Very professional explanation, I am retired licensed state HVAC, I don't do much work anymore, but I keep watching videos to keep my memory sharp, I am 68 still active. Thank you for taking the time to share your knowledge.
@johnjennings-JJ3 жыл бұрын
It isn't much knowledge! I do try to keep thinking about hvac stuff because we do lose some of it when we stop using it. Stay sharp and thanks for watching.
@coolramone2 жыл бұрын
Hey can one of you guys more experienced than me tell me, what if you run the yellow wire (cool) from the thermostat to the condenser AND to the blower motor in the air handler? Can you wire it that way?
@johnjennings-JJ2 жыл бұрын
Depending on exactly where you do the connections the answer is "Sure"...when the t'stat calls for the contactor on Y it will also call for the blower. But, when the t'stat calls for the blower on G it will also call for contactor too! So make sure if you do something like that you think about the flip side of the coin. The old school mercury t'stat had the G and Y physically tied together like you are thinking. W just turned heat on and the unit would turn the blower on. Nowadays the digital t'stats do the same thing through the programming and initial setup. Hope my 2 cents worth helps.
@coolramone2 жыл бұрын
@@johnjennings-JJ In that case could you connect the yellow (cool) and green (fan) to the same terminal on the blower motor contactor? Or would you need a second contactor?
@johnjennings-JJ2 жыл бұрын
You could put both Y and G on the coil of the blower relay/contactor if you had room to do it but that ties in to what I was saying before, if you just wanted to circulate air and run G then it would also run the compressor each time. Depending on what you are trying to do with the circuit/operation...just remember that the more stuff you tie together the more precise you have to be with the wiring. Are you trying to do something specific or just tinkering around?
@JS-ur8lw Жыл бұрын
I really enjoy your knowledge and detail on explaining Components. I've been doing HVAC for many years now!! Your videos are what I will show my young techs coming in!!! Thank you for taking the time and doing this!!!
@johnjennings-JJ Жыл бұрын
Appreciate the kind words!
@jacobreinen5392 Жыл бұрын
Phenomenal job articulating technical content in a clear, methodical, and meticulous manner. It is so very much appreciated! Please keep them coming!
@johnjennings-JJ Жыл бұрын
Thanks.
@ponzo1967 Жыл бұрын
By far the clearest explanation of a basic relay 🤔😁💡
@johnjennings-JJ Жыл бұрын
Thanks
@jmead6121Ай бұрын
Thanks best explanation on this 90 340 relay ive ever seen esp the Right to left .. scenario used to trip me overtime if Iam adding an relay not just replacing an existing relay bc one can just go wire for wire but adding an relay for what ever reason can be tricky to some including myself
@Okie-Tom7 ай бұрын
Your demonstration board helps. Understanding voltage drop and voltage potential screws a lot of people up! Thanks
@justiniancasillas10696 ай бұрын
Thank you this video has taught me more about relays than my hvac school has taught me
@johnjennings-JJ6 ай бұрын
Got to start somewhere...lot more to learn!
@johnnyriser85196 ай бұрын
Thank you so much for the straight-forward, simplified explanation. You are an excellent teacher. Thanks for sharing!!
@emoneyblueАй бұрын
Thanks for sharing the knowledge.
Жыл бұрын
Maannn!!! ... I just came across this video,,, Thanks for putting this info out. It has help to clear up a lot of my cob webs.
@franknovak79333 жыл бұрын
Wow ! Of all the videos Ive seen on relays this is one of the best ! Thxs for sharing your well explanation on this subject you are truly a professional .I subscribe to your channel after seeing it ! Thanks again
@johnjennings-JJ3 жыл бұрын
I appreciate it. I just hope it helps. There are a lot of ways to get mixed up on switches. I have been there and done it myself too many times.
@masongriffith85592 жыл бұрын
At the 16 min mark you should put the black probe on a ground and then check, that would be the best way to explain it. You would have 120v at the wire you are checking if the light is on. The power difference you are talking about is correct but makes that explanation hard for some people.
@johnjennings-JJ2 жыл бұрын
Thanks for the insight and comment. Since doing this video I have tried to put a few checks in "to ground". I even did a video on why I don't like to use ground for a lot of voltage checks but that is beside your point. I think for this video I wanted to do some checks to ground but to honest...that board wasn't grounded! I'll try to include more in the future. Thanks again.
@Sbrabson046 ай бұрын
Thank you so much for your knowledge. I kept getting hung up on why I didn’t have voltage
@christianurbano14832 жыл бұрын
One of the best explanation I’ve seen so far.After watching it I said I must suscribe to the channel,Thanks .
@johnjennings-JJ2 жыл бұрын
Thanks. Relays and voltage checks got me early on so I put this video out just to try and help someone else.
@hugogarcia7574 Жыл бұрын
Thanks has you said I finally understood this relay thanks to you
@johnjennings-JJ Жыл бұрын
Thank you.
@teklesenbetgebreamlak73653 жыл бұрын
Thanks for the great details explanation how it works fan relay really l wasn't understanding clearly lam new hvac apprentice thanks again
@johnjennings-JJ3 жыл бұрын
No problem. We all were new hvac guys at one time. Thanks for watching.
@ritchpoint2 жыл бұрын
Thanks for a thorough explanation
@johnjennings-JJ2 жыл бұрын
No problem. I hope it helped a little bit if you needed it.
@paulbryant68 Жыл бұрын
light bulb just came on in my head too! thx great example
@theprofessor5584 Жыл бұрын
Very good video, really like the way you explain things
@johnjennings-JJ Жыл бұрын
Thanks.
@jetko43 Жыл бұрын
THANK YOU FINALLY UNDERSTAND SWITCHES. I WAS THAT TECH
@johnjennings-JJ Жыл бұрын
I think we all were...thanks for watching.
@coolramone Жыл бұрын
“Typically” what are the two power sources coming in on 3 and the other on 2? 14:00
@johnjennings-JJ Жыл бұрын
The way that a lot of manufacturers use the PSC blower by having 1 speed for both heat and cool mode operation leads me to say that you have a direct wire from L1 coming into terminal 3 and also a wire from the load side of the heat relay switch bringing L1 into terminal 2.
@1971omi3 жыл бұрын
Great explanation. Great teacher
@johnjennings-JJ3 жыл бұрын
Thank you.
@balfretsoriano47953 жыл бұрын
Thanks again and it was a great teaching!
@johnjennings-JJ3 жыл бұрын
Thanks
@marshallstephens73562 жыл бұрын
Fantastic video. Thanks so much for sharing!!!
@johnjennings-JJ2 жыл бұрын
Thanks .
@CHOMAHOMA3 жыл бұрын
Great. Thank you. I am Learning A LOT.
@johnjennings-JJ3 жыл бұрын
Awesome..
@argenismoreno72532 жыл бұрын
Thank you so much, from Venezuela
@johnjennings-JJ2 жыл бұрын
Thanks. I often wonder how different the ac unit is other countries...
@joe-hn9fd Жыл бұрын
Great videos, very helpful.
@johnjennings-JJ Жыл бұрын
Thanks
@hvactipsnow98923 жыл бұрын
Good information and video quality....Easy to follow instructions on all aspects of the power duty relay!!! 😎
@johnjennings-JJ3 жыл бұрын
Thanks! 👍
@drh4882 ай бұрын
What does the normally closed position control in an air handler for heat pump with heat strips. Anything?
@johnjennings-JJ2 ай бұрын
The normally closed switch is usually used as a redundant circuit if a electric heat kit is installed. After power goes through the heat relay, there is a circuit that powers the heater and also one that goes to the normally closed switch on this fan relay. It powers the fan motor anytime the heat strip is on.
@joselora6169 Жыл бұрын
nice and I'm assuming all thr common wires are in a 1900 box or on a board if there is one
@EyeForKnowledge.2 жыл бұрын
A switch is a switch. A relay works the same as a contactor or a sequencer. 24V coil, power in common out. I had a hard time with relays and sequencers until I came to the realization that they work the same as a contactor.
@johnjennings-JJ2 жыл бұрын
Sounds simple now but I remember calling my supervisor 5 times a day...once upon a time. I try to tell these new guys I see that "you hear me but you ain't listening" !! If they could truly understand and get it in their head that a switch is a switch...just like you said boss. Thanks for commenting and checking it out.
@HenryD8997Ай бұрын
Merry Christmas to you and your family,sir! Thank you so much for all the great lessons video that you made, it helped me a lot in the field. May I have a question for the 90340 relay? So when we in the heat mode so we have the power 24 voltage to the contactor that kick in and 240 voltage form L1 L2 power to the other side and turn on the heat strip. Then the blower fan will turn on and the terminal 2 of the 90340 relay will energize the power to terminal 1 ( speed taps) and terminal 1 to 3 will open right?
@johnjennings-JJАй бұрын
Sounds right. Power goes in on terminal 2 and 3 and then out on terminal 1 to the blower. This way no matter if you have 24 volts on the 'G' or not the PSC blower should come on.
@HenryD8997Ай бұрын
@ thank you so much sir
@mts72742 жыл бұрын
9:10 ...my old Honeywell relay had only 8 terminals, but the replacement part has 10 like the one shown here. The circuit schematic [numbering] molded into the plastic back is exactly the same, though. Do I need to use those terminals on the very edge (where your thumb is)? I can't imagine they can be left open or uncovered, but there aren't any extra wires to attach there.
@johnjennings-JJ2 жыл бұрын
No, not necessarily. They put two male terminals on each side of the relay. As long as you put your 24v common on one side and the 24 "hot" (like the green wire) on the other side of the relay it should be good. They give you 2 male terminals on each side as an extra to maybe connect another 24v wire to it from another relay. Only use what you need!
@mts72742 жыл бұрын
@@johnjennings-JJ Thanks! Yeah, the replacement part from Grainger looks EXACTLY like the original OEM part except there are four terminals on either side instead of the original three on each side. And the replacement is like $80 cheaper than an unused [discontinued] OEM relay. Same voltage, amps and everything. Peace!
@MarkThrive2 ай бұрын
17:00 light bulb on ! 💡😮
@johnjennings-JJ2 ай бұрын
Awesome!
@theonetoday2 жыл бұрын
Hi My 90-340 is 8 pin for 8 pin socket. Will this 10 pin 90-340 fit my socket - extra coil blades hang over the socket and not touch anything?? I cannot find a different marking or part number for 8 to 10 pin 90-340????
@johnjennings-JJ2 жыл бұрын
Never seen a 90-340 with a socket before. I have seen more 10 pin than 8 pin but never a socket. I would think in a pinch you could clip off the extra 2 coil connections and make it work though...but that is just me.
@theonetoday2 жыл бұрын
@@johnjennings-JJ Thanks John, I have a White Rodgers 90-130 Fan Control Center that has the socket - 8 pin. My relays are not marked but the spec sheet shows the 90-340. All pics of the 90-130 have an 8 pin socket?????
@vincentliggio3320Күн бұрын
Excellent example change the colors of the light bulbs and that would be perfect
@dammo361 Жыл бұрын
Best video in explaining the voltage part on relay in the most simplest terms... 💪🏼🧰🥷
@johnjennings-JJ Жыл бұрын
Thanks
@gotchaplumber5 ай бұрын
Great explanation!
@RC-Heli83510 ай бұрын
I have one 90-340 to turn the inducer motor on in my old Rheem gas furnace and a 90-370 which G controls for fan. Whether I'm in heat or cooling mode, G flips the 90-370 relay to turn the high AC fan on immediately on startup. When the thermostat is satisfied and G goes away, then the medium fan comes on at the normally closed contacts of the 90-370 which runs also through the fan limit switch and will run the fan until the furnace cools down to 120 degrees and the fan limit shuts the blower off if the furnace is on. That circuit stays hot until the 90-370 is pulled in. This is how I found it! Can you recommend a better way to set this up? I want the heater fan to come on with the fan limit switch when temp gets to 80 degrees, run on medium and stay active to cool the furnace down after W and G go away. What I don't need is the Fan On switch at the thermostat to turn hi fan on while the heater's medium fan is on. I basically don't need G to function if W is calling for heat. Thanks for sharing!
@johnjennings-JJ10 ай бұрын
I think the equipment should control the fan in heating mode anyway...like you were saying. No 'G' when 'W' is calling. The thermostat should be setup for that whether it is an older one or a new digital one. Not knowing if you have a digital tstat or not, I would say check the programming. There is an option , or a selector switch, that will, or should at least, prevent the 'G' from being energized on a call for heat....that is, unless you have a thermostat problem and 'G' is energized due to that (but I doubt it)
@RC-Heli83510 ай бұрын
@@johnjennings-JJ Thanks I found a way to control G while W is on. The trick is to let the W relay send power to the G relay for medium heat fan while W is on or off. Then if G comes on without W it turns power off to the medium fan and turns on the high AC fan.
@viper223043 жыл бұрын
Thanks for sharing the video. Could you share how you have the set-up so i could practice and understool how it works.
@johnjennings-JJ3 жыл бұрын
Sure thing. I have a video that I haven't posted and was waiting to make it public but it might be something you could use. Try it and see if it works. kzbin.info/www/bejne/imq2goCFn6qbjdE
@GotchaplumberGotchahvac3 жыл бұрын
Will you do video explaining difference between 90340 & 90380 relay? Thank you.
@johnjennings-JJ3 жыл бұрын
I will try to get to that one. Thanks.
@griffinbrown1182 Жыл бұрын
Hi there! Currently replacing one of these on my woodburner furnace. Should this get hot amd hum when power is applied??
@johnjennings-JJ Жыл бұрын
I have seen a lot of them get warm to the touch and hum too. Seems normal from my experience. It does have electricity flowing through it. I guess you could go with a circuit board setup but that might take some modification...may be a little quieter.
@olurotimiadepitan50872 жыл бұрын
Thanks for your wonderfully helpful videos. So high voltage goes from the transformer to the relay normally open. Is this necessary for the relay to power the fan?
@johnjennings-JJ2 жыл бұрын
High voltage relay comes from the main terminal block but some of the units will have it coming from the transformer only because it is a closer connection to L1 or L2. Either way of supplying main, high voltage power is needed in order to power the fan motor through the relay in a cool mode operation or just fan "on" operation.
@That_40yrOld_Dad Жыл бұрын
Is that relay anything similar to the 12-wire plug-in on the circuit board, I see it's numbered just like it
@johnjennings-JJ Жыл бұрын
The circuit board plugs can be/are a little different than this relay. The plug can have both high and low voltage going through it in order to check safeties and flame sensors if it is in a furnace. The relays on a circuit board are typically those raised black boxes on a circuit board.
@smacleod69 Жыл бұрын
Could also describe the change in path or direction of voltage like a railroad track switch. NO position you want it to left. NC having the voltage go right.
@johnjennings-JJ Жыл бұрын
Never thought of it that way, i like it.
@franklinknight14603 жыл бұрын
wonderful grate teacher very good explenations
@johnjennings-JJ3 жыл бұрын
Thank you.
@GB-ue6wr2 жыл бұрын
Great explanation!!
@philochristos2 жыл бұрын
Why would there be 24 volts across the two terminals when the coil is one continuous wire from one terminal to the other? Shouldn't there be zero volts?
@johnjennings-JJ2 жыл бұрын
It is a "load" in the 24v circuit. It is the one thing we are powering and consumes the power. If checking voltage at a load you should get XX amount if working and a switch in the same circuit would be 0 volts as that load works.
@darrellwofford4052 жыл бұрын
what would cause to burn off the element from the relay
@johnjennings-JJ2 жыл бұрын
Loose connection maybe...that would generate a lot of heat at that particular point in the circuit/wiring.
@darrellwofford4052 жыл бұрын
@@johnjennings-JJ I not a electrician so it done it 3 or 4 times I was thinking it was a relay or something thanks for replying
@andybauer43633 жыл бұрын
Great videos. Thanks John
@johnjennings-JJ3 жыл бұрын
Thanks.
@simmonsjr253 жыл бұрын
Awesome video and info.
@johnjennings-JJ3 жыл бұрын
Hope it was helpful.
@bluegrassdna55723 жыл бұрын
There's no difference between them. I think I will use that next time I explain it to a new guy in the field. Too many guys sourcing power to ground and getting confused or don't know how to check a fuse with power applied. Thanks.
@johnjennings-JJ3 жыл бұрын
Never like checking to ground. I try to tell my guys that you always check back to your power source. Thanks for watching.
@realSamAndrew3 жыл бұрын
How do you check a fuse with power applied?
@bluegrassdna55723 жыл бұрын
Across both fuse points. If you read voltage between both ends of your fuse, the fuse is open.
@johnjennings-JJ3 жыл бұрын
(Something happened and I couldn't see the comment but i agree with BLUEgrassBLOOD on this one)
@realSamAndrew3 жыл бұрын
@@bluegrassdna5572 but what if you're not sure if power is flowing? Open fuse (or closed for that matter) reads zero voltage there also. It's really tricky to me.
@realSamAndrew3 жыл бұрын
Why is it called 90-340? Do those numbers mean anything or is that just the part number and people learned to call it that? For example, a 35/5 capacitor means the mfd level on 2 different circuits. 90 and 340 mean anything??
@johnjennings-JJ3 жыл бұрын
More or less just a part number from the manufacturer. There is a 90341 and 90342 as well. The 90340 is a double pole single throw relay with a 24v coil. I think the 90341 is just one with a 120v coil and 90342 is a 208v coil.
@realSamAndrew3 жыл бұрын
@@johnjennings-JJ thanks for the quick response. Just a note to clarify-- isn't the 90340 actually dpdt ? That's what other sources list it.
@johnjennings-JJ3 жыл бұрын
Sorry. Yes it is. I meant to put down that down but I guess I got caught up typing. My bad.
@johnjennings-JJ3 жыл бұрын
I think it was all that turkey and ham talking from this past week!
@tercyalexanderdiaz51572 жыл бұрын
Finally understood.
@johnjennings-JJ2 жыл бұрын
Can you teach me...i am still trying!
@devinwilliams34893 жыл бұрын
I have an old furnace with single stage a/c that has had it's original nordyne control board that connected to the thermostat and controlled everything replaced with a packet pr380 relay. Do you think that was an appropriate repair? The system does work
@johnjennings-JJ3 жыл бұрын
I am not exactly familiar with all the nordyne controls and there are a lot of reeplacement components out there for professionals to use. Personally, i can and have used a "universal" part to fix a customers system and it worked fine. I would say if it works properly...i wouldn't worry about it.
@LaughLiveLove5632 жыл бұрын
Great video , thank you !
@johnjennings-JJ2 жыл бұрын
Thank you for checking it out.
@Seeykulatahy9 ай бұрын
Thank you very much
@treyfurniss65763 жыл бұрын
Very very helpful thank you
@johnjennings-JJ3 жыл бұрын
Thanks. Switches can be confusing sometimes so I hope this does help a little.
@kyle_1873 жыл бұрын
What happens if you voltage to ground when the switch is closed will it say 120 or still 0?
@johnjennings-JJ3 жыл бұрын
If you check voltage to ground at the switch when it is closed you should find 120 on either side of the switch. Watch out checking voltage to ground though, it messes with a lot of people.
@bakemmmmm3 жыл бұрын
You doing so good
@johnjennings-JJ3 жыл бұрын
Thanks.
@migneg4853 жыл бұрын
wow thank you!
@johnjennings-JJ3 жыл бұрын
Your welcome. Hope it helped.
@markferguson34773 жыл бұрын
Great video but I would like to see how u wire the circuits
@johnjennings-JJ3 жыл бұрын
Thank you. That video is actually on my list to do in the next month.
@markferguson34773 жыл бұрын
@@johnjennings-JJ cool, looking forward to see that video. I'm very young in this trade and the stuff u talk about school doesn't teach me those.
@johnjennings-JJ3 жыл бұрын
I don't know if you really wanted to see the wiring of circuits on a practice board or a real unit. I made this recently in preparation for some stuff I have going on next month. If it is what you wanted to see, let me know what you think as I have it unlisted right now. If you don't watch it it is no big deal. Thanks kzbin.info/www/bejne/imq2goCFn6qbjdE
@markferguson34773 жыл бұрын
@@johnjennings-JJ k, will do
@juangallegos57522 жыл бұрын
Eso está bueno
@johnjennings-JJ2 жыл бұрын
Thank you.
@damon820110 ай бұрын
Very detailed video. I'm gonna share this with my fellow techs and all the rookies. 🫡
@ignacioalmaguer31324 ай бұрын
how do you determine how many n/o or n/c do mi have
@johnjennings-JJ4 ай бұрын
If you are looking at a relay it should have a sticker that shows you or tells you. It may even be "drawn in" to the relay itself. You would notice it is a raised part of the surface of the relay. If you can't see any information on it I would not use it. Just get another with the specs that you need.