Пікірлер
@HarishSingh-fi1kh
@HarishSingh-fi1kh 12 сағат бұрын
1 इंच का पाइप 14 मंजिल तक पानी 1 कि की
@RajeshSingh-poulterybioscience
@RajeshSingh-poulterybioscience 4 күн бұрын
Sir any equipment for poultry environment temperature cooling
@LearnWithMir95
@LearnWithMir95 4 күн бұрын
@@RajeshSingh-poulterybioscience you can use air circulation fans and exhaust fans for air movement and temperature control
@Surya-kp8qv
@Surya-kp8qv Ай бұрын
The hardest part about making a perpetual motion machine is where to hide the battery
@tkgthambi119
@tkgthambi119 Ай бұрын
❤😂🎉😮😅😊😊
@girgashankar
@girgashankar Ай бұрын
Very good
@LearnWithMir95
@LearnWithMir95 Ай бұрын
@@girgashankar Thanks
@sanketsudhirjoshi1932
@sanketsudhirjoshi1932 Ай бұрын
Channel & angle ring ka weight calculatiob???
@LearnWithMir95
@LearnWithMir95 Ай бұрын
@@sanketsudhirjoshi1932 You mean Square box or what??
@sanketsudhirjoshi1932
@sanketsudhirjoshi1932 Ай бұрын
@@LearnWithMir95 circular channel frame. Circular channel weld around shell.
@razackjohny
@razackjohny 3 ай бұрын
Can you tell me the wattage consumption of the external unit and indoor unit per ton. Will it be cost effective if I use a 10 ton outdoor unit with 7 variable indoor units? (1 ton to 3 tons)
@LearnWithMir95
@LearnWithMir95 2 ай бұрын
@@razackjohny If you have 10 Ton outdoor unit then you can use 5 indoor units with 2 ton each or as per your requirement but with same tonnage as outdoor. Variation in tonnage outdoor to indoor will not be effective..
@razackjohny
@razackjohny 3 ай бұрын
Nice and crisp explanation 👌👌👏👏
@LearnWithMir95
@LearnWithMir95 2 ай бұрын
@@razackjohny Thanks
@Engineeringchannel-ro3sf
@Engineeringchannel-ro3sf 3 ай бұрын
Not really fly
@ArvelBithyni
@ArvelBithyni 3 ай бұрын
🥰🥰🥰🥰👍
@benediktjostingmeier2223
@benediktjostingmeier2223 3 ай бұрын
The flapping mechanism doesn't mirrow the bird at all that thing would fly super unefficient if at all
@sriramr7765
@sriramr7765 3 ай бұрын
Flapping Mechanism can be placed in the fins of a Plane ✈?
@maheshshindolkar4503
@maheshshindolkar4503 4 ай бұрын
Prize
@sharibmallick2575
@sharibmallick2575 4 ай бұрын
Explanation is good but can you tell me ,this unit is humidity showing 85 80% that time what will do , temperature is okey, like that 20, 21 degree Celsius
@glenhunt6247
@glenhunt6247 5 ай бұрын
🌸 Promo_SM
@EnjoyFirefighting
@EnjoyFirefighting 5 ай бұрын
What a bs!
@shukrimahmood
@shukrimahmood 6 ай бұрын
Thank you! 👍
@bdm191
@bdm191 6 ай бұрын
This is right because knowledge is power but experience is a hardwork power
@MatovuRonald-ej5vk
@MatovuRonald-ej5vk 6 ай бұрын
wow it performs in such a way
@ДмитрийКиселев-ш2з
@ДмитрийКиселев-ш2з 6 ай бұрын
Мощность индуктора какая?
@AzamAzam-fx1hy
@AzamAzam-fx1hy 7 ай бұрын
Yar tum to refrigeration sycle bta rahe ho is unit ka main kaam batao
@LearnWithMir95
@LearnWithMir95 7 ай бұрын
Bhai refrigeration cycle same he work krta hai sab mai...Iska kaam hai temperature control and humidity control as well.
@md.shahid4305
@md.shahid4305 7 ай бұрын
Nahi pata to batane ka nahi maaloom apch 2 ya 1 rakhe baagut koi 1 bhi rajhte hai koi 2 bhi rakhte hai
@LearnWithMir95
@LearnWithMir95 7 ай бұрын
Samja nhe bhai aap kya kehna chahte ho
@md.shahid4305
@md.shahid4305 7 ай бұрын
@@LearnWithMir95 sorry actually I don't understand how to apch value put 1 or 2 these value are confusing to please clear to me,
@LearnWithMir95
@LearnWithMir95 7 ай бұрын
ACH or ACPH is based on industry, national standards, international standards, client-specific requirements as well as location. However, based on our experience, a reference list is given, General Areas 0.5 -1.0 Meeting rooms 4 - 6 Normal Stores 6 -10 Chemical Stores 10 - 15 Educational Facilities 4 - 6 Student Classrooms 6 - 12 Library 4 - 10 Office Buildings 0.5-1.0 Municipality Buildings 0.5-1.0 Electrical Room 2-5 Pump Room 6 -12
@novasnet
@novasnet 7 ай бұрын
Motor de arranque se le dice aquí en RD 🇩🇴
@LG-qz8om
@LG-qz8om 7 ай бұрын
Looks like a lot of Friction. Probably very hot in Real Life. But keep coming up with more ideas. Something will be Best.
@D.R.O.N.I.K.S.
@D.R.O.N.I.K.S. 7 ай бұрын
Механический обогреватель-стружкообразователь.
@Aman-f1b6k
@Aman-f1b6k 7 ай бұрын
I think it is blow through type Air Washer because i Saw Fan before pad ?
@LearnWithMir95
@LearnWithMir95 7 ай бұрын
Yes brother
@Aman-f1b6k
@Aman-f1b6k 7 ай бұрын
@@LearnWithMir95 I also worked in one of HVAC company bro and just have 1 year experience
@Aman-f1b6k
@Aman-f1b6k 7 ай бұрын
I think you know our company Edgetech Air Systems Pvt Ltd, Delhi
@VibrantVisionsIndia
@VibrantVisionsIndia 7 ай бұрын
384 sq. Ft ka CFM kitna hoga
@LearnWithMir95
@LearnWithMir95 7 ай бұрын
CFM= ( Area x ceiling height x ACH)/60 =(384x8x2)/60 =102 cfm
@VibrantVisionsIndia
@VibrantVisionsIndia 7 ай бұрын
@@LearnWithMir95 Thanks you very much for quick response. You are always healthy and fit.
@Алексей-у9в8р
@Алексей-у9в8р 7 ай бұрын
Это если неприкипел, в моём случае отвёртка восьмеркой
@sandeepwadhavinde3399
@sandeepwadhavinde3399 8 ай бұрын
Thanks 👍🏻
@LearnWithMir95
@LearnWithMir95 7 ай бұрын
Welcome 👍
@RashidAli-rn2ls
@RashidAli-rn2ls 10 ай бұрын
Dont gaj per minute. This is a galane per minute
@yamlectures1799
@yamlectures1799 Жыл бұрын
Filter clean karana hai meko ahu ka
@ahmedmowafy1634
@ahmedmowafy1634 Жыл бұрын
what about the duct length ? the calculated CFM should be modified according the duct length, size and the distance where the exhaust fan will be located! how can i calculate all these variables to get the correct the CFM ?
@chandrakantprusty8878
@chandrakantprusty8878 Жыл бұрын
Ty sir
@beleiveandachieve2635
@beleiveandachieve2635 Жыл бұрын
How much it costs
@LearnWithMir95
@LearnWithMir95 7 ай бұрын
15-20k
@hafizshahid8754
@hafizshahid8754 Жыл бұрын
Great
@anilsurani2953
@anilsurani2953 Жыл бұрын
Very nice 👍
@Sensibullstockmarketnews
@Sensibullstockmarketnews Жыл бұрын
Carc pdx BMS configuration kaise karate hai control se video 📷 video 📷
@mohankavalangatt5934
@mohankavalangatt5934 Жыл бұрын
🌹good
@zahidtechmech1013
@zahidtechmech1013 Жыл бұрын
Bhai 2 kaha se assume kiye?
@SS-vc1rt
@SS-vc1rt 2 жыл бұрын
Asslaam-o-Alaikum Stulz indoor fan is not working reply me
@rougenajo7223
@rougenajo7223 2 жыл бұрын
Ye air washer kaha pe install kiya hai apne?
@LearnWithMir95
@LearnWithMir95 2 жыл бұрын
Minda kosei Gujarat
@miyangmiyan7855
@miyangmiyan7855 2 жыл бұрын
Maray pas ya use condition main Hain kisi ko zaroorat ha to btao
@miyangmiyan7855
@miyangmiyan7855 2 жыл бұрын
Price Kya ha
@LearnWithMir95
@LearnWithMir95 2 жыл бұрын
2 Ton PAC Unit price:- 3.2 lakhs
@raviprajapati7360
@raviprajapati7360 2 жыл бұрын
Thank you👆
@nitingothankar2601
@nitingothankar2601 2 жыл бұрын
++
@RahulSingh-vn4xv
@RahulSingh-vn4xv 2 жыл бұрын
Srry sir, Area of ractangle= length*breadth Not 2(length+breadth)
@faisalsaeed3321
@faisalsaeed3321 2 жыл бұрын
Dear Mir. helpful vedeo regarding duct work. Please mention for us the ranges of pressure for low, medium and high pressure ducts. Velocity and also explain this pre insulated duct material. is this also GI with insulation?
@vgames6792
@vgames6792 2 жыл бұрын
if i have two fans of 72.8 CFM and i will stack them on top of each other will i get 144 CFM?
@bakhtrawan3924
@bakhtrawan3924 2 жыл бұрын
Sorry bro totally confused how u get 2 and then cfm its mean we have know frist how much air change per hour after that we can get cfm and for knowing air change we need cfm whata this?
@miguelmagana7714
@miguelmagana7714 2 жыл бұрын
the number 2 that he is talking about is the vents. If you have a supply vent (air coming into the room from the system) and return vent (air returning to the system) that's why he has two. if you only had 1 vent (most typical on a bedroom) then it's only one. Hope this helps
@zameerparvezansari155
@zameerparvezansari155 2 жыл бұрын
Bhai aap k no chahiye kich baat karne ke liy