Do u not think that the test date sticker should still be on boards??
@Dailymailnewz2 жыл бұрын
I started a new job a few days ago, guess what I found? I thought the previouse jobs were funny because of what I found as contractor. Three live wires in a ceiling rose but no neutal at all ha ha. Then the good man who is supposed to be electrical man on that site tried to install an led emergency light in the bath in the same room, but had connected all the black wires to the neutral including the emergency feed wire that feed the batteries ha ha ha. And on the two live wires that were permanent in the ceiling apart from the main live wire, it had two blue tages or sleeving on it and the same was with the other one in the bath. Nothing worked so he called me, ha ha ha ha. I mean I can go on and on and tell you so many funny things it makes MR BEAN FILM IN THE REAL WORLD. In the same work place did a visual inspectoin on emergency lights, all the batteries are dead on- around 400 lights are like that, filled the paper work- and guess the lady incharge said? How do you know it failed emergency test or not you have to do 3 hourse emergency test, told her you do not do three hourse emergency test on dead batteries ha ha ha. THAT MEANS for the last two years or so people were simplying filling the monthly emergency test as passed until all the batteries went dead. 400 Batteries dead in the emergency lights imagine that.... I got another 3 building to do.... Good luck to me...
@kindwarf10 ай бұрын
You do know that those who write the various editions of electrical regulations have never turned a screwdriver in their lives, they just make electrical installations more expensive, in the name of safety. But they have never worked on 1890 houses that was last rewired in the sixties.
@Firecul2 жыл бұрын
On the bright side, the board was in a great place to work on. Reasonable level, bright location, no walls within 1mm of both sides. Basically a dream compared to some.
@cultusgti2 жыл бұрын
A couple of hours and it's all just another job done
@rpvitiello Жыл бұрын
What’s amazing to me is you called that a dream location, and that would not meet minimum code in North America for accessibility!
@PhilThurston64 Жыл бұрын
But everything just went rapidly downhill from there. That loft was insane!
@iamdave84 Жыл бұрын
At least lots of the things were labelled@@PhilThurston64 ! That's gotta help
@jarthurs2 жыл бұрын
Having done a fair bit of amateur wiring, I have to say the worst wiring I've seen was the stuff left over from the 80's council contractors that upgraded our 1950's house from aluminium to copper. I have to leave the building when electricians visit because there's only so much tutting I can tutting and sucking of air through teeth I can tolerate. I think it's fair to say there isn't a lot of wiring in our house that is to regulation, although to be fair the regulations change on a weekly basis anyway.
@danmckenzie6234 Жыл бұрын
Not sure if anyone has said it already but that bus bar that you use on the lower side of the breakers can be modified by breaking of the teeth that line up with the neutral pole. Then use the normal cable entry in the neutral to run a neutral wire to the neutral bus for that RCD. Make sure you insert the bus bar so the teeth are at the back and the angle comes forward to the front of the breaker
@callumBee2 жыл бұрын
This is what happens when your house crashes into ScrewFix 🤣
@havoctrousers2 жыл бұрын
No way, they sell flex at Screwfix and this guy badly needed some!
@PatonCavaney2 жыл бұрын
Love the jokes but appreciate Screwfix a lot. Sometimes they're the only place to have the stock, if not, the cheapest.
@megatronskneecap2 жыл бұрын
@@PatonCavaney I've used homebase a few times and their patress boxes are the cheapest bits of s*** to exist in the electrical accessory world.
@johncorbett1130 Жыл бұрын
Always makes me cringe reading the diyers reviewing the electrical products on Screwfix and using the product review section to "show off" by saying how they did this or that 🔥
@skfalpink1232 жыл бұрын
You should never swat a wasp. An injured (or squashed) wasp releases a powerful pheromone that has the effect of attracting other wasps (from the same hive), which will then instinctively attack any non-wasp that has the hive pheromone on them. And I learned that from Vic Reeves and Bob Mortimer.
@lindsaymcdade3102 жыл бұрын
I get all my health and safety information from Reeves and Mortimer....lol
@shaunnewell197111 ай бұрын
Been there done that. Its true and it hurts when you get stung 😢
@audigex2 жыл бұрын
I think this probably leads to a good idea for a "Here's how to do DIY right" playlist... tell us how not to do things, how to do things properly, and point out where you *definitely* need an electrician, and where you *probably* want one, and where you can do things for yourself if you're comfortable enough to do so
@dankdavies2 жыл бұрын
pretty simple really. leave Electrical work too a proffesional who has been too college and served the time needed too become qualified. far easier.
@ww-pw6di Жыл бұрын
Ironically, almost all of the "hobbyist" wiring is done by electricians.
@spinner4148 Жыл бұрын
@@dankdavies good luck booking one in and getting them to actually do the job that you want. Main reason people DIY isn't to save money, it's because actually getting a tradesman in, hard enough, isn't even the end of it. You've then got to convey the job to them and hope you don't end up with something else completely.
@dankdavies Жыл бұрын
@@spinner4148 you're living on another planet mate, what you need to do is use a reputable tradesman. Not once have I had a customer ask me to carry out a job to then supply them with something they didn't require and then go further to not rectify the mishap. What kinda madness are you spouting?
@HrHaakon Жыл бұрын
I mean, I managed to fuck up installing a ceiling lamp, so... remember your audience! :D
@alliefdxproductionservices58562 жыл бұрын
Perfect use of AFDDs. Installation with known sketchy wiring, not all of which can be remedied immediately - massively reduces fire risk!
@blower1 Жыл бұрын
Apart from the fact AFDDs don't actually work and do nothing for any loose connections anywhere in a domestic installation.
@TheWebstaff2 жыл бұрын
19.40 Cory calmly testing his work while it looks like something is on fire behind him.
@TheStevenWhiting2 жыл бұрын
19:40
@thefakemaker2 жыл бұрын
I’m hoping there is a tumble dryer running and venting outside.
@computeraddic6752 жыл бұрын
@@thefakemaker No!Problably roasting a neighbor..
@Lucky-gf3vq2 жыл бұрын
Could of done with the afdds on the sub main by looks of it 😂
@steve112112 жыл бұрын
I love Hager but they need to come out with a single module rcbo/afdd breaker, I think your solution is the best solution, I think I might have put it on a 40A RCBO but still all protected.. They have had a while to come out with one and with other manufacturers coming out with them its unusual for Hager to be behind the game..
@DTech1012 жыл бұрын
Hager do have a single module RCBO not sure at AFDD’s though but at 100 a pop I can’t see much people spec’ing it, their SPD is a two module device which is pretty much the same as all the others as it doesn’t need and MCB connected to it.
@steve112112 жыл бұрын
@@DTech101 New Regs mean properties that are deemed high risk will have to have socket outlets covered by AFDD's but agree that its unlikely that anyone will choose until the price point comes down, but it was not that long ago you could have said the same about RCBO's... AFDD's need something like 2A in which to trip so with led lighting its unlikely they will ever be required for lighting as that would be pointless.. But sockets and shower and cooker will probably be mandatory in the next edition of the regs as long as prices come down a bit.. Hopefully Hager will have caught up by then and got a single module AFDD
@rpvitiello Жыл бұрын
It’s very interesting how different this is done than North America. Here each circuit has its own combination GFCI/AFCI (RCD/AFDD) breaker. The bus bars are built into the breaker box (consumer unit). Things are also broken down into many many more individual lower amp circuits. That whole mess in the attic (loft) would all come to the consumer unit as individual circuits.
@TwoDogsFighting Жыл бұрын
Looks a lot better than what bellway left me with.
@adamosity7127 Жыл бұрын
Texas USA here. Always a jolly seeing how things are done across the pond.
@SabretoothBarnacle2 жыл бұрын
Faded print on those thermal printers are usually a sign of weak batteries
@Firecul2 жыл бұрын
By default these use a rechargeable battery so it should be obvious if it's low, and really easy to test, if he has the charger handy it can print while plugged in.
@henrytwigger2245 Жыл бұрын
What is important is that people are trying to do things for themselves and are learning. :)
@amarkhaliq2 жыл бұрын
17:19 - Jordan saving this clip if Cory asks for a pay rise 😂
@martinhansen68022 жыл бұрын
Wasp queens will nest up and hibernate during winter. Especially in houses with the old insulation batts. They wake up once temperatures get up and around 10 degrees
@karoln70782 жыл бұрын
0:56 not supposed to stand on that 🤣🤣
@andyclark14262 жыл бұрын
Definitely a kitchen fitter/wood layer who “knows lectric” and has been trying to pass his short course log book
@chrisholt24742 жыл бұрын
It’s always a great film with Cory.
@angryscottishidiot2 жыл бұрын
"I don't see how this is worth filming" was my favourite bit.
@mick32162 жыл бұрын
None of it is worth filming
@gorillaau Жыл бұрын
Always film it, but decide to edit it out. Can't edit to include something when you never filmed it.
@entertainmentbydjt2 жыл бұрын
Arctic flex doesn’t have to be 110v, the colour is just the colour. It’s often used with 110v 16A yes, but it’s just yellow Arctic flex
@jamesdyas5422 жыл бұрын
Think it comes from c form sockets where yellow is 110 volt, blue is 230 and red 400. Some extension leads were coloured accordingly.
@entertainmentbydjt2 жыл бұрын
@@jamesdyas542 exactly, however the cable itself is just cable, and will have its own voltage rating written on it. Arctic flex I’ve seen is usually rated 300/500V, no matter the colour
@James-dv1df2 жыл бұрын
@@entertainmentbydjt Just out of interest is using yellow for 240v illegal/doesnt meet the regs or just best practice? Or is the wrong to not use yellow for 110v on a site?
@entertainmentbydjt2 жыл бұрын
@@James-dv1df I’ve seen 110v leads with black rubber cable used, matching the colour of ceeform connector to the colour of cable is convention, and to the best of my knowledge is not regulation. They are just PVC cables, with their own respective voltage ratings, most Arctic flex I’ve seen is 300/500v and can be used for any appropriate task. If you had a household 13a extension lead with yellow cable, you likely wouldn’t question it. On a building site if a 110v lead was made from blue cable, it may be confusing, so likely easiest to match the colours. Though ceeform connectors can only be plugged into the correctly rated sockets due to the keying.
@James-dv1df2 жыл бұрын
@@entertainmentbydjt Brilliant thanks,
@Razuliann Жыл бұрын
I'm from Belgium and I can tell you that our country is quite behind on safety. First time I saw an AFDD, never heard of it before and Belgium's codebook doesn't mention it as far as I can tell (a quick search doesn't show anything at least). Pretty much two RCCB's are needed: 300mA before all breakers and an extra 30mA for "wet" rooms (e.g. bathroom) Not much else for safety. Now imagine bringing a very old house with crumbly wiring up to code, you don't have to redo the wiring to add earth. Mainly document the wires and where everything is located
@klarnorbert Жыл бұрын
Interesting. IEC mentions AFDDs, even in my country - Hungary - we use it, even tho it's not required to install one.
@Cablesmith2 жыл бұрын
Correct about the single module AFDD/RCBO’s. But not many at all have made one yet. Think at the moment only 3 brands are actually on the market. Fusebox, wylex(for well over a year already) and lewden
@xeno0872 жыл бұрын
Don't forget Contactum
@Cablesmith2 жыл бұрын
@@xeno087 ah didn’t know they were out
@herensugue2 жыл бұрын
More like a career switch from pyro to DIY. That looks more like shape charges at 4:45 and that yellow wire outside must be leading to a detonator somewhere.
@ThatJay283 Жыл бұрын
nice vid! i really like seeing tradies clean up after working too, i like how you added that. not all tradies do it, and when a sparkie did stuff where i live there was bits of plasterboard and bits of stripped wires when they left. i create these bits of stripped wires too, but they're MUCH smaller lol i'm into more low voltage stuff.
@user-od8ki6tt1j2 жыл бұрын
Is that a retro Casio calculator type watch? Brings back some memories
@frimleyfrodo2 жыл бұрын
Why would you use drums of arctic flex, weatherproof sockets and trailing sockets on a fixed loft installation? Got to be dearer on parts than doing it properly.
@AndrewStrydomBRP2 жыл бұрын
Could've had it laying around already, using what you have is always cheaper than buying new.
@tobysherring13692 жыл бұрын
Did you grommet strip the CU back entries? Why not put tails in the trunking? Aren't there only 2 cables in there?
@heepsy7672 жыл бұрын
It doesn’t need grommet strip on the back either as the entry holes the cables are coming through in the wall are preventing the cable from snagging on thr edge of the board…clearly not that hard to see 🤣
@tobysherring13692 жыл бұрын
@@heepsy767 do you mean "clearly hard to see" or "not hard to see"? Either way, I didn't see any protection.
@marc92222 жыл бұрын
Is the looping cable for the AFDD underrated. Technically you are using one phase and neutral cable to supply to both AFDD?
@r03112 жыл бұрын
Btw. If not already noticed, there are special bus bars with neutral and live wire to connect these breakers.
@JSunday452 жыл бұрын
Couldn't see well, but those RCDs should feed separate rolls of breaker right? If they're all on one bus bar then both RCDs have to be tripped? Power comes from two poles main switch then feeds L and N to the RCDs and after that, you treat every RCD as it's own circuit right? All just theory for me still. That's why I'm so curious!
@lrdisco2005 Жыл бұрын
It's never another spark that created the mess, always mr diy. Let's face it you never get an electrician making up figures instead of actually testing.
@charg1nmalaz0r51Ай бұрын
You say that but theres literally video evidence on youtube of sparks doing questionable things all over the place
@sagster2 жыл бұрын
I have seen such in an installation done in commercial building! Sockets, plugs and even 4way extensions used everywhere in the loft area LOL
@tobysherring13692 жыл бұрын
Could be perfectly OK if done properly. 4 way extensions are often made to BS 1363. Extension leads are not automatically wrong. Load considerations, fuse rating, cable type, length and location are important factors.
@iamdave84 Жыл бұрын
@@tobysherring1369 in Australia (240V) all 4 way power boards MUST contain a 10A circuit breaker and be rated for 10A. Likewise all mains extension cables must be rated for minimum 10A. I've heard in the US you can get extension cables that can't handle much current, and nothing stops people using them for full 15A loads, leading to melting, fire risk, etc.
@tobysherring1369 Жыл бұрын
@@iamdave84 I lived in Aus for ten years and that was a good feature. I didn't like the thin plug pins or 40A-fused radials much. Simpler than fused plugs but less localised protection. Here in UK it's common to see people making extensions with thin flex and not downgrading the fuse in the plug. In a commercial setting you'd hope the PAT would pick it up.
@iamdave84 Жыл бұрын
@@tobysherring1369 yeah, I agree, our plugs suck. UK ones are far superior for a stack of reasons. Foot damage is their only downfall, but worth it for the benefits!
@casperbang4882 жыл бұрын
My experience is that the customer doesn't think anything's wrong, because it's been working for 10 years, and it's an electrician who's done the job, right? That's what they always tell me 🤣
@Jay3692 жыл бұрын
Had a client before who was trying to say I was just trying to get more work from his rental as he also believed it was perfectly fine as an "electrician" had done the rewire. I'd usually be professional and just show them the photos and report but instead left him with this: "But Doctor, I can't possibly have an STD. I've never worn condoms and have always been fine".
@TheWtfnonamez Жыл бұрын
I am a very handy bodger and I can fix most things myself. But I never mess with electrical or plumbing. They are two things that can destroy your house and destroy you.
@cultusgti2 жыл бұрын
Probably be for the best to wear some PPE when entering an attic with that much glass partials floating around
@tobysherring13692 жыл бұрын
"Arctic flex is for 110v". You do come out with some BS! I agree it's not suitable for the application, but that's not why! And junction boxes are well within regs as long as they're wired properly, accessible, correct rating, no exposed single insulated cable, etc. You seem to think all JBs are automatically a 'fail'. Much bigger problems to deal with here.
@James-dv1df2 жыл бұрын
I'm no electrician and don't do DIY electrics other than very basics like changing light fittings however watching some of these videos to learn more and if I want to change occupation. I feel like some electricians are too critical on small issues which reduces the impact when there is a real issue. Still learning but surely you can have as many junction boxes as you like as long as you can access them and they are rated for the load in use and also not using them in the wrong circuit e.g. used to spur off to multiple circuits on 2.5 or something? Surely you cant be too critical for something that meets regulations but is just not best pratice?
@tobysherring13692 жыл бұрын
@@James-dv1df junction boxes are a specified way to join cable, spur, extend circuits, wire light switches etc in the regs! They have to be properly used, the right one for the situation, etc. However you do it, multiple spurs off one unfused spur from a ring final is wrong - junction boxes are not the only way to do it wrong! Yes, he does pick up on minor issues that may be fine, but the more 'faults', the more they can quote to put it right. Other sparks would quote to do a bank of sockets in the attic - clearly marked 'lighting only' and on a 5a fused spur, and have that mess sorted in a couple of hours. The unqualified guy up there is left to do work which is connected to power without inspection. Corey has incorrectly identified the garden flex as 110v, put main tails by heating pipes, said EICR is only for 'fixed wiring', not used grommet strip on CU, and condemned JBs without any testing or evidence of fault. All wrong. Not Artisan at all - just average but very expensive. You don't always get what you pay for! One of the others caused structural damage to a house because no site visit or plan was completed, and he didn't know what a timber frame is!
@granvillebloor65692 жыл бұрын
Evan I whouldant have done that flex is for temporary power not to be used in install in house
@chrisardern45942 жыл бұрын
I think his boggle about joint boxes are 1 the more their are the more chance of a dodgy connection 2 someone willing to use these items excessively are more likely to be a diyer or a kitchen fitter than a Electrician 3 it can take days to find locate hidden JBs. Just my opinion folks.
@tobysherring13692 жыл бұрын
@@chrisardern4594 true - but they're not hidden, and who says what's excessive? Like anything, it needs to be visually inspected and tested. Circuits without any JBs can be full of poor connections inside sockets, switches, CUs etc.
@elusive627 ай бұрын
I know its a 2 year old video, but please be careful even with the plugs, i watched a video from another youtuber who was fixing a boiler connection, long story short, the plug he unplugged was WIRED LIVE! from another connection. Always check dodgy DIY stuff.
@smoll.miniatures2 жыл бұрын
I fitted an outside socket today using a fused spur. I turned off the rcb labelled “living room main” and began and my work. When installing the new wiring I contacted the new cables with the old and it caused the main switch to turn off. Why would this be? Found it kinda weird considering I had turned the rcb off.
@kal90012 жыл бұрын
Most breakers only switch the live off. The earth wire should always be 0 volts, with very little deviation. But neutral, depending on how long the wire run is, and what other appliances you have, can have stray voltages on it, when you put a meter on it, you may see 4, 5, even 10VAC and not think much of it. But that can easily push 25ma through earth and trip the RCD if they touch. So most likely, when wiring stuff up, you had let neutral and earth touch, and in that moment +25mA was seen by the RCD and pop. I had the same issues fitting some lights in a garage, that was a long fused spur off a kitchen ring. It ran through an isolator switch which was turned off, but of course it only switched the live. Due to high load in the kitchen at the time there was some a few volts on the neutral when I got the meter on it.
@glennlockey10122 жыл бұрын
Yep, kal has got it covered but be careful of 'borrowed' neutrals or even lives sitting on ring older ring main circuits, you turn off the rcd but the circuit is tapped into another circuit keeping it live. Switch off and check for voltage... stay safe
@kal90012 жыл бұрын
@@glennlockey1012 Indeed, In this case, and likely OP's case it's not inherently an issue. But it does expose one glaring problem for those who are paying attention. If you were holding a neural conductor on your ring main, it's near 0VAC so safe right... sure. But what if the neural back at the fuse box becomes disconnected somehow. there is no longer a path pulling neutral to 0VAC, and the neutral will rise to 120/240 (wherever you live) The same can happen if you have a very heavy load somewhere, particularly if the neutral has a bad higher resistance connection. Your heavy load will be filling up the neutral quicker than it can empty through your distribution board, so you get voltage on the neutral, potentially dangerous. If someone screwed up and were to put a breaker on neutral instead of live... oh boy...
@gorillaau Жыл бұрын
19:22 Where is that smoke coming from? :-)
@Aalountulai Жыл бұрын
The smoke at 19:21 made me shit myself 😂
@TheStevenWhiting2 жыл бұрын
12:17 Copper plated some older ones are bronze.
@tobysherring13692 жыл бұрын
EICR is not just 'fixed wiring': it's for a whole 'installation' and that attic stuff is definitely installed. You're getting confused with commercial Fixed Wire Testing.
@jacobguile7782 жыл бұрын
The cert they do for the board change will be a Domestic EIC, not an EICR
@farmersteve1292 жыл бұрын
Correct, putting a 13A plug top on it doesn't make it non-fixed wiring - technically a 4 way extension block screwed to the wall can be considered "fixed" wiring & should be taken into account. Likewise, simply unplugging doesn't make it safe as it can be plugged back in & giving the customer a written warning acknowledges that you are aware of the fault.Removing the plug top from the cable is a safer option because the customer or a third party would can't simply plug it back in and would have to take extra actions to reconnect. Yet another case of Artisan going in to a job blind & half cocked, then scrabbling around to get a result - it's a shame because they are able to do quality jobs.
@tobysherring13692 жыл бұрын
@@jacobguile778 he was talking about doing an EICR. if it's just a board change he would issue a EIC but then he wouldn't bother unplugging all the mess. The 'fixed wiring' language is just wrong for domestic. He's either checking the whole installation or he's not - you can't ignore the bits with plugs on the end.
@tobysherring13692 жыл бұрын
@toddbod94 obvs not. But that stuff in the attic is an installation, with several installed lights connected to installed wiring. It's obviously not acceptable on visual inspection and at least a written warning should be given - just unplugging it doesn't advise the customer it's potentially unsafe. If you saw a washing machine with singles into the plug you'd do the same. Extension leads are included in EICR.
@JasperJanssen2 жыл бұрын
@@tobysherring1369 …. What part of this video makes you think no written warning will be given to the customer?
@MartynSmith2 жыл бұрын
What is going on outside the window at 19:31 - is someone summoning Jordon?
@woodsmic2 жыл бұрын
So what did all that stuff in the loft do?
@nmccw32452 жыл бұрын
Home automation: Alexa, please burn the house down…
@smorty12612 жыл бұрын
Can never seem to justify spending all that money on Hager. They always seem to behind the times and their solutions for DP RCBOs, AFDDs and SPDs are clunky and seem like a massive afterthought.
@Dranok12 жыл бұрын
...and the price! I had to change RCBOs in two DBs from Type AC because they were feeding all the socket cct's in a bunch of "mission-critical" offices that were overladen with switch-mode PSUs dumping enough earth leakage to make half of them fail basic RCD test. The Eaton board cost us £48 per RCBO, the Hager (the bigger board of course) cost £159 per unit.
@03simm2 жыл бұрын
I’m not an electrician at all, I watch these videos because I find them interesting. Could someone please explain why they have everything plugged in their loft including the fridge what could be the reason for this. Thanks
@rfitzgerald20042 жыл бұрын
I'm not an electrician just an observer. Part of the reason is that they've added home automation devices (I could see "LightwaveRF" as one of them in the video) and adding them onto plug sockets avoids the need for the work to be compliant to electrical regulations as it's then not classed as fixed wiring. It also allows them to easily remove it and revert to the previous fixed wiring if they leave the house just by switching the plugs around etc (common on rented houses I would assume). It's a shame that they did so much wrong here, as much of the stuff appears well mounted and labelled, they've just made questionable choices with the type of cable chosen, containment, and some of the connections (lack of earths for example). As the guy said in the video, it appears they've got some sort of electrical experience, but aren't an electrician
@oicfas4523 Жыл бұрын
3:13 Are those the customer's Pringle? 😂
@JackBowley952 жыл бұрын
Is today's sponsor someone who produces junction boxes?!
@artisanelectrics2 жыл бұрын
Should have been! 😂
@makg46552 жыл бұрын
@@artisanelectrics do u think test date sticker should still be put on boards??
@TONE111112 жыл бұрын
never enter a junction box unless your exit is clear ⚡
@andrewpowellnz2 жыл бұрын
@@TONE11111 🤣
@davideyres9552 жыл бұрын
Love the retro calculator watch. Does the Bosch screwdriver have the correct insulation resistance, I know some of the sparky tools are certified up to 1kV so how does that fit with the Bosch? Not criticising just interested as I have the old version of that screwdriver that has metal parts on it so I don’t use it for anything that may be live, the old one is a lot more chunky and has a torque gearbox that locks up when you are manually turning it.
@slinkdroonk41752 жыл бұрын
IMHO removing accessory plate screws doesn’t need the 1kv rating. Just as long as the bit and the handle aren’t continuous (in the electrical sense)
@dixonm92 жыл бұрын
Safe Isolation is law. 🤙Unless your job justifies live working, insulated drivers are a marketing gimmick
@DanBurgaud2 жыл бұрын
8:24 instead of using sub panels, this house uses sockets? nice nice nice...
@creativejamieplays71852 жыл бұрын
Is the cable entry in the back of the board got Edge strip on? Looks like it doesn't even after terminations have been made.
@QPRRhino2 жыл бұрын
Great Attitude to life and work. Stay positive !
@g.t.362 жыл бұрын
Do you have a link for that battery screwdriver. Pls
@rayc15032 жыл бұрын
Google Bosch Go 2 screwdriver. 👍🏼
@artisanelectrics2 жыл бұрын
Link in the description 👍🏻
@g.t.362 жыл бұрын
@@artisanelectrics thanks
@chrissilva56592 жыл бұрын
You don’t have a regular impact that is in the shape of a drill?you guys do things so differently then we do in the states
@snazy77772 жыл бұрын
Are AFDDs now mandatory on new installs?
@AndrewStrydomBRP2 жыл бұрын
Only on some installs, like HMOs and student accom.
@ronaldomac49182 жыл бұрын
Papa Pringle never let's me down........... hahahaha love it mate :)
@chriscollins17042 жыл бұрын
The unmistakable sound of screw cam-out
@test-rj2vl Жыл бұрын
Would have been interesting if you pointed out reason why you cant put your signature to something. For example what's exactly wrong with stuff in attic or at 7:00. I mean if you already put 20 min video on youtube you can should expect that non electricians watch this and want to know.
@Umski2 жыл бұрын
They had the courtesy to label all the dubious wiring at least ;)
@jagdeepchatha28852 жыл бұрын
Can anyone tell me what the name of the wireless socket tester?
@crcameron12 жыл бұрын
I know that feeling, when the day doesn't go as planned and you wish you stayed in bed. Also that mess wasn't so bad, I have seen far worse. Great video. Cheers from Canada
@jibcot85412 жыл бұрын
I have never thought of drilling 1p coins when I have run out of washers, I will have to remeber that one, or just remember to order washers!
@Centrelink_Bogan2 жыл бұрын
are you required to install AFDD's over there? we only need RCD (aus)
@iamdave84 Жыл бұрын
What does an AFDD do that an RCBO doesn't?
@Morris121r2 жыл бұрын
Could you tell me what company you get those pant from.
@cliveroulstone93662 жыл бұрын
Hi i know your , channel isn’t a Q&a but ive just acquired a 110v wet and dry vacuum cleaner can i use it in the house ?? Ps love your channel
@mintsauce5632 жыл бұрын
Just advise a full rewire pointless tinkering with that shit 🤣
@Milo199702 жыл бұрын
I hate the strict regulations sometimes in my country but at the same time I'm happy they are there to make houses idiot proof before being bought😂 That house right there would lose its insurance with that electric work in my country.
@lorconhildred622 жыл бұрын
Odd question - what trousers are you guys wearing?
@buixote2 жыл бұрын
Intruction Manual?! Next thing you know, we'll be watching you stop to ask for directions! You might want to try a vacuum on the wasps... dunno if they can come back out, though! ;-)
@artisanelectrics2 жыл бұрын
It's a slippery slope!
@robbmerrett55612 жыл бұрын
Good vid 🙌🏻🙌🏻🙌🏻👏🏻
@artisanelectrics2 жыл бұрын
Thanks Rob!
@theodorgiosan2570 Жыл бұрын
This doesn't look that different from typical US wiring. Aside from the grounds cut out all over the place it looks like what we have here. Individual circuits running all the way back to the panel, junction boxes all over the place, cables stapled every foot or so. Seen houses where every single outlet in the kitchen has its own run of cable 100 feet or more back to the panel. Also seen others where there are subpanels upon subpanels in different sections of the house so they only had to run one thick cable instead of a bunch of small ones. Pretty common to see a big array of random electrical devices and smaller subpanels expanding out from the main panel in older houses. AFCIs (AFDDs) are required here in some states but it's not clear that they do much. I have drawn an arc between hot and neutral and seen the AFCI do absolutely nothing. Some states have gotten rid of the requirement because they cost $80 a piece or so and most new construction houses have a 42 circuit panel or larger, sometimes even 84 circuit, and there hasn't been any clear benefit to the AFCIs.
@tommymack32102 жыл бұрын
Nice to see you finally got a electric screwdriver Cory
@RabM19902 жыл бұрын
15.30 - what bag is that on the table?? Been hunting for one of them for my Megger.
@HugoDenbyMann2 жыл бұрын
Look like camera bag - look up the likes of Lowepro
@RabM19902 жыл бұрын
@@HugoDenbyMann cheers! Exactly what I was after! Seen all the chrap amazon ones but was wary of them
The electrics may be iffy, but the roof structure is superbly solid, it’s the same as mine, built 1969 by Wimpy non of that bent metal jointing plates, just big nuts and bolts.
@grayhalf18542 жыл бұрын
Wot, the burger people??? 🙃
@2001035112 жыл бұрын
Loved the "leave it safe" comment..... safety #1 no matter what
@joshwalker94462 жыл бұрын
Lol the drilled out penny’s done me 😂😭
@stevejagger86022 жыл бұрын
This job doesn’t feel like it was properly planned - too many unexpected DIY disasters, and a prescribed DB from the client.
@elfynjones2117 Жыл бұрын
If client suggested he was supplying the DB i would just walk away. not worth the hassle and this job is a classic diy nightmare.
@stevethomas58492 жыл бұрын
Penny washer fashioned out of a 2p was either made of Bronze from 1971 to 1992 then from 1992 to present copper plated steel. Of course the old Penny was the size of the 2p today.
@buttyboy1002 жыл бұрын
1982 was the cut off date for all alloy 1 and 2p coins. From then on steel blanks were used. This was during the tenure of a certain iron lady, funny that. Archeoligists and metal detectorists of future centuries will not have much luck with these coins. They rot very quickly in the ground.
@ForTheBirbs2 жыл бұрын
Wow, there's a crap ton of special wiring in that place! Thanks for another great video. Cory spoiling his image being shown eating celery! lol
@artisanelectrics2 жыл бұрын
Glad you enjoyed it Jim! To be fair he did balance out the celery with a tonne of Pringles...
@gadam2btk Жыл бұрын
If the outside lights are on a socket then they’re classed as an appliance that’s probably why it was done like that
@Midori9002 жыл бұрын
you could have used a hager kdn263 for the afdd
@ashreid202 жыл бұрын
12:47 feels like a heart surgon?
@explosivegardenreboot Жыл бұрын
omg , im a electrical tested to destruction madhead, done few diy bits but nout on the DB. this place is absolutely shocking. id be afraid to live there
@PaulJones-lf4zq Жыл бұрын
Less than 3mins in and I’d walk away as soon as the customer says ‘I’ll supply the board’ also as you said your not sure how it’s loaded-trust what you know. Sorry gents couldn’t finish the rest of the video.
@davida1841 Жыл бұрын
Lot of comments about just unplugging the attic extras. An EICR doesn’t include plugged in items. Yours might. Mine doesn’t. Saying it should doesn’t make it so. Quote me a reg definition? It’s what PA testing is for. Clearly the offending items would all fail a Pat check 😮 So given he’s been commissioned to do an EICR. He’s unplugged what he doesn’t like and informed the customer. Good for him 😊 However, if he starts cutting plugs off things that he is not entitled to be examining he is liable for their destruction. It’s not even that bad at first glance. Seemingly class 2 equipment all nicely clipped to provide strain relief… just some poor choices. Not really a rampant fire risk. Ooh the drama!😅
@vinnyvtec87222 жыл бұрын
I find these videos really interesting, but I'm not an electrician and if I'm honest, I spend most of these types of videos asking myself what's he talking about lol.
@kevino23562 жыл бұрын
Why not use 2 pole busbar on the bottom of the AFDD’s, Far handier
@chrissilva56592 жыл бұрын
Is that panel made of Plastic ?
@DrRusty52 жыл бұрын
Bit will the arc-fault devices find faults??
@PhilThurston64 Жыл бұрын
Multi line busbars: LNLNLN are really common on the continent. Never seen them in the UK.
@jooproos6559 Жыл бұрын
Are those thin cables really the norm????
@therealdojj2 жыл бұрын
That looks exactly like my house, there's only two plugs on the distraught ring, the 3 are from the upstairs But wait, it gets better, there are only two plugs in the upstairs ring, the other 7, not including the 3 from downstairs, are spured of that ring 🤦
@artisanelectrics2 жыл бұрын
Wow 🥴
@therealdojj2 жыл бұрын
@@artisanelectrics the same guy put 3 nails through the wires too Not to mention the junction box, from one line, that wasn't to a socket, and then the cable from that socket, wasn't back into the same junction box again One plug was wired using 4mm rubber cable And there's great and white cables everywhere And the downstairs lights are on a ring, not a radial Oh, and the additional wall lights are powered from the mains, but the switch is also connected to the lighting curcuit So to kill the lights you have to turn off the lights AND the sockets Did I mention the plug in the front room that's spurred of the armoured that goes to the garage? No? It only powers the phone It's been an intresting few weeks figuring out what's what And it so stayed with I think one of your videos with the green gunge oozing out of a cable when I changed a security light So thanks for that 🤣
@sjowners2 жыл бұрын
😂😂😂Why do people do it??
@therealdojj2 жыл бұрын
@@sjowners even worse what we found ripping the stuff out, he'd taken a spur (off the spur he'd already run) via a junction box, which was then using some 1.5mm cable Which then went into another junction box, which then fed two additional double sockets 🤦 As we've been removing them we've tried to strip out the wires to keep the power on, but the cable won't strip as its got so hot over the years its fused itself to the inner insulation The wires are black and some were actually physically melted around the terminals of the junction boxes 😲 And earlier today we discovered that the cu has 202 amps worth of breakers in it in a 100a fuse so guess what next weeks jobs are going to entail? Yes, spending more money on fixing things that should never have needed fixing in the first place 🤦🤦🤦🤦🤦🤦🤦
@sjowners2 жыл бұрын
@@therealdojj how else was he going to run his 3kw heater all day in the garage😂😂
@swelectricals5682 жыл бұрын
You need to buy yourself a bug zapper racket, Those wasps will no longer be a problem. Surprised Pringles don't sponsor you.
@artisanelectrics2 жыл бұрын
We need to make that happen
@adamshafiq68492 жыл бұрын
i’m sure u missed the grommet strip at the rear entry
@sephstar-offical2 жыл бұрын
5:59 looks like an "earth" wire to me!
@Spark101.2 жыл бұрын
Awful installation. (Just so you know though….Yellow Arctic flex isn’t limited to 110volts). The copper cores are no different to a 3 core white flex of the same size.
@sjowners2 жыл бұрын
But yellow means 110v. Can't really sign that off knowing its there.
@alreadynuked2 жыл бұрын
I'm thinking a Pringle sponsorship is long overdue
@AlejandroTaylorEscribano2 жыл бұрын
You should go to India. Not an electrician but the stuff here is insane.
@artisanelectrics2 жыл бұрын
I can only imagine!
@sjowners2 жыл бұрын
Thailand is pretty bonkers also. Blue haze at the top of every pole😂