In this Video Function of Antipumping Relay has been show.Please go through the video so to understand how Antipumping Relay work.
Пікірлер: 11
@surendrakverma555 Жыл бұрын
Excellent lecture Sir. Thanks 🙏🙏🙏🙏
@subhranilmallick19912 жыл бұрын
Very nice concept
@prabhatsingh5377 Жыл бұрын
Under frequency and under voltage load shedding testing par bhi video banaiye
@relayprotectionelectrical Жыл бұрын
Ok I will
@saurabhbansal7193 Жыл бұрын
Sir make vedio how to detect fault by drawing reading
@relayprotectionelectrical Жыл бұрын
Ok I will
@umeshpanda55672 жыл бұрын
Gret
@rjshtk2 жыл бұрын
Why do you need S0 contact? Can we not use the S0 contact in series with the 94 coil?
@relayprotectionelectrical2 жыл бұрын
S0 contact is the CB aux contact. Purpose of Antipumping relay is to avoid another pulse to CC of CB. That means if CB is on then only function of Antipumping Relay comes. That's is why S0 contact is used in series with 94 R.
@user-khanaamir8765 Жыл бұрын
If S0 NO contact is sufficient then why is 94 R NO contact used
@rjshtk Жыл бұрын
@@user-khanaamir8765 the NO contact of 94 is to prevent closing pulse from reaching a close coil in the event of cloding the cb on to a fault and holding the tnc lever for a while..