2020 NEC Changes series: 250.68(C) Grounding electrode conductor connections

  Рет қаралды 72,020

Ryan Jackson

Ryan Jackson

Күн бұрын

The NEC no longer allows rebar to be used as an interconnection between grounding electrodes. This videos explains the ramifications of the change and why it happened.

Пікірлер: 104
@JacobYoces
@JacobYoces 2 жыл бұрын
I appreciate your directness while saying plumbers are evil. They really are.
@RyanJacksonElectrical
@RyanJacksonElectrical 2 жыл бұрын
LOL
@wakes_inc
@wakes_inc 2 жыл бұрын
All of the worst examples of the trades taking the easy way out come from plumbers. Have a joist in the way of a plumber? Say goodbye to it. Didn't really need that joist anyways.
@christieporter5465
@christieporter5465 2 жыл бұрын
Hey Ryan, We never intended for the concrete encased electrode to be used as a bonding jumper to interconnect other electrodes. Although it was never tested as you mentioned, and that is one of the reasons we clarified the language in the 2020 edition. We did allow it for the metal frame of a building because 1) it is NOT likely to have the continuity of the metal frame interrupted the way metal water piping is likely to be interrupted. and 2) it is suitable for systems that have ungrounded service conductor that exceed 1100 kcmil CU or 250kcmil AL, in other words, no matter how small or how large your service is, the metal frame is akin to a properly sized wire type bonding jumper. With metal water piping it is the same issue, (as long as it is connected within the first 5' as it enters the building) the metal water piping will work again for the smallest service or the largest service. Rebar (concrete encased electrodes are a very different matter. For example, if you had a 3000A service that includes metal frame and a concrete encased electrode, the 4 AWG connection to the electrode is not the same as a 3/0 connection needed for the metal frame and using the 4 AWG to connect metal frame would not meet the requirements of the NEC.
@RyanJacksonElectrical
@RyanJacksonElectrical 2 жыл бұрын
I agree.
@jfbeam
@jfbeam 2 жыл бұрын
I've always thought rebar to be a bad choice. Unless it's tested, there's no telling if it's actually contiguous, or driven into the ground anywhere. All it takes is one concrete saw and your ground is no longer a ground, and you'd never even know it. Water pipes would also have to be tested, even if you can visually see it going into the ground -- how deep is it, and how far does it go before becoming plastic? While my house (80's) has a copper inlet -- 2' down, ~20ft to the meter -- it's grounded from a dedicated ground rod a few feet from the service connection. ("first disconnecting means") My parent's house (60's) used to be grounded from a cast iron pipe. A decade+ ago that was replaced with a proper copper rod when backup power was installed.
@keepitreal1448
@keepitreal1448 Жыл бұрын
The problem isn't his explanation of the code but inexperienced electricians . Ive seen a lot grounding practices from Jack Leg electricians who just don't know.
@KrazyKajun602
@KrazyKajun602 Жыл бұрын
What is code if a #4 ground wire is connected to the rebar within the footings of the slab that is encased, thus the bare wire is the only thing visible within the wall? Is this NEC 2020 code compliant?
@billyg4985
@billyg4985 6 ай бұрын
​@@KrazyKajun602I wish someone would answer this I'd like to know to.
@toctami
@toctami 2 жыл бұрын
Hey Ryan, I'm enjoying your videos, but i have a confession to make. Around 15 years ago or so you inspected the electrical install on a new build church, i was using the white wire iin a 12/2 mc cable as my switch legs in every room, you told me to mark them all black, i promised i would and you signed off on 4 way. But i never did LOL!
@RyanJacksonElectrical
@RyanJacksonElectrical 2 жыл бұрын
LOL I can't believe the building didn't burn down without that tape!!! 😅
@garagekeys
@garagekeys 2 жыл бұрын
Ryan is a good guy. You are a dishonest person that you did not keep your word wouldn't want you to ever work on my properties
@roudibien-aime2198
@roudibien-aime2198 2 жыл бұрын
Hi Ryan, 250.68 (C)(1) allows connection to the extended concrete encased rebar type. If all requires are met, are we allowed to run a#2 aluminum on a 400 amp service being #2 al. Is larger than #4 bare copper?
@RyanJacksonElectrical
@RyanJacksonElectrical 2 жыл бұрын
@@roudibien-aime2198 Yes, 2 AWG aluminum is allowed.
@davids8536
@davids8536 2 жыл бұрын
You savage
@grimdoomsday
@grimdoomsday 2 жыл бұрын
Plumbers? Evil? That kind of speech is gonna get my electrodes purposely cut.
@Icehso140
@Icehso140 4 ай бұрын
Only if an electrician is available to help the plumber understand the big words. LOL On our jobs I point out to the plumbers that they can be replaced by a plastic outhouse and a brother-in-law that needs a job really bad.
@effinawesome3088
@effinawesome3088 2 жыл бұрын
When's the last time I saw a copper water pipe underground? Every day lol
@RyanJacksonElectrical
@RyanJacksonElectrical 2 жыл бұрын
I guess it depends on where you are! 🤷
@garbo8962
@garbo8962 2 жыл бұрын
Here in the Philadelphia area they have used nothing but copper to feed houses & small businesses. They are slowly changing over to Led tubing after the water meter. Wired a large house a few years ago where the water meter was at least 150' from street. They installed an underground water meter by street and ran 1" type K copper tuning to supply the house.
@johnnyb8629
@johnnyb8629 2 жыл бұрын
The trend is to switch to PEX even in feed from the main in the street is trending to plastic. Here in Chicago all water pip is underground like 3 feet or more probably 4 feet so as to not freeze in winter but in the Southwest I see it above ground all the time. Personally , using water lines inside a building for ground is bad because plumbers routinely take that apart and if the screws on the bonding wire clamps are rusty then they are not going back on.
@infinitybeyond6357
@infinitybeyond6357 2 жыл бұрын
"spliced with water" so like a toaster in a bathtub? XD, made my day.
@azizullah1755
@azizullah1755 2 жыл бұрын
Thank you Sir I followed you Your Lecture is very easy for understand to NEC
@megavoltelectricllc4642
@megavoltelectricllc4642 2 жыл бұрын
Lol when I heard spliced with water my brain crashed but then was rebooted when you questioned yourself 🤣
@sparkyjerred419
@sparkyjerred419 2 жыл бұрын
Kansas City, Kansas / Wyandotte County requires copper waterpipe to the water meter still.
@bobbyb2952
@bobbyb2952 Жыл бұрын
Great video Ryan! Always informative and I love that you keep it real!
@paullindsey9409
@paullindsey9409 2 ай бұрын
Since rebar does not come in 1000' lengths (usually max 60'), the sections of rebar would have to be electrically connected together, not just touching with a piece of rebar wire tie around them. Also, unlike a water line whose location is well known and makes a huge mess when it is cut, someone could core or cut into the concrete right through the piece of rebar that is being used as the grounding conductor and never be the wiser.
@electricalron
@electricalron Жыл бұрын
As I heard you say “splice with water” I knew I’d already seen this video! 😂😂😂
@dudeinthewoods
@dudeinthewoods Жыл бұрын
Mis speaks, and then takes a big swig of his beer...haha, thank you for being a regular dude!
@bee4pcgoldrule.007
@bee4pcgoldrule.007 2 жыл бұрын
Some electricians and inspectors still dont realize the size of the grounding electrode wire is determined by the size of the largest UN-grounded conductor in the service entrance feeders .Its in the code book. . And some inspector's want a solid bare wire not insulated.
@nooneyouknowhere6148
@nooneyouknowhere6148 2 жыл бұрын
Evidently some electricians and inspectors don't read the code. As for the bare solid wire, i guess they have only seen a number six solid going to a ground rod.
@richardprice5978
@richardprice5978 2 жыл бұрын
@@nooneyouknowhere6148 to be far the book 📖 is thick so remembering all a one time for a pop quiz is hard, i end up reading it more than once for new questions i have or refreshing my memory about a part im working on
@MrOpinionCantSignIn
@MrOpinionCantSignIn Жыл бұрын
And our inspectors now want grounding wires to be shielded in any exposed areas between panel and ground clamp and to second ground clamp Residentially interestingly is capped (localy anyway) at AWG6 despite it being below the normal feeder to ground ratio at 200A systems
@10Flat
@10Flat 9 ай бұрын
That’s awesome you kept that spliced with with water 💦. Bravo Ryan 🤣
@sloppydoggy9257
@sloppydoggy9257 2 жыл бұрын
EE here. The idea that a continuous rod which is half burred and half not being half grounding electrode and half not is ridiculous if you ask me. The first problem with it is that it almost implies the bonding should be done under ground which would then make inspection impossible. The second part is that its just physically incorrect & under this reasoning you could never bond to the grounding electrode because the second your wire enters dirt the portion of it in the dirt is then a grounding electrode lmao. Of course you want your bond to the grounding electrode to be such that it would never be reasonably open from the grounding electrode, but lets not get carried away here trying to pretend one piece of metal is two just b/c its half buried and half not.
@michaelvrbanac6923
@michaelvrbanac6923 Жыл бұрын
Washington State, Mount Vernon, 2020 NEC: I just got off the phone with a local inspector, and he said that two rebar stub outs at least 20 feet apart (tied via tie wire using std construction practice) into the rebar footings is sufficient provided the rebar length is at least 20 feet. He also said that a #4 copper wire (20 ft bare tied to the rebar structure with 6-7 feet of protected wire) above the concrete) can be used instead of the rebar stub out. So, either system is ok: two rebar stubs at least 20 foot apart or #4 copper wire.
@dvone4124
@dvone4124 2 жыл бұрын
Is there also a consideration that the rebar of a large structure is not electrically continuous? The rebar won't be a single piece in your IKEA example, but multiple (likely rusty) pieces temporarily mechanically tied with maybe 16 ga. steel wire until it is locked in place with the concrete. Any bonding, even if it had been done, is certainly no longer accessible once the concrete hardens, and I doubt the concrete has a UL label as a bonding conductor.
@RyanJacksonElectrical
@RyanJacksonElectrical 2 жыл бұрын
No, the rebar is still permitted to be multiple pieces tied together with the wire when creating the electrode itself, see 250.52(A)(3). Also, nothing is ever required to be listed by UL, and a conductor doesn't need to be listed at all.
@samjames8185
@samjames8185 2 жыл бұрын
I just had a local building inspector tell me my ground wire to the ground rods ( we are required to use 2, 8 foot rods 6 feet apart) was supposed to be solid wire. I've looked up where it says that in the code and it doesn't, at least not where I can find it. For some reason #4 solid is in short supply, I couldn't find any within 15 miles and was in a crunch. I had 30 ft of #2 braided and used it, quite a bit overkill. He did pass it but not before raising my blood pressure.
@RyanJacksonElectrical
@RyanJacksonElectrical 2 жыл бұрын
It's not required. The Code specifically allows multiple GECs or bonding jumpers. See 250.64(F) and note that a wire between two electrodes is NOT a GEC, but rather a bonding jumper. That means the splicing requirementvof 250.64(C) does NOT apply.
@rupe53
@rupe53 Жыл бұрын
as I recall, the rods should be at least 6 ft apart. Most guys go 8 ft because it's an easy eyeball with no questions. The grounding wire is a solid piece" meaning no splices from the farthest rod to the ground bar in the panel. You can use solid or stranded wire.
@karenstein8261
@karenstein8261 2 жыл бұрын
Just a detail, but I believe that the green wire we see connected to the rebar is a violation. IIRC the NEC specifically excludes the GEC from the list of where green is allowed. Comments.?
@McmM-cv9sb
@McmM-cv9sb 2 жыл бұрын
Very good that makes very good sense.👍
@DawsonTyson
@DawsonTyson Жыл бұрын
If I had to guess at their reasoning; the skin effect is the conduction point of the material and the gauge of the material is its heat retention and dispersion factor, a corroded material will see increased resistance reducing or eliminating its ability to conduct a short over the desired distance causing a "blockage" so to speak causing the current to back up at the weakest point of the connection and a failure of connection would be the result.
@DawsonTyson
@DawsonTyson Жыл бұрын
@James Karrie false. Oxidized metals have a higher resistance than the base metal. Also; the skin effect is not millimeters deep it is microns deep.
@DawsonTyson
@DawsonTyson Жыл бұрын
@James Karrie this is why aluminum is rarely used and never used in buildings for electrical wiring. Many a fire have been caused by lightly oxidized aluminum wire.
@DawsonTyson
@DawsonTyson Жыл бұрын
@James Karrie no it wouldn't. We use solid core wire to safely carry high current. Stranded wire bundles offer a lower resistance but are prone to heating up quicker and at lower currents. This is why your vacuum cleaner power cable is warm after 10 minutes or more of use. The reason this works is the beauty of alternating current. If we were still using Thomas Edison's direct current Stranded wire would be the standard so that the power could go further. With A/C we can send more power with the same surface area 100 times the distance. The skin effect will also go deeper into the material at higher power but this sinking into the material is also fueled by heat. Keep it cool and will stay at the surface.
@keepitreal1448
@keepitreal1448 Жыл бұрын
I have to explain this to a lot of electricians who's not aware of the code changes and plumbers cutting out old metal pipes and replacing it with pvc.
@jskjsk3986
@jskjsk3986 9 ай бұрын
Defining an electrode as the underground portion is deceiving in that current may be flowing from the connection point on. Many plumbers have been killed opening water mains, and I believe the 5 foot rule is for that reason.
@RyanJacksonElectrical
@RyanJacksonElectrical 9 ай бұрын
No, the five foot rule is to ensure the premises wiring system will still be connected to the grounding electrode if a plumber replaces an aboveground portion with nonmetallic piping. There will always be current on any grounding electrode because they are in parallel with the utility's grounded conductor.
@rg2blades429
@rg2blades429 Жыл бұрын
Great video . Happy knife life
@ronaldramirez3256
@ronaldramirez3256 2 жыл бұрын
Good lecture. Thank you!
@davenag957
@davenag957 8 ай бұрын
Just putting these questions out there for opinions. This is in regards to a service entrance. If you have both a ufer connection point and a 20+' copper water main available, which would you choose as your grounding electrode? If you choose the ufer, you would still need to bond the water piping. If you choose the water pipe, would you abandon that ufer connection point, or use that as a supplemental grounding electrode? Many local utilities want a driven rod at the meter fitting regardless of what the AHJ requires, so that would qualify as your required supplemental electrode.
@RyanJacksonElectrical
@RyanJacksonElectrical 8 ай бұрын
You have to use all that are present, and if one of those is a water pipe it must not be the only electrode. So use the Ufer and water pipe and then you're done.
@sixofnine9407
@sixofnine9407 2 жыл бұрын
Love that comment about plumbers.
@vince6829
@vince6829 Жыл бұрын
Great explanation. Thank you.
@Ittiz
@Ittiz Жыл бұрын
Seems to me instead of just going on what someone said 70 years ago we should take another, more in depth, look. It could save contractors a LOT of money!
@chadgerman8173
@chadgerman8173 2 жыл бұрын
Thank you Ryan!!
@jeffsmith291
@jeffsmith291 2 ай бұрын
Hi Ryan, you almost answered the question I had that brought me to your video. Since this video is 2 years old, I hope I can still pose a question and get an answer back? My question is: can I use a rebar encased electrode, (EEC), bond it to the steel building at that location and then 100' away, bond the 400 amp meter service to the steel building? Rather than running an exposed bare wire up over the ceiling from the meter service to the EEC. Would that qualify as the grounded electrode for the service?
@MrOpinionCantSignIn
@MrOpinionCantSignIn Жыл бұрын
OK..... A piece of rebar in the concrete is 'never' grounding .... concrete insulates and rebar should never extend into the dirt as it introduces corosion into the rebar framework .... and 'corosion proofing' does not reall work long term and if it is likely interferes with contictivity to earth.... It can be used as a 'grounding plane' for the floor freequently needed gor 'differential' in large / multy floor buildings .... absolutely never considered actual ground . Intermaterial bonding creates risk of electrolysis and failed connections , therefore should never be relied on
@RyanJacksonElectrical
@RyanJacksonElectrical Жыл бұрын
Stand on a piece of concrete and touch an ungrounded conductor originating from a solidly-grounded system and tell me how well concrete insulates. As far as "actual ground," the NEC defines ground as "The earth." Obviously concrete is not "actual ground." But I never said it was and neither does the NEC.
@nabilkattan9318
@nabilkattan9318 Жыл бұрын
So if I may ask, can we then use Ufer in commercial or residential as grounding method?
@rudert56
@rudert56 2 жыл бұрын
Somewhere I saw a table that showed the multiplication factor for multiple ground rods in parallel if one ground rod isn’t less than 25 ohms. It was somewhere in the 250 part of the 2020 NEC I think. Anybody know where it can be found?
@im2yys4u81
@im2yys4u81 Жыл бұрын
250.56
@dennissmith7219
@dennissmith7219 Жыл бұрын
@@im2yys4u81 thanks
@Fullblastx2
@Fullblastx2 Жыл бұрын
Is a duplex with one continuous foundation allowed to have two SEPARATE Ufer grounding systems with 4 ga. copper wire connected at three separate points with approved concrete contact connectors 20' along the the concrete encased 20' long rebar for two separate 200 amp services, i.e. each service panel is connected separately to the rebar in the footings? I would use the flexible conduit to encase the 4ga. copper wire from the footing up through the slab below where the panel would be in the basement.
@lanceleavitt7472
@lanceleavitt7472 2 жыл бұрын
Why can't "ground" be a grounding conductor? -- I know, that's just crazy talk. ---
@petersplat6164
@petersplat6164 Жыл бұрын
I can see how earth can provide an electrical return, as in a ground. But looking at a rebar imbedded in concrete, something in my head says that no electrons, nor electrical potential, is ever going to travel through that hard concrete thick concrete. It might as well be rebar in a wall of glass. What's the physics that I'm missing?
@DarioBartolo
@DarioBartolo Жыл бұрын
Broooo <a href="#" class="seekto" data-time="185">3:05</a> is the most underrated and most ingenious explanation to give customers ~~ PLUMBERS ARE EVIL, EVIL I SAY. But it makes sense logically, most of them come to work drunk lmao
@nayivisdenis1401
@nayivisdenis1401 Жыл бұрын
Hi..Ryan,can you explain me what is the size wire for foundation grounding for building???/.abel casanova
@jehadabraham5825
@jehadabraham5825 Жыл бұрын
Why voltage drop down
@Junkawayllc
@Junkawayllc Жыл бұрын
Hey Ryan, on an existing pole barn for a 200 amp service with no plumbing or rebar stubbed up what would be the option? Also building has R panel so that would be bonded.
@tracynation2820
@tracynation2820 2 жыл бұрын
Super. 💙 T.E.N.
@rgmenon1148
@rgmenon1148 Жыл бұрын
Ryan, I am having a monolithic foundation poured and plan to use a 1/2 20 ft rebar in the footing as the CEE. Can I just have this rebar extended up through the slab and attach that to a #4 using a clamp to bond the service panel ?
@Holop88
@Holop88 Жыл бұрын
Yes
@james77011
@james77011 Жыл бұрын
Time <a href="#" class="seekto" data-time="346">5:46</a> is amazing 😅
@theseattlegreen1871
@theseattlegreen1871 Жыл бұрын
Hi Ryan have you ever seen a water meter that is underneath the ground outside the house? It looks like a small version of a manhole cover. I am used to water meters (like the one in your video) where I would Bond one before the water meter and one after the water meter. Any ideas? The house was built in 1980
@RyanJacksonElectrical
@RyanJacksonElectrical Жыл бұрын
My water heater is underground near the sidewalk.
@theseattlegreen1871
@theseattlegreen1871 Жыл бұрын
@@RyanJacksonElectrical water heater?? I was asking about your water main
@RyanJacksonElectrical
@RyanJacksonElectrical Жыл бұрын
@@theseattlegreen1871 meter, sorry. It is underground.
@theseattlegreen1871
@theseattlegreen1871 Жыл бұрын
@@RyanJacksonElectrical Okay no problem so how do you bond that?
@RyanJacksonElectrical
@RyanJacksonElectrical Жыл бұрын
@@theseattlegreen1871 you don't. It's thirty feet away from the house, so it's not part of the grounding electrode.
@KrazyKajun602
@KrazyKajun602 Жыл бұрын
What is code if a #4 ground wire is connected to the rebar within the footings of the slab that is encased, thus the bare wire is the only thing visible within the wall? Is this NEC 2020 code compliant?
@alec4672
@alec4672 Жыл бұрын
Yes, either it has to be secured to the rebar or 20ft of the proper grounding conductor size needs to be buried in the concrete (you do the 20ft option when there's not much steel in say a slab to tie into). It just makes it harder to verify that it was done right. Though to be fair I have seen electricians forget to have the rebar stubbed up in the right spot and they'll cheat and drill a hole epoxy a tub of rebar into it and tie onto that. That guy got fired from the company pretty fast.
@jordanharris3553
@jordanharris3553 2 жыл бұрын
Well why don’t we just test it then
@RyanJacksonElectrical
@RyanJacksonElectrical 2 жыл бұрын
Go ahead.
@james77011
@james77011 Жыл бұрын
Spliced with water 🌊😅 U just needed a sip of water sir 😅
@ryanjourneymanwireman4937
@ryanjourneymanwireman4937 2 жыл бұрын
Spliced with water.... Have another hahahah
@realestateservicessaleshea99
@realestateservicessaleshea99 2 жыл бұрын
🥃🍺🤔👍🏻
@james77011
@james77011 Жыл бұрын
<a href="#" class="seekto" data-time="345">5:45</a> 😅
@jlyn9047
@jlyn9047 2 жыл бұрын
Plumbers Evil , don’t think you should have said that . There are a lot of good plumbers out there !
@RyanJacksonElectrical
@RyanJacksonElectrical 2 жыл бұрын
It's a joke...
@mikemarlowe6102
@mikemarlowe6102 2 жыл бұрын
lighten up Francis
@gusmartinez90
@gusmartinez90 10 ай бұрын
Here is to water 🍺
@marvinj1972
@marvinj1972 Жыл бұрын
Never trust plumbers 🤣🤣🤣
@myronwilliams7
@myronwilliams7 2 жыл бұрын
Plumbers are evil people 😜
Kitchen islands and peninsulas in the 2023 National Electrical Code
17:14
2020 NEC changes series: 110.14 Conductor Terminations
23:28
Ryan Jackson
Рет қаралды 81 М.
My Cheetos🍕PIZZA #cooking #shorts
00:43
BANKII
Рет қаралды 26 МЛН
Why Is He Unhappy…?
00:26
Alan Chikin Chow
Рет қаралды 107 МЛН
Little brothers couldn't stay calm when they noticed a bin lorry #shorts
00:32
Fabiosa Best Lifehacks
Рет қаралды 18 МЛН
Please Help Barry Choose His Real Son
00:23
Garri Creative
Рет қаралды 20 МЛН
How to Size Grounding Electrode Conductors "GEC" Full Lesson
13:40
Electrical Code Coach
Рет қаралды 15 М.
The Easiest Way To Drive Grounding Rods
6:45
Practical Home Projects
Рет қаралды 179 М.
Grounding and Bonding an Electrical Panel
13:24
Appalachian DIY
Рет қаралды 308 М.
Grounding and bonding
29:15
Eaton
Рет қаралды 37 М.
Why Neutrals & Grounds are Connected in a Main Panel
20:13
Benjamin Sahlstrom
Рет қаралды 1,5 МЛН
Grounding and Bonding
8:01
schulerruler
Рет қаралды 668 М.
My Cheetos🍕PIZZA #cooking #shorts
00:43
BANKII
Рет қаралды 26 МЛН