3in wye strainer replacement

  Рет қаралды 220

Dave Adamson

Dave Adamson

Күн бұрын

Пікірлер: 3
@glenn4452
@glenn4452 Жыл бұрын
Nice job,looks a lot better now
@rodneyandrade4919
@rodneyandrade4919 11 ай бұрын
That meter and strainer should not be installed between the #1 shutoff valve and backflow preventer there after, as approved backflow prevention assemblies are classified, approved and supplied as a complete assembly with direct inlet and outlet shut-off valves. However you likely would have had to shut down the supply from the water meter in order to make the correction.
@dave_adamson
@dave_adamson 11 ай бұрын
Yeah I inherited it when it needs to be replaced I will correct it. For now they don't want to spend the money. It's original so was approved at some point by an inspector