refresh the iPad network list, Mark. It could be that you’re logged in on that iPad with a user that doesn’t have admin rights (to edit the network configuration). If that is the case, ‘forget’ the network and then log back in with an admin account.
@keesm3072 жыл бұрын
Thanks for taking the time to explain these features clearly, even though I probably will just use a fraction of them. At least now I can judge if the features would help for my circumstances. Much appreciated. I would definitely love a video that gives examples of situations when these features and scenes could be helpful for regular house use. You already point out examples in your videos at times, but more examples definitely would be usefull. Either way: thanks!
@CasamBee2 жыл бұрын
That’s not a bad idea and it’ll also give me an excuse to make more videos. I can already think of things like porch lights, entrance lights and kitchen bench lighting.
@marktime612 жыл бұрын
Many Thanks
@mountainlover49042 жыл бұрын
Hi, you are making amazing information and practical videos appreciated your efforts.
@CasamBee2 жыл бұрын
Thank you! I’m happy to hear that people find the videos useful.
@spatiallightingdesign2 жыл бұрын
Thanks for the updated videos, I see this configuration working in a hall way or a location where you'll use 2way switching
@patrickcollins23822 жыл бұрын
Big welcome back, your tutorials and especially your Tips are brilliant, looking forward to many more-!
@CasamBee2 жыл бұрын
Thanks, Patrick!
@marktime612 жыл бұрын
Anyone know if 2 Enocean switched can be made 2-way? I have one at each end of the room and whilst they work One ideally needs to be inverted function wise?
@CasamBee2 жыл бұрын
You should just be able to duplicate the the two EnOcean switches and out one at each end of the room. If you find that means you’re still having to press the same button twice, create on and off buttons for each switch and disable the Use Toggle option. I’ve not forgotten about the bathroom fan video for you - just been really busy.
@marktime612 жыл бұрын
Can I use a CBU-TED as a basic Switch (without dimming)? Or is there another Casambi solution/product available? I need for a fan in a bathroom tks
@CasamBee2 жыл бұрын
The CBU-TED can't be used for on/off switching because of the dimming curve. Instead use something like a REL-240 from Liga Air. That'll do the job and they also have a very small form-factor. Alternatively, add a 230VAC relay to a CBU-ASD. That'll do exactly the same job.
@marktime612 жыл бұрын
@@CasamBee Thanks for your prompt reply as I need to order a device asap. What about if the default dimmer range is set to 100% - meaning full on? Thanks. (I also have a spare TED so could try)
@CasamBee2 жыл бұрын
@@marktime61 I wouldn't risk it... Even if you could alter the dimming curve of the TED to go from 0 - 100% as quickly as possible, there's still that 'ramp up' to 100% and ramp down to 0% (even if it's a really short time). Much safer to go with a true relay. The TED designer once told me that it's the fade-down from 100 to 0 which is problematic if trying to use a TED to switch 230VAC (rather than the fade from 0 to 100, as most people would suspect).
@marktime612 жыл бұрын
@@CasamBee Understood and thanks
@marktime612 жыл бұрын
@@CasamBee Apologies but another related question. I have used EnOcean switches successfully for on/off dimmer etc and there are many modes/function under the Casambi App as to the action taken by these Switches. I wondered if you know which type/mode would best replicate a push to make switch as the bathroom fan scenario would normally take power (via light switch or spring back switch) and then after power removed the fan would continue on a timer/timeout within the fan. An ordinary Sw function would be in the wrong state after the timeout. Perhaps an EnOcean Sw mode or a Casambi App timer could work?…. Thanks again
@marktime612 жыл бұрын
Hi, could you comment on if these wireless Casambi/Enocean switches are ok to use in the bathroom to control lights? Electrician muttering IP rating but supplier says wireless and battery less so probably not required to be rated? Just wondered if they were semi moist tolerant ... ? tks
@upendrachaudhari46352 жыл бұрын
- set up an absence sensor , for this part as you suggested a case of boardroom meeting, as an extension to that case is it possible to group multiple TED PIR sensors to get more accurate results ? any opinion sir
@CasamBee2 жыл бұрын
I suspect you've already got this working, but in case you're interested I've now answered this in more detail in this new video: kzbin.info/www/bejne/hKelfaWLYrF_hNE
@fareedalshihab51772 жыл бұрын
Can I send for you my light list ... If you can help me with casambi drivers because I don't know witch one I buy for my lights
@CasamBee2 жыл бұрын
Sure! You can write the list here. But the list needs to contain the types of LED drivers which your lights use.
@fareedalshihab51772 жыл бұрын
@@CasamBee 1. Recessed spotlight, LED chip 15W,1375lm 2. Recessed Laser Blade Spot Light, LED 10W,925lm 3. Surface Mounted Spot light, LED 2x3W ,83lm/W 4. Recessed spotlight, LED chip 15W,1390lm 5. Recessed spotlight, LED chip 15W,1375lm 6. Recessed spotlight, LED chip 15W,1375lm 7. Linear light, LED 10W 8. Recessed Spot Light, LED chip 7W,83lm/W 9. Surface Mounted Spot Light, LED chip 7W 10. Recessed down light, LED 24W 11. LED Inground Light, 1x2W, 240V 12. LED Inground Light, 8W, 240V 13. Recessed Underwater Spot Light, LED 3x2W 14. Wall Mounting Landscape Light, 1x4.5W, 240V 15. Projector Light, LED 8W, 220V 16. **All lights above NON-DIM driver .. 17. LED chip, 9.6W, 24V,TRIDONIC LED Driver 100W, 24V 18. LED chip, 9.6W , 24V,TRIDONIC 80 LED Driver 100W, 24V 19. LED chip, 4.8W, 24V,TRIDONIC LED Driver 60W, 24V 20. LED SMD, 48V, IP67, side bend, 6w,40W, 48V AC-DC Single output LED driver Mix mode (CV+CC) with built-in PFC; Output 48Vdc at 5A
@CasamBee2 жыл бұрын
@@fareedalshihab5177 For lights 1 - 15 (which aren't dimmable), you'll need to use a relay switch to turn them on/off. There are several of these to choose from on the Casambi website. Personally, I recommend the Liga.Air models as they have a very small form-factor. 17 - 19, if those Tridonic drivers are dimmable, they're likely to use DALI control. So in that case you can use the CBU-ASD or CBU-A2D. Both do the same job but have different form-factors, so see what suits you (or your electrician). Note that the CBU-A2D is the newer of the two devices. 20. That looks like an LED driver which can control tuneable white lighting. Against, I'd suspect that the LED driver sis DALI controlled so you can use the ASD or A2D, as mentioned above. But you need to get more details from the manufacturer to confirm the LED driver's control method. Hope this all helps!
@fareedalshihab51772 жыл бұрын
@@CasamBee Thank you for the information, was very informative.. For the lights, from 1-15, what if I wanted them to be dimmable, do i need a separate driver for each, or is there a driver or a specific device from casambi
@CasamBee2 жыл бұрын
@@fareedalshihab5177 it depends… if the lights are standard 220VAC dimmable lamps then you can just use a CBU-TED. I’d recommend no more than three lamps per TED, but Casambi claim the amount is not limited and instead based on the inrush current.
@lucyna28912 жыл бұрын
is there any way to integrate this with apple homekit ?
@CasamBee2 жыл бұрын
Unfortunately not. It’s designed specifically for Amazon Alexa.
@clemenswe42093 жыл бұрын
Hi there, active again? Nice idea for a little at home project. If one uses a DCS plus a Dali power supply (Tridonic or Lunatone, both not that expensive) instead of the A2D, it might allow longer wires. Of course also not Casambi approved :). Thanks for sharing.
@CasamBee3 жыл бұрын
Yes, a DALI PSU and a CBU-DCS would do the same thing. It's just the purchase cost of the extra device to consider... FYI: don't ever connect a DALI PSU to an A2D or ASD, as it will damage the Casambi sevices.
@marktime613 жыл бұрын
Thanks for the video, I looked at this a few months ago and decided a) too expensive, b) didn’t support google or Siri, c) didn’t allow FW upgrades if you started with the entry level amount of channels. FWIW I use a Raspberry Pi now c. Euro 70 with Homebridge (FOC) and Casambi plugins (FOC) and use Siri.. works great.
@CasamBee3 жыл бұрын
Yeah, I've been aware of the Homebridge option for quite some time. Bear in mind that Casambi API access will no longer be free from the 1st July 2022 onwards, though.
@marktime613 жыл бұрын
@@CasamBee Yes I grumbled as a domestic user when I heard but was semi assured they would not close the door on us. Seems odd when so many are going open and using thread and matter..
@belgiumarthur3 жыл бұрын
I cannot comprehend why it isn't able to work with Alexa or Google Home out of the box without half-assed solutions. It's the minimum for a smart home device, ffs. I will throw out the Casambi devices I have and replace them with Hive, Hue or even IKEA.
@CasamBee3 жыл бұрын
It’s because Casambi’s focus is on commercial installations, not residential homes. But, of course, their devices have naturally crept into the consumer market via online resellers - it was unavoidable. I’ve been meaning to do a ‘part 2’ of this video but I just haven’t got round to it yet. But, like you said, it requires an extra solution to make it work: a device called a X-Moment, and they’re not cheap…
@belgiumarthur3 жыл бұрын
@@CasamBee I did not know that! Honestly I rather blame the installers kind of misleading us in this aspect. I already looked at the x-moment, it's a possibility, but switching to a different system like Hue seems cheaper. I only have 4 separate light fixtures with casambi, so not that much lights to replace. Thanks for your input though. I'm simply disappointed because of it and I was looking for a way to dim the lights as well via voice commands.
@fareedalshihab51773 жыл бұрын
Can I use one casambi module for controlling multi light?? Casam 🐝 how can I contact with you??
@CasamBee3 жыл бұрын
It depends on what type of light(s) you want to control. But, in general, it's one device per light load. Feel free ask ask as many questions as you like via KZbin. I will reply - even if it takes a few days.
@jumadirosidi84213 жыл бұрын
Hallo, how to set casambi for dali 8 is it supported? i need for driver for tunable white led sir, thankyou.
@CasamBee3 жыл бұрын
Yes, DALI DT8 is supported for the CBU-DCS, CBU-ASD and CBU-A2D. There are multiple TW fixture profiles available for all three of those devices. Just look for the profiles names which include 'DT8' and 'TW'.
@marktime613 жыл бұрын
why does my timer, time-out before the time set? I do not have "Use Control Hierarchy" set on at the moment nor any presence sensors... - tks
@CasamBee3 жыл бұрын
You probably manually controlled the light(s) being controlled by that timer. So I doubt it was the timer, it'll have been manual control.
@marktime613 жыл бұрын
@@CasamBee Nope. Set timer in advance (future) and then not touched the App/phone at all. Its on its own currently as testing. Other Luminaires will become live when the building project is finished (home renovations and new kitchen)..
@CasamBee3 жыл бұрын
@@marktime61 are your devices losing power? If they lose power, then they also lose network time which would clear the network time. Also remember that a timer should be refreshed after it’s been created ( or wait until its start time arrives in the future. It’s a bit hard to advise anything else without seeing your network configuration (which I can’t)
@marktime613 жыл бұрын
@@CasamBee Thanks I am in touch with Casambi support and sent them my config. Initially they cant see anything wrong with it but my network is not on permanently due to building works so I will re-evaluate when its all up and running. One other Q you might be able to comment on is what does the red badge (circle) indicate in the App? When I open it there is nothing obvious and the badge disappears…. Think it has a “1” in it.. thanks
@CasamBee3 жыл бұрын
@@marktime61 id all of your devices lose power then they lose network time and your timers won’t work. The red circle over the Casambi app icon is telling you the network(s) in your app have recently had a configuration change. …this is presuming I’ve understood which red circle you’re referring to.
@marktime613 жыл бұрын
would be nice if they had a low cost repeater module as its a waste and expensive to fill network holes...
@CasamBee3 жыл бұрын
Any permanently-powered device acts as a repeater. So you don’t have to buy ready-made repeaters.
@marktime613 жыл бұрын
Please do you know where the Timer function is stored? (Phone, Local Network/Devices, Casambi Cloud? - Only I am testing this with a Porch Light (with a Casa Bulb E27) and results are mixed. Seems BT range is an issue although kitchen spots (CBU-TEDs) are only some 10-15ft away (plus some walls/doors. (Could be so called Island Issue) Siting another TED in a nearby socket seems to improve things but Timer still variable so wondering if phone location is relevant? I would hope not otherwise leaving the house would compromise timers... Thanks
@CasamBee3 жыл бұрын
All network configuration (including timers) are stored on each individual device within the network. However, if a device loses power or its connection to the rest of the mesh network then it will lose network time and the timer will not work correctly. Use the All Luminaries button on the Luninaires page to check if you have an island issue. You have an island issue if the all luminaires button does bot turn off/on all devices in your network.
@CasamBee3 жыл бұрын
The phone location is irrelevant unless you’re using it as a gateway device - in which case it must be connected via bluetooth to the network.
@marktime613 жыл бұрын
Re: CBU-PWM4+PSU vs CBU-ASD Dali controller +DALI Driver. For driving LED strips (just warm white dimmable) where up to 4 runs are co-located like in a kitchen cabinet, could I use the PWM4 (x1) as opposed to the more expensive option of DALI driver +ASD (x4)? What are the pros/cons? Should I assume that for 12v Strips the PSU input to PWM4 would be 12 volts? Also are the 4 channels shown in Cassambi App as 4 separate luminaires?
@CasamBee3 жыл бұрын
From my experience, people tend to use DALI drivers for larger LED lights rather than LED strip. For LED strip, a PWM4 is probably the cheaper option. Yes, the PWM4 PSU voltage will need to match the LED strip’s voltage and you also need to make sure that the PSU will offer enough amps for the lengths of LED strip(s) you’ll use. Yes, you can use four strips with a single PMW4 but, again, make sure your PSU can cope. A single PMW4 device will be visible in the Casambi app but you can adjust each of the four channels individually.
@MrHazaraak473 жыл бұрын
thanks for the such great presentation...i just need some information about...i have Casambi ASD Blutooth, Casambi wirleless wall switch, LED Module and sensor...what do i need more to complet my installation....thanks
@CasamBee3 жыл бұрын
All you need to do now is install the Casambi app. Then create a network, pair the devices and configure them as you want.
@MrHazaraak473 жыл бұрын
You mentioned extern relay do I need that or
@CasamBee3 жыл бұрын
@@MrHazaraak47 only if you intend to control a 1-10V controlled LED driver.
@marktime613 жыл бұрын
I am wondering if you can comment to the main differences (benefits/shortcomings) over 2 strategies I am considering. (1) Casambi bulb (native) and (2) E27 dimmable LED plus CBU-TED? The Bulb is quite expensive but is native. Thanks
@CasamBee3 жыл бұрын
Casambi-enabled bulb: they usually offer tuneable white lighting but weaker signal range. CBU-TED: usually offer a better signal range but no TW. A CBU-TED and Ikea’s dim-to-warm bulbs could give you a slightly similar feeling.
@marktime613 жыл бұрын
Can the iOS App be used on both an iPhone and iPad (at same time/ either/ or)? If I open iPad App says unpair? This could be (testing with single CBU-TED) because I didn’t create a network on iPhone but did on iPad? Perhaps I need to unpair and re-pair on both devices using same Network/ name? Tks
@CasamBee3 жыл бұрын
It can be used on both, but you first need to share out your network (using the device you used to create the network).
@marktime613 жыл бұрын
If this is a mesh network and rely upon each other as a transport I assume all existing hardwired wall switches would need to be left on to maintain the network? However assuming short distances turning some lights off at the wall switch shop still allow control of others when in range? (How long is boot time from power up?) thanks
@CasamBee3 жыл бұрын
That’s right. Casambi devices are designed to be powered on 24-hours/day. And, as you said, any devices which are powered off will still allow the remaining devices in the network to be controlled - but only as long as they are all within range of each other! If even one device is powered on but can’t communicate with the mesh network then you will create an island issue and communication will not work properly. Luminaries generally power up and connect to the mesh network within a second (if not even quicker). From my experience, sensors can take up to around ten seconds to power up and notify the network, depending in the manufacturer.
@marktime613 жыл бұрын
@@CasamBee Thanks for your extensive explanation. Whilst I can and will troll through the Casambi website and its partners, I am wondering if there is a single device that supplies power (12/24v) for Led strips that also contains dimming (Driver/Dimmer)? Or if this is always a 2 box scenario? (Driver + Dimmer). Your thoughts appreciated. Thx
@CasamBee3 жыл бұрын
@@marktime61 yeah, there are plenty of Casambi-enabled LED drivers available - meaning the Casambi module has been built into the LED driver’s PCB. Have a look at the Casambi website for lots of examples, then find a reseller near you.
@marktime613 жыл бұрын
@@CasamBee any that contain dimming as well as drivers? Tks
@CasamBee3 жыл бұрын
@@marktime61 yes, they’re all dimmable drivers. (Because the Casambi dimming module is built into them).
@marktime613 жыл бұрын
Is the ASD in Relay mode dry contact? No voltage for say momentary closing contacts for gates?
@CasamBee2 жыл бұрын
Apologies! This one seemed to have slipped through the net and I only just noticed it now as I'm about to make new videos. In short, yes, it non-voltage, just a closed-contact.
@marktime613 жыл бұрын
What is considered an “Element “ ? Thanks
@CasamBee3 жыл бұрын
An element could be a couple if things. For example, in the case of a 2-channel luminaire, each channel could be considered an element. And a relay, or switch within a luminaire, can also be considered an element.
@marktime613 жыл бұрын
@@CasamBee So its the lowest form of control in the hierarchy? One Luminaire may have one or more elements for example?
@CasamBee3 жыл бұрын
@@marktime61 An element isn’t considered a separate part of the control hierarchy, it’s the device (which the element belongs to) which is controlled by the control hierarchy. Yes, one luminaire/device may have more than one element. For example, a 2-way relay means two elements.
@marktime613 жыл бұрын
Can you have 2 Xpress switches in same area controlling different things? Or would they conflict? Tks
@CasamBee3 жыл бұрын
Yes, you can have multiple Xpress switches assigned to the same network. They can then control anything within the network - even two Xpress switches controlling the same luminaires (in a case where you may want to duplicate the switch at opposite ends of the same room. They won’t interfere with each other because they’re assigned different Unit IDs.
@marktime613 жыл бұрын
@@CasamBee Thanks very helpful
@konradaquaform84033 жыл бұрын
Hey! I just wanna say, that you make an excellent job and it gives more feedback than casambi sellers or even, casambi support. Thanks!
@CasamBee3 жыл бұрын
Thanks!
@Nathan-cm1qu3 жыл бұрын
Great and clear presentation thanks! What is the slimplest and most cost effective setup to get a relay function? For instance, turning on or off an existing plug (or any electrical device that might need more than 150W)?
@CasamBee3 жыл бұрын
Thanks! The most basic option is a 230VAC relay attached to a CBU-ASD. But there are now many different types of relays made by Casambi's partners. You can see the various devices here: casambi.com/ecosystem/ Just search through the text for 'relay' and you'll find them. ...cost-effectiveness is a completely different matter, though ;)
@keithildinho3 жыл бұрын
Where do you buy your casambi controls from in uk?
@CasamBee3 жыл бұрын
You can find your local Sales partner from the list here: casambi.com/contact/
@minhthanhnguyen22463 жыл бұрын
i have a problem with how to connect casambi remote control 4 way, 8 way, and glass?
@CasamBee3 жыл бұрын
I’m not aware of any 8-button Casambi switches. I believe one or two companies have created 6-input button interfaces but not actual wall switches.
@RusticRaver3 жыл бұрын
hello, cool product and video, what would you recommend to control 2 ballast 320w meanwell 0-10v independently , I take it you would need 2 casambi? 150w limit does not apply since I would control them by 0-10v? sorry I'm a bit lost about this Casambi CBU-ASD
@CasamBee3 жыл бұрын
Hi! You're right, the wattage of the LED driver is irrelevant as the Casambi device is just controlling it. You could use two Casambi devices if you like, but you could also use a single CBU-A2D (AC powered) or a CBU-ASR (12-24VDC powered). Both allow 2ch 0-10V control. It really boils down to how you'd like to control them. If you would like separate icons for each LED driver in the Casambi app, then go with two Casambi devices. If you're ok with both 0-10V channels appearing under the same icon then just use a single device. You could always start with a single device anyway and buy a second if you feel you might get more flexibility that way.
@TadasBurovas3 жыл бұрын
How to unpair xpress? Have deleted the network without unpairing first. Now struggling as instructions not working..
@CasamBee3 жыл бұрын
Press buttons 1 and 3 on the Xpress switch at the same time (that should wake it up). Then quickly go to MORE > NEARBY DEVICES within the Casambi app, select the Xpress switch and then choose UNPAIR DEVICE. It'll then ask you to press a button to confirm. Then it should be un-paired.
@TadasBurovas3 жыл бұрын
@@CasamBee Thanks! After asking I tried one last time - clicked Unpair -> Start -> hold 1 and 3 and then a magic happened - saw a moving bar, clicked a single button and it unpaired. Clicking both buttons and going to unpair couldn't detect any actions I've tried.. Almost drove me crazy :)
@jumadirosidi84213 жыл бұрын
hello, can one switch for control of 2 networks sir, thanks
@jumadirosidi84213 жыл бұрын
what is the luminare capacity for 1 network
@CasamBee3 жыл бұрын
Yes, it's technically possible. But it takes quite a long explanation and actually installing it isn't quite as easy as it seems. Give me a few days and I'll make a new video about this.
@CasamBee3 жыл бұрын
@@jumadirosidi8421 Classic: 127, Evolution: 250
@jumadirosidi84213 жыл бұрын
@@CasamBee ok we will wait, and hope soon, thank you
@CasamBee3 жыл бұрын
@@jumadirosidi8421 I've now made a video on this topic. It's Tutorial 17 if you want to watch it. Sorry it took so long!