ماشاءاللہ سر ایک اور معلوماتی ویڈیو دیکھ کر خوشی ہوئی اللہ اپ کے علم اضافہ فرمائے
@test09576 ай бұрын
This man is an amazing master in his job. With his help, through online consultation, we repaired two 5KV UPS controller board. . Only after describing the problem, he immediately showed us the damaged part... Now both of UPS working like a new. Lots of thanks and recommendations from me. I want everyone who has had problems with UPS devices, to know about him. He has an expert knowledge. That's why I write this comment on all his videos. I spent 4 nights without sleep looking for the problem. 👍 👍👍
@ImranNazar-v4x4 ай бұрын
Please make a video of extremely over voltage apc srt5000
@AKElectroTech4 ай бұрын
@@ImranNazar-v4x Ok
@ganeshm1735Ай бұрын
Sir i am checking one surt3kva when i soft start battery relay 702 not closing,then i found q707 getting fault when start.i changed control card at that time q707 not getting fault.What may be the fault with control card having connector black flat type not the ethernet type
@ganeshm1735Ай бұрын
Sir I have another doubt can I use 10kva control to check 3kva to verify the problem with control card
@AKElectroTechАй бұрын
@@ganeshm1735 there will be multiple faults that controller stop PSDR power.
@ganeshm1735Ай бұрын
@@AKElectroTech ok sir can I use 5kva control card in place of 3kva
@AKElectroTechАй бұрын
@@ganeshm1735 Yes It it compatible with each other
@rajukv59159 ай бұрын
sir ji . i want to down load SW from ST72324 MCU which is used in APC BI850sine Inverter ..can u pls suggest how to do that . I have CH341A in my hand
@varishali91114 ай бұрын
SurtD5000 uxi controler card working ok but no display..... Only display not working... No LED glow.... Only on off button working.. Where we serch fault in controller card... Please reply
@AKElectroTech4 ай бұрын
@varishali9111 ON/OFF switches on display panel are separate and rest LEDs are separately operated on display panel. First of all check RJ45 cable between controller and display panel. Check connection between IC 3 pin 2 which is used on display panel. This is +5v DC used on display panel. If +5v is coming then check RN24. I hope you will find solution
@rizwanullah28926 ай бұрын
sir 5kva mai fan error kese clear krna haia
@AKElectroTech6 ай бұрын
replace fan or drive where connector is connected. IC36 and Q36 are used for fan drive and fan error
@rizwanullah28926 ай бұрын
@@AKElectroTech sir aik capactor damage hai control pe number hai uska 33 35v L09 fan on na huni waja ye tu nhi kia
@AKElectroTech6 ай бұрын
@@rizwanullah2892 These all capacitors 33uf35v are connected on power supply portion. What is L09 and where this is located
@rizwanullah28926 ай бұрын
@@AKElectroTech 33uf35v l09 is complete model number of capactor sir .
@AKElectroTech6 ай бұрын
Ok replace it if it is damaged.
@lucasnorbach10 ай бұрын
Ola amigo, voce vende placa de controle surt 6000,
@AKElectroTech10 ай бұрын
Hello friend No at this time.
@PakGuides8 ай бұрын
Greeting sir, I have a surtd 3000xli showing the error 00010 I replaced the control board with a new one, and the error is fixed. Can you help me sir where is the fault in faulty control board. Thanks in advance
@AKElectroTech7 ай бұрын
@PakGuides This fault 00010 is related with backfired relays. Backfeed means that AC input relays are not operating. There may be so many issues in control card. 1. Backfeed relays are operated by IC18 (ULN2003). Check wiring pin 13 of this ic to backfeed relays. 2. It is possible that controller stop back feed relays due to not sensing AC input. You can check D23, IC35 and IC27 and related components. This portion is used for AC sensing. 3. It is possible that ADC is not sensing AC references at pin_120 and pin_121.
@PakGuides7 ай бұрын
@@AKElectroTech sir, bundle of thanks
@RahmatBabbar2 ай бұрын
Sir Mary pass ye ups khula para hy wo bilkul on nhy Hu rah iski koi led on nhy Hu rahy .koi relay nhy lag rhY us K control volt drop Hu rahy hn kindly is ka circuit diagram send ker dyn. Jazak Allah
@AKElectroTech2 ай бұрын
Check 13V at ON button if not present then check IC 4093 at control card.
@RahmatBabbar2 ай бұрын
@@AKElectroTech ok sir
@emsa_co Жыл бұрын
Hi bro, Please take a video about ((backfeed relay weld)) fault in apc ups.
@emsa_co Жыл бұрын
When this fault happens,led 2 from down to top turning on.
@AKElectroTech Жыл бұрын
Ok
@AKElectroTech Жыл бұрын
@@emsa_co It is the reflection of lower LED. Only one is glowing with fault LED
@mailsonfreitas396711 ай бұрын
olá tenho uma placa de controle do SURT 6KVA com falha PFC como eu faço pra resolver essa falha
@AKElectroTech11 ай бұрын
Hello Which PFC side is not working. Pl follow these steps Install batteries in ups and apply input voltage to ups. UPS power supply will activated and check DC positive bus on d716 and DC negative bus on d715. Now which bus side is not working on supplying input power to ups.
@mailsonfreitas396711 ай бұрын
a placa de controle assim que colocar a tensão de entrada ele já dispara o disjuntor da bancada. Não dar tempo de verificar as tensão positiva e tensão negativa no diodo.@@AKElectroTech
@AKElectroTech11 ай бұрын
@@mailsonfreitas3967 You mean that input circuit breaker tripped when applying input voltage to ups. If this condition appears then check input circuit of PSDR board. Otherwise follow these steps: Connect batteries to ups and connect dmm negative lead to battery black and positive lead on d716. Now switch 'ON' ups on battery and check DC voltage on this diode. Same for d715 diode and check DC voltage. Also check that ups is normal functioning on battery or going to pfc fault state. Then apply input voltage and repeat same procedure. I hope you will find any solution
@mailsonfreitas396711 ай бұрын
olá amigo!! tenho surt6000kva xli ta com falha DC BUS OVERVOLTAGE eu identifiquei que o problema tá na placa de controle. a tensão no diodo 716 tem 200 volts no diodo no 715 tem 67volts. você pode me ajudar.
@AKElectroTech11 ай бұрын
Dear friend How do you identify control board? Connect batteries and apply input voltage. Now check D716 and D715 for +ve and -ve bus.
@mailsonfreitas396711 ай бұрын
já verifiquei mas as tensão estão baixo@@AKElectroTech
@mailsonfreitas396711 ай бұрын
já coloquei a placa de contro em outro surt6kva deu a mesma falha
@AKElectroTech11 ай бұрын
@@mailsonfreitas3967 Install Ok control board to this faulty ups and check status
@mailsonfreitas396711 ай бұрын
ele funcionou ... perfeitamente.. @@AKElectroTech
@G-Ser-u6g2 ай бұрын
king
@AKElectroTech2 ай бұрын
Thanks
@emsa_co Жыл бұрын
hi bro, where is connection of cathode of diode 24(D24) that is below 74htc245(ic 19)? this diode of control board was burnt but cathode of that has no connection with everywhere?
@AKElectroTech Жыл бұрын
Brother D23 is used after input transformer on PSDR board and convert AC sensing in to DC voltage and connect it to D24. D24 received 24VDC from D23 and 24V_SW from LV power supply from PSDR board. D24 cathode connected with R182 parrallel with R250. Both R182 and R250 are 100 Ohm.
@emsa_co Жыл бұрын
@@AKElectroTech thanks alot. You helped me well.
@sajidalam85652 ай бұрын
inverter fault plz control card
@AKElectroTech2 ай бұрын
@@sajidalam8565 ???
@smartups1 Жыл бұрын
Sir 2 kva online apc ups kay pfc feedback control pay video banyea .
@AKElectroTech Жыл бұрын
Oķ
@PakGuides Жыл бұрын
Dear Sir, Can you make a video on Error: 01010.
@AKElectroTech Жыл бұрын
Yes This is charger fault. I will create video on it
@awaisahmad151611 ай бұрын
APC SMT ka kuch dair baad AVR relay weld aa jata hay, AVR proper function kar raha hota hay. Supply card na laga ho to yeh issue aata hay
@AKElectroTech11 ай бұрын
AVR relay or relay driver circuit mat be faulty.
@awaisahmad1516 Жыл бұрын
Is unit Ka software kase kartay hain
@AKElectroTech Жыл бұрын
اس پہ بھی جلد ہی ایک ویڈیو بناونگا۔ اس کی کیبل ایک طرف سے سیریل اور دوسری طرف سے RJ45 سے ہو گا۔
@awaisahmad1516 Жыл бұрын
Battery calibration Nahi Hoti.. I mean 0 ke value
@AKElectroTech Жыл бұрын
بیٹری کی تاریخ تبدیل کردیں۔ مسئلہ حل ہوجائے گا
@dimanaaja1910 Жыл бұрын
sir how to repair apc error p13
@AKElectroTech Жыл бұрын
Please go to event log for detail and check the fault code. Clear its alarms. Go to configuration and reset factory default
@dimanaaja1910 Жыл бұрын
Inverter hardware ckt
@AKElectroTech Жыл бұрын
Check inverter portion
@fayyazahmad5813 Жыл бұрын
سر مجھے اس UPS کے PFC کو ریپیئر کرنے میں پرابلم ہو رہی ہے میں نے پہلے دو دفعہ اپ کو کمنٹ کیے جس میں میں نے اپنا فون نمبر دیا تھا لیکن وہ دونوں دفعہ کمنٹ ڈیلیٹ ہو گئے سر مجھے آپ کی مدد چاہیے
@AKElectroTech Жыл бұрын
اچھا میں جلد ہی PFC اور Inverter پہ تفصیل سے ویڈیو بنا کے اپ لوڈ کرونگا۔
@fayyazahmad5813 Жыл бұрын
سر پی ایف سی کے ٹرانسسٹر لگانے کے بعد جب یوپی ایس کو آن کرتا ہوں تو جب پی ایف سی کام کرنا شروع کرتا ہے تو نہت زیادہ کرنٹ لیتا ہے
@AKElectroTech Жыл бұрын
دو چیزیں ہیں۔ ایک کنٹرول کارڈ اور دوسرا پی ایس ڈی آر PSDR بورڈ۔ پہلے یہ تعین کرلیں کہ کنٹرول کارڈ ٹھیک ہے یا PSDR بورڈ ۔
@AKElectroTech Жыл бұрын
پلیز C807 کپیسٹر پہ 24 وولٹ دیں۔ اس کے بعد inverter and PFC کے Opto driver چیک کرلیں۔ وہاں پہ 17 وولٹ آرہے ہونگے۔ آپ ان Optos کو 2 وولٹ دے کر چیک کرلیں۔
@fayyazahmad5813 Жыл бұрын
سر آپ کے بتائے ہوئے طریقے کے مطابق میں نے اپٹو کپلر چیک کیے ہیں سارے ٹھیک کام کر رہے ہیں