Kenapa Neutral sentuh Earth Tetapi RCCB Tidak TRIP

  Рет қаралды 48,080

Petrus Goel

Petrus Goel

Күн бұрын

Пікірлер: 378
@hasbibujang4919
@hasbibujang4919 9 ай бұрын
Terbaik tuan
@Riotz77
@Riotz77 Жыл бұрын
Simple mudah difahami....terima kasih kawan....harap2 kalau tak sibuk buat lagi conten2 begini.......share ilmu 🙏🏻
@XpisserzX
@XpisserzX 3 жыл бұрын
Terbaik eksperimen cikgu! Jarang nak dapat tengok pengujian ni kat luar sana. Semoga bermanfaat ilmunya. ⚡
@petrusgoel
@petrusgoel 3 жыл бұрын
Terima kasih... Semoga bermanfaat.
@georgesolomon
@georgesolomon Жыл бұрын
Salam.saya newbi lagi.pengajaran dan penerangan yang Sangat bermanfaat. Terima kasih banyak cgu.
@halismaMGT
@halismaMGT 6 ай бұрын
👍👍👍tahniah.. tuan menyampaikan ilmu yang baik kepada masyarakat pengguna
@mymal2002
@mymal2002 4 ай бұрын
Antara Content Provider Electrical yang terbaik di Malaysia. Setaraf dengan John Ward. Terima kasih Sir!
@petrusgoel
@petrusgoel 3 ай бұрын
@@mymal2002 wahhh… yakah? Saya belum pernah tengok John Ward punya channel. Anyway terima kasih singgah dan sokong channel saya 🙏🤩
@mymal2002
@mymal2002 3 ай бұрын
@@petrusgoel Dari UK. Agak popular. Sesuai untuk rujukan orang Malaysia sebab dorang pun guna IEE@IET, BS & IEC.
@petrusgoel
@petrusgoel 3 ай бұрын
@@mymal2002 owhhh ok. Nanti saya tengok 😃🤩
@adnannan7767
@adnannan7767 3 жыл бұрын
Bagus sekali utk semua yg belajar dlm bidang elktrk ini dpt mnmbah lgi pengaln t ksh
@petrusgoel
@petrusgoel 3 жыл бұрын
Ya... saya pun belajar juga dari test ini. Terima kasih.
@lawerncemantan9842
@lawerncemantan9842 3 жыл бұрын
Penerangan yg simple ttpi padat. Terbaik
@petrusgoel
@petrusgoel 3 жыл бұрын
Welcome
@jefferykai7922
@jefferykai7922 3 жыл бұрын
Tahniah petrus...bagus video ini.penuh informasi..hehehe..dari kawan sekelas.
@petrusgoel
@petrusgoel 3 жыл бұрын
halloooooo kabannn ... sudah SUBSCRIBE ka? share channel aku ngan students ILP aokk..
@muhammadafzalhakimi925
@muhammadafzalhakimi925 3 жыл бұрын
Trima kasih Tuan atas ilmunya
@ibnishak8191
@ibnishak8191 2 жыл бұрын
Terbaik cikgu..
@gotze7754
@gotze7754 3 жыл бұрын
Terbaik.....suka tgok rcd tester
@petrusgoel
@petrusgoel 3 жыл бұрын
Welcome... Ya. Digital RCD Tester adalah alat uji RCD paling bagus untuk uji RCD.
@muhammadmoaat8769
@muhammadmoaat8769 3 жыл бұрын
Terima kasih cikgu..👌👍👍
@rifanrifan3463
@rifanrifan3463 2 жыл бұрын
Terima kasih ilmunya
@fauzanmf9083
@fauzanmf9083 Жыл бұрын
Terbaik.. Terima kasih
@gffotv2975
@gffotv2975 10 ай бұрын
Jelas cikgu terima tu
@agsabtubinjuaraagsabtubinj2336
@agsabtubinjuaraagsabtubinj2336 3 жыл бұрын
Tlg dulu guru...tekaran suda sya kemarin...sya tgk ko pnya content ni buli² jgk...memang org wiring
@petrusgoel
@petrusgoel 3 жыл бұрын
Buli ba... Haha.. Harap bermanfaat ya
@agsabtubinjuaraagsabtubinj2336
@agsabtubinjuaraagsabtubinj2336 3 жыл бұрын
@@petrusgoel cigu skol ka kau ni ataupun tukang wiring rumah...mcm smat² ja baju kau dlm gambar tu,hensom boy lg tu...😀😀😀
@petrusgoel
@petrusgoel 3 жыл бұрын
@@agsabtubinjuaraagsabtubinj2336 say ajar sini politeknik kuching bah...hehe bule ba sikit sikit haha
@agsabtubinjuaraagsabtubinj2336
@agsabtubinjuaraagsabtubinj2336 3 жыл бұрын
@@petrusgoel patut la pandai....bah bagus² cigu mengajar & mendidik anak bangsa kita (walaupun bkn sama bangsa kan😉😉😉😉)....jan ko risau...saport² org² kita juga ba ini...klu ada yg br² ko post saja...sya tlg kasi 👍
@agsabtubinjuaraagsabtubinj2336
@agsabtubinjuaraagsabtubinj2336 3 жыл бұрын
Jadi lama suda la ko nda balik kg klu bertugas d sarawak ni kan...sabar jak kau..
@hanyasatu1275
@hanyasatu1275 3 жыл бұрын
terbaik bro terima kasih kongsi ilmu 👍
@petrusgoel
@petrusgoel 3 жыл бұрын
Sama sama
@muhammadzuhdibinibrahim5430
@muhammadzuhdibinibrahim5430 2 жыл бұрын
Terima kasih cikgu di atas penerangan dan demonstrasi.. Penerangan jelas dan mudah difahami.. sangat memberikan manfaat..
@petrusgoel
@petrusgoel 2 жыл бұрын
Sama sama
@SHAHRIMMOHD
@SHAHRIMMOHD 3 жыл бұрын
terima kasih video perkongsian ni...sgt bermanfaat...baru lah faham..
@petrusgoel
@petrusgoel 3 жыл бұрын
Sama sama
@AILAli-hg8bf
@AILAli-hg8bf 3 жыл бұрын
Terima kasih byk2 cikgu.terbaek sgt2.
@petrusgoel
@petrusgoel 3 жыл бұрын
sama-sama...harap membantu
@mhanafi7905
@mhanafi7905 3 жыл бұрын
Terima kasih cikgu.. senang faham penerangan.
@petrusgoel
@petrusgoel 3 жыл бұрын
Sama sama..
@awiesukiro2185
@awiesukiro2185 3 жыл бұрын
Ilmu yang sangat berguna..terbaik
@petrusgoel
@petrusgoel 3 жыл бұрын
Terima kasih... Semoga bermanfaat
@syafiqani2085
@syafiqani2085 3 жыл бұрын
T.kasih atas ilmu tuan...semoga dpermudahkan urusan tuan dan dilimpahi rahmat...
@petrusgoel
@petrusgoel 3 жыл бұрын
terima kasih. semoga bermanfaat.
@endyX286
@endyX286 3 жыл бұрын
terima kasih tuan.perkongsian yang sangat bagus.sekarang baru faham.
@petrusgoel
@petrusgoel 3 жыл бұрын
Sama sama
@Matanep
@Matanep 3 жыл бұрын
Ilmu yg bermanfaat.. Tq cikgu 👍
@petrusgoel
@petrusgoel 3 жыл бұрын
Welcome
@anuarnor3318
@anuarnor3318 3 жыл бұрын
Hari ni saya subscribe cikgu. Terima kasih ilmunya.
@petrusgoel
@petrusgoel 3 жыл бұрын
Terima kasih
@melzahra4025
@melzahra4025 3 жыл бұрын
Terima kasih... dapat sedikit ilmu...
@petrusgoel
@petrusgoel 3 жыл бұрын
Welcome
@KuchingRocketeer
@KuchingRocketeer 3 жыл бұрын
Konsep RCCB ni secara asasnya adalah berdasarkan keseimbangan arus di antara L & N. RCCB akan trip bila mana arus (return path) melalui N tidak mengalir sepenuhnya balik ke TX (IN < IL) disebabkan sebahagian arus (return) melalui ke path lain, iaitu E. So, consider it's leak condition. Situasi yang agak mudah kita faham bagaimana ia berfungsi. Untuk RCCB trip bila mana situasi berlakunya leakage di antara N & E, iainya bergantung. Sekiranya berlaku leakage/ sentuhan diantaranya, maka prinsip ketidakseimbangan tetap diambil kira untuk trip. Maksudnya, arus pada L dianggap tetap atau sebagai rujukan perbandingan dengan arus N. Maka, teorinya, bagi membolehkan RCCB trip untuk kes N-E, bergantung kepada litar lengkap atau tidak, circuit resistance, earth resistance dan nilai arus mencukupi untuk trip. Penggunaan RCCB adalah wajib untuk sistem TT kerana galangan sistem tersebut adalah tinggi (max 100 ohm). Penjelasan tuan keseluruhan memang betul. correct me if im wrong.keep it up!
@petrusgoel
@petrusgoel 3 жыл бұрын
Terima kasih singgah komen cigu... Betul. Harap video tok dapat bantu orang yang mencari kenapa dan bagaimana RCCB beroperasi dan kaitan Neutral dan Earth.
@semingochannel2151
@semingochannel2151 2 жыл бұрын
Sempoi la encik
@asyifasyif5206
@asyifasyif5206 3 жыл бұрын
Terima kasih ilmu, mmg tgah buat trouble shot ni, masa blaja tidak ada blaja trouble shot
@petrusgoel
@petrusgoel 3 жыл бұрын
Welcome
@monolitobanderasmantoya7739
@monolitobanderasmantoya7739 3 жыл бұрын
Good job bro
@Itz_Iris7212
@Itz_Iris7212 Жыл бұрын
Thanks Sir💯
@hayusrisamsudin5085
@hayusrisamsudin5085 3 жыл бұрын
Tq bos for free ilmu..hi2
@petrusgoel
@petrusgoel 3 жыл бұрын
Sama sama
@piratedprivacy9052
@piratedprivacy9052 3 жыл бұрын
Maaf tuan PetrusGoel, ada seperkara yg perlu diketengahkan ttg N-E fault yg tidak Tripkan RCD... Secara umumnya, N-E fault yg tidak dapat tripkan RCD walaupun Neutral dalam keadaan Loaded adalah kerana Rintangan Pembumian (Earth Resistance) yg terlampau Tinggi sehinggakan Neutral tidak menemui Path yg Solid utk mencetuskan Residual Current(mA) yg mencukupi utk menimbulkan ketidakseimbangan dlm Sensing Coil RCD... Perlu semua kita beringat perbezaan (voltan, impedance) antara L dan E adalah sangat Besar dan Ketara. Namun perbezaan (voltan, impedance) antara N dan E adalah Teramat Kecil dan Tidak Signifikan... L-E fault adalah sangat mudah utk Tripkan RCD walaupun Earth Resistance adalah agak Tinggi kerana mA yg tercetus akibat perbezaan(voltan, impedance) mereka sudah Tentu Tinggi/melepasi batas kadaran Residual Current RCD nya. N-E fault pula adalah sangat bergantung kpd Earth Resistance dan/atau 'flow' utk menentukan samaada mA yang tercetus adalah cukup besar utk melepasi/menghampiri ambang kadaran Residual Current mA RCD... Jika Earth Resistance terlampau tinggi, maka tentu Tiada Solid Path utk Neutral ini 'bocor' utk menimbulkan mA yg mencukupi. Sebab KeDua yg menimbulkan Kesulitan utk RCD Trip ketika N-E fault adalah kerana Earth Resistsnce yg Zero Ohm (spt yg cuba disimulasikan dlm video dgn Isolation TX dan Neutral dibumikan) Apabila perbezaan rintangan pada konduktor N dan konduktor E adalah Seakan-akan Zero Ohm, maka tidak timbul Perbezaan-Medium utk N 'bergerak ke' E. Dalam keadaan seperti ini, maka ia Bergantung Sepenuhnya pada Current(Loaded N) yg terbawa pada konduktor Neutral yg akan 'cuba mengambil path² yg lain/tersedia' seperti konduktor E. Perlu kita beringat bahawa Current/arus memgambil SEMUA Path tetapi lebih menyukai path yg low resistance. Jadi Current yg terbawa oleh konduktor Return (N) sedikit-sebanyak akan ada yg 'menyimpang' ke konduktor E. Dan jika Current yg 'menyimpang' ke konduktor E adalah cukup banyak/besar mA nya berbanding ambang kadaran Residual Current RCD, maka barulah RCD dapat Trip dlm keadaan Neutral Loaded. (sepatuynya ClampMeter tuan dlm video dipasang ke kabel Neutral) Jika Neutral adalah Unloaded, maka sudah tentu tiada Current/arus yg akan 'menyimpang' dan mencetuskan apa² ketidakaeimbangan dlm Sensing Coil RCD, terutamanya bagi kes² N dan E berada seakan² Zero Ohm. Apa²pun terbaiklah kpd pihak tuan kerana menerbitkan video² yg bernas dan jitu... ♥️👍👍👍
@petrusgoel
@petrusgoel 3 жыл бұрын
Betul tuan. Itu adalah antara cabaran semasa saya nak buat video simulasi Trip RCCB Nke E ni... dengan peralatan yang minimum dan 3 elektrod bumi yang tinggi lebih dari 20 ohm, saya terpaksa cantumkan E dan N dekat DB. Ya, L ke E mudah untuk Trip. Walau bagaimanapun, N ke E sukar (ada ditunjukkan bila hanya lampu hidup... sebab current diversion rendah dari 80mA) dan hanya Trip bila Hair dryer dihidupkan kerana leak current lebih 80mA sebab hair dryer guna lebih arus. Walau pun tak lengkap, harap penonton memahami kenapa E ke N RCCB tidak Trip dalam keadaan tertentu.... ya dlm keadaan sebenar, rintangan bumi tinggi. Terima kasih respon... 👍👍
@syafiqani2085
@syafiqani2085 3 жыл бұрын
Maknanya....apabila Earth berstatus rintangan tinggi...maka ia memberi kesan kepada kepekaan elcb/rccb utk trip pada leakage yang sebenar la ya?.. Sebab ada rumah yang mengalami kebocoran L dan N sehingga 70 volt...akan tetapi elcb/rccb tidak trip... Bila pegang belakang peti sejuk...ada kejutan elektrik...bila pegang periuk nasi ada kejutan elektrik... Sepatutnya elcb/rccb trip la kan?.. Tetapi tidak trip... Boleh cikgu ulas maksud saya ini betul atau tidak....
@piratedprivacy9052
@piratedprivacy9052 3 жыл бұрын
syafiq ani Maaf mencelah tuan, tapi utk Rintangan Elektrod Pembumian Utama yg terlalu tinggi sehingga melebihi 200 Ohm sudah dikategorikan Rintangan Pembumian Tidak Stabil. Segala Leakage dari L mahupun N perlukan Satu Path utk Fault Current itu mengalir. Antara path ialah Earthing dan/atau tubuh manusia yg 'grounded'@memijak tanah. Jika Earthing Path adalah Lemah dgn erti kata lain Resistance Terlampau Tinggi/tidak stabil, maka Arus Bocor yg mengalir ke Rod Bumi TIDAK DAPAT MENCETUKAN satu Leakage Current(mA @ A) yg memadai/mencukupi utk Menyentuh/membolosi Ambang Threshold RCCB (contoh RCCB 100mA, minima 60mA diperlukan) walaupun Touch Voltage sudah sangat tinggi pada Chassis.❗😭 Touch Voltage yg dibenarkan adalah 50VAC dan apabila ia bergandingan dgn RCCB 100mA, maka Rintangan Pembumian tidak boleh lebih 500 Ohm. Ketika bergandingan dgn RCCB 300mA, Rintangan Maks. wajib tidak boleh lebih 166 Ohm. (selain Rintangan Pembumian, tuan perlu pastikan Konduktor Bumi Utama dari Chamber Earthing adalah lengkap, tidak terputus dan Tamatan pada Rod Clamp adalah memuaskan)
@wshnbl2274
@wshnbl2274 2 жыл бұрын
@@piratedprivacy9052 tumpang tanye tuan..sy ade buat ujian manual sentuh N sentuh L di soket kuasa tetapi mcb atau rccb tidak trip..sy menggunakan rccb utk litar kuasa 0.03 dan mcb 16a dan buat pengasingan litar kuasa dan cahaya.. pendawaian baru pembumian baru cable 16mm 4 btg rod..2 chember dan rumah saya tak pernah trip walau pun kilat atau guruh kuat.. sy eh Chek semua litar mengikut st tetapi sy tidak dpt mengukur ohm pembumian kerana tiada alat..harap tuan blh bagi pencerahan kenape N sentuh L mcb rccb tidak trip.. sy pening memikirkan... sedangkan E sentuh N rccb trip
@mattmatt3
@mattmatt3 2 жыл бұрын
@@piratedprivacy9052 Salam tuan 1)Utk rccb 100ma, rintangan bumi kena kurang 500 ohm, 2)rccb 300ma, rintangan bumi kena kurang 166 ohm 3)touch voltage kena kurang 50Vac . Utk item 1) hingga 3) nilai dapat dari pengiraan atau reference dari ST/IEC. Kalau dapat dari pengiraaan tolong bg rumus mcm mana dapat nilai. Terima kasih tuan
@hazanrohanidullami1424
@hazanrohanidullami1424 3 жыл бұрын
Buatkan demo macamana nak dapat earth testing bacaan 0 atau kurang dpd 10 ohm, Tq bro..teruskan buat content..Terbaik
@tharmaraorasengeran4206
@tharmaraorasengeran4206 10 ай бұрын
Digital Earth tester ade panduan juga tuan
@afiq358
@afiq358 3 жыл бұрын
Terbaik bosku 👍. Video yg sgt bermanfaat. Semoga segala usaha sentiasa diberkati 👌
@petrusgoel
@petrusgoel 3 жыл бұрын
Terima kasih
@onedeeProject
@onedeeProject 3 жыл бұрын
Terbaik bos atas perkongsiannya
@petrusgoel
@petrusgoel 3 жыл бұрын
sama-sama..
@aloysritz701
@aloysritz701 Жыл бұрын
Terbaik Soma..
@petrusgoel
@petrusgoel Жыл бұрын
Terima kaseh somba
@keydeedin605
@keydeedin605 3 жыл бұрын
Terbaik info tuan
@petrusgoel
@petrusgoel 3 жыл бұрын
Welcome
@wamaw5015
@wamaw5015 3 жыл бұрын
Very good tutorial and I think it would help us from cheated by the electrician
@A.A11632
@A.A11632 3 жыл бұрын
Tahniah sir dh dpt 1k subscriber!
@petrusgoel
@petrusgoel 3 жыл бұрын
Welcomee... Hehe
@timunbonik6883
@timunbonik6883 3 жыл бұрын
Tutorial yang manfaat kepada semua
@petrusgoel
@petrusgoel 3 жыл бұрын
Tq noyung.. Hehe
@mattmatt5439
@mattmatt5439 3 жыл бұрын
@@petrusgoel blh bagi no phone
@clarkjasonchia1887
@clarkjasonchia1887 3 жыл бұрын
Tq Guru 😀😀
@petrusgoel
@petrusgoel 3 жыл бұрын
Thank you
@kaizalarlis5759
@kaizalarlis5759 2 жыл бұрын
Ok mantap
@abdrahmanabdullah3113
@abdrahmanabdullah3113 2 жыл бұрын
Thank you bro
@petrusgoel
@petrusgoel 2 жыл бұрын
Sama sama
@hplar2972
@hplar2972 3 жыл бұрын
Thanks cikgu..kalau ada masa buat explanation untuk earth fault relay.
@petrusgoel
@petrusgoel 3 жыл бұрын
Kena cari EFR...dan CT... Nak tahu parts mana? Cara EFR beroperasi dan trip?
@hplar2972
@hplar2972 3 жыл бұрын
Ya..nak tau operasi dan trip
@zackdee99
@zackdee99 3 жыл бұрын
tuan,,Saya inginkan penjelasan…kenapa life earth ada bacaan 240 tp misal kata life earth dipandang pada lampu ianya trip tp Bila dipasang life neutral dia x trip…mohon penjelasan🙏🏻🙏🏻
@petrusgoel
@petrusgoel 3 жыл бұрын
Sebab Neutral dan Earth tu datang dari punca yang sama. Neutral kat SUB station disambung ke bumi. Earth kat rumah tu elektrod dia kat bumi juga. Sebab itu bacaan antara L dan E adalah sama dengan L dan N. Kenapa L lalu lampu ke E RCCB trip? Sebab RCCB kesan berlakunya 'arus bocor'.... Di mana arus balik tidak melalui N tetapi E. Kalau tuan tiada RCCB.... lampu akan menyala seperti biasa. Tengok video saya yang ini, tuan akan faham : kzbin.info/www/bejne/fKrdf6qootNphZI
@yusaniyunus1091
@yusaniyunus1091 3 жыл бұрын
Terbaik cikgu, boleh tunjuk ajar cara cek ohm pembumian
@petrusgoel
@petrusgoel 3 жыл бұрын
Saya rasa sudah ada orang lain buat video testing ini. Walau bagaimanapun, saya akan cuba buat... ikut style saya sendiri... Tunggu ada masa.
@yusaniyunus1091
@yusaniyunus1091 3 жыл бұрын
@@petrusgoel ok cikgu
@tomthru
@tomthru 3 жыл бұрын
Terbaik Bro...buat lagi banyak content pasal Pendawaian Elektrik :)
@petrusgoel
@petrusgoel 3 жыл бұрын
Welcome... Ya. Saya usahakan dengan kaedah saya sendiri. Lebih pada masalah dan penyelesaian.
@marlonbarry4197
@marlonbarry4197 2 жыл бұрын
Terimah kasih cigu dengan penjelasannya kalau bole buka group whatapp atau telegrams cigu bole saya sentiasa bertanya setiap masalah wiring yang sy bikin
@petrusgoel
@petrusgoel 2 жыл бұрын
Sama sama. Boleh tanya saja di sini sebab saya sentiasa buka youtube…
@edy_elec5254
@edy_elec5254 Жыл бұрын
cikgu nak tnya, kalau x dapat nilai 10 ohm ke bawah, boleh sambung pada besi BRC tiang rumah x?
@abdqayyum708
@abdqayyum708 2 жыл бұрын
Wayar direct life bertemu bumi jadi apa. Mcm dlm vid cikgu buat wayar life masuk life, wayar neutral masuk bumi
@petrusgoel
@petrusgoel 2 жыл бұрын
Kalau live bertemu Earth, akan berlaku litar pintas. Tiada litar pintas sekiranya tiada Neutral disambung ke bumi. Wayar neutral masuk bumi dalam video bertujuan untuk simulasi di mana Neutral di sub station disambung ke bumi.
@paksujun1576
@paksujun1576 3 жыл бұрын
Tuan cuba uji dipendawaian dirumah Offkan semua beban dan shortkan neutral dgn Earth rccb trip dak
@petrusgoel
@petrusgoel 3 жыл бұрын
Tuan dah cuba ka? Trip ka tidak?
@dyhamdydy5015
@dyhamdydy5015 3 жыл бұрын
@@petrusgoel ya tuan. Sy pn nak tngok jga. Sbb sblm ni sy pernh buat tpi tak trip.
@petrusgoel
@petrusgoel 3 жыл бұрын
@@dyhamdydy5015 tanpa load.... kalau rintangan bumi bagus, RCCB akan trip.
@syafiepie9815
@syafiepie9815 2 жыл бұрын
Power tuan. Terus subscribe channel tuan😃
@petrusgoel
@petrusgoel 2 жыл бұрын
TERIMA KASIH
@deanslevin5511
@deanslevin5511 2 жыл бұрын
Ringkasnya, RCCB HANYA akn trip bila wujud imbalance the residual current dlm circuit. Namun perkara utama yg sy nak kongsikn ialah 1) Earthing resistance value mestilah krg drpd 5 ohms. 2) Nilai Rated sensitivity current ( nilai yg tertera pd badan RCCB: 0.1A,0.01A,0.03A..) mestilah a) max' 0.03A utk personal protective maksudnya utk litar spt soket dapur,pgering rambut,water heater dll yg mlibatkn sentuhan secara langsung dgn manusia. b) nilai 0.1A dan keatas adalah utk fire protective, maksudnya litar yg tidak bersentuhan secara langsung dgn manusia cth pam air,lampu,kipas angin dll. harap membantu.
@mohdhafiz7815
@mohdhafiz7815 2 жыл бұрын
tq tuan...penerangan yg jelas
@petrusgoel
@petrusgoel 2 жыл бұрын
Terima kasih. Yup, rintangan bumi kalau diikutkan standard ST below 10 ohm. Walau bagaimanapun untuk video ini, saya shortkan N dan E…hampir sama dengan sistem TN.
@mymal2002
@mymal2002 4 ай бұрын
Dalam demo ni, tak kisah sangat berapa Earthing Resistance, sebab sudah direct connect antara Neutral dari Isolation Transformer ke Earthing Bar DB. Seolah2 guna sistem TN-C Earthing sistem yang tidak memerlukan Earthing Rod di DB pengguna.
@muhammadmoaat8769
@muhammadmoaat8769 3 жыл бұрын
Betulkan saya jika saya silap permahaman..Uji kaji yg cikgu lakukan..jika saya mengunakan rcbo kepekaan 0.01..dan arus bocor 11 mili amp..rcbo akan trip..dan rccb hanya akan berfungsi jika ada load(amp) lebih besar dari kepekaan 0.1..dan tanpa load(amp).rccb tak berfungsi..walaupon ada sentuhan antara cable neutral dan earth(jika arus yg bocor sgt rendah)
@petrusgoel
@petrusgoel 3 жыл бұрын
kalau di rumah, walau tiada load... sepatutnya akan trip (jika pembumian bagus) bila Neutral jumpa Earth. Ini kerana bila di rumah, neutral kita berkongsi dengan jiran kita yang lain. Untuk eksperimen yang saya tunjukkan, saya guna isolation transformer dan hanya 'satu rumah' tidak berkongsi dengan rumah orang lain. Dalam eksperimen ini, saya tunjukkan bahawa rccb hanya akan trip sekiranya arus bocor ke bumi itu melebihi kadaran RCCB. Untuk kes tuan, ya RCBO akan trip dulu dari RCCB 100mA kerana RCBO lebih sensitif.
@muhammadmoaat8769
@muhammadmoaat8769 3 жыл бұрын
@@petrusgoel baik..👌👍terima kasih cikgu
@mrsaiful7776
@mrsaiful7776 3 жыл бұрын
Terbaik bosku👍🏻 *nilai rintangan elektrod bumi 500ohm buku ST terbaru.
@petrusgoel
@petrusgoel 3 жыл бұрын
ya... itu baru. Tapi kalo boleh... lagi rendah lagi bagus.
@petrusgoel
@petrusgoel 3 жыл бұрын
@@Castello-ff3ql itu yang ditulis dalam buku itu. Tak ada pula justifikasi kenapa tukar bawah 500 ohm.
@bensnopy4182
@bensnopy4182 3 жыл бұрын
500 ohm samalah tak ada earth , siapa berani pakai , saya pernah repair satu rumah,hujan kilat sikit ,trip ,itu pun 150 ohm earth resistent .
@mohdazrisyafiqazhar9504
@mohdazrisyafiqazhar9504 3 жыл бұрын
@@bensnopy4182 150ohm barang2 mcm lmpu cepat rosak x?
@muhamadyusriibrahim5730
@muhamadyusriibrahim5730 3 жыл бұрын
hye tuan yg pemurah yg sudi berkongsi ilmu.. Sy nk tnya.. sy nmpak tuan guna clmp meter bran UNI-T.. soalan sy .. tuan rsa ok tk clamp meter jnis UNI-T ? Agak2 accurate tk bacaan nya? Sy pn bru pkai jnis yg sama. Cuma tk slalu guna bli sbb stndny dn harga pn boleh thn cheap2. Model UT210E
@petrusgoel
@petrusgoel 3 жыл бұрын
Ya...boleh consider sebagai accurate. Yang saya guna ni ada 3 titik perpuluhan. Saya compare dengan Kyoritsu KEW2117R yang dua titik perpuluhan. Ada beza +-0.01A rasanya. Sangat kecil dan rasanya boleh diabaikan.... kecuali kita sangat memerlukan kadar kejituan yang tinggi. So far... the UNI-T was reliable.
@derpoyo8181
@derpoyo8181 3 жыл бұрын
Terima kasih atas tunjuk ajar tuan. Byk yg dpt belajar dr youtube tuan. Soalan sy ada 2, normal ke ada leaking current antara N - E? Dan kenapa kalo kita probe multimtter N - E kita boleh dpt reading voltage?
@petrusgoel
@petrusgoel 3 жыл бұрын
Terima kasih. Kemungkinan ada leak N ke E itu tetap ada. Ini berpunca dari litar elektrik atau elektronik... mungkin dalam kadaran yang sangat rendah.. milli ampere atau micro ampere. Seboleh bolehnya ia tak tinggi sehingga boleh tripkan RCCB. Sebab itu kita mesti buat pengujian penebatan antara E dan N supaya rintangan melebihi standard Mega ohm. Berkaitan ada bacaan voltan antara N dan E... ya boleh ada bacaan voltan. E dan N datang dari satu punca yang sama. N melalui kabel, manakala E adalah N yang melalui tanah. Kalo kita ukur L dan N pakai meter kita dapat bacaan voltan. Begitu juga jika kita buat antara L dan E... ada bacaan. Akan ada beza voltan... mungkin dalam 1 atau 2 volt. Jadi bila kita test antara N dan E, kemungkinan yang dipaparkan voltmeter itu beza voltan antara N dan E yang melalui laluan berbeza. Sebab itu kita digalakkan untuk dapat rintangan bumi yang rendah supaya tidak terlalu tinggi perbezaan.
@derpoyo8181
@derpoyo8181 3 жыл бұрын
@@petrusgoel terima kasih tuan atas pencerahan sgt teliti. Adakah dalam nilai voltage L-N lebih tepat berbanding L-E? Adakah perbezaan ni ada pro contra? Mula2 jangkaan sy Nilai L-N ptt lebih tinggi dr L-E tp lps menonton video test RCCB tuan yg baru sy tgk nilai voltage L-E > L-N.
@petrusgoel
@petrusgoel 3 жыл бұрын
@@derpoyo8181 L-N penting. Perbezaan yang tinggi dengan L-E akan menunjukkan ada masalah pada sistem pembumian. Kalau bukan sistem pembumian, ia juga disumbangkan oleh ketidak seimbangan siatem 3 fasa. Mungkin rumah tuan guna fasa Merah (L1). Jiran dan lain guna fasa Biru dan Kuning. Neutral hanya satu sahaja... semua kongsi. Jadi, voltan E dan N mungkin berubah ubah pada masa yang berbeza.
@otaitaiko9301
@otaitaiko9301 3 жыл бұрын
Terima kasih cikgu.. baru paham macam mne RCCB trip bila E-N touching.. lepastu saya nk tanya memang normal kan volt L-N = L-E = 230v ??
@petrusgoel
@petrusgoel 3 жыл бұрын
Sama atau hampir sama kerana N dan E datang dari punca yang sama. Hanya diasingkan RCCB utk keselamatan. Boleh tonton video saya ini utk info... kzbin.info/www/bejne/fKrdf6qootNphZI
@mattmatt5439
@mattmatt5439 3 жыл бұрын
Tuan blh share contact no..
@tanjong2021
@tanjong2021 Жыл бұрын
"Inspection" sekadar dari "DB" ke "incoming supply" yg."first" sudah ada byk."testing tool" nya..hanya perlu "tahu" cara guna dan "maksud" bacaan nya shj. Tetapi "keadaan sebenar" di lapangan ada lah "circuit" yg."huru-hara" dari "first incoming supply" ke point-point "switch" & "plug"/"soket kuasa" beserta "internal circuit" kat "lampu"/"kipas"+"water heater"+"aircond" dan perkakas-perkakas elektrik. Jadi..pada masa skrg.apa kah "ada" atau sebalik nya, "teknologi" atau "testing tool" just sekadar utk."tahu" dgn."mudah" dan "cepat", "continuity"nya berbanding "cara tradisional" pakai "manually check" yg.mana ia nya bergantung sepenuh nya kpd."kepakaran"/"pengalaman" seseorang wireman. Jika "solusi"nya..tetap kpd."re-wiring" jugak, "lebih praktikal", silibus pembelajaran di pusat-pusat latihan diringkas "content" & "hour"nya kpd.setakat "wiring" shj. sbb "rata-rata" nya wireman skrg.at the most "cenderung" kpd."inspection" & "testing" + "re-earthing"/"re-wiring" shj.atau di"lain bahasa" disebut "after sales service"/"maintenance". Kerja-kerja "troubleshooting" & "repairing" sudah "pupus". Kalau "handphone" pulak.."technician" sgt."suka" dapat job "circuit shorting" sbb "harga pasaran" sgt."tinggi", "x perlu beli barang" dan kerja nya "ringkas" & "cepat" janji "mmg.expert".
@petrusgoel
@petrusgoel Жыл бұрын
Wireman bertauliah sepatutnya boleh buat troubleshooting walau dengan ketiadaan alat tangan yang canggih. Sebaik mana sekalipun dan seluas mana pengalaman wireman, akhirnya ia masih stick kepada business. Nak buat bisnes dengan jujur dan beretika itu, ia perlu juga datang dengan ''kehendak perniagaan'. Memang pelanggan suka orang yang jujur, tapi orang yang berniaga biasanya mengejar masa. Silibus dan latihan yang diberikan di pusat latihan memang banyak fokus pada kerja wiring berbanding troubleshooting. Troubleshooting banyak diperolehi semasa bekerja. Saya setuju dengan tuan, kalau kita banyak mengelak kerja troubleshooting serta menyelesaikan masalah....ia menunjukkan wireman itu belum cukup mahir menjalankan kerja sebagai wireman yang kompeten. Tapi, banyak juga wireman yang kompeten dan mahir troubleshooting memilih untuk buat wiring baru sebab lebih mudah. Pure business...
@tanjong2021
@tanjong2021 Жыл бұрын
@@petrusgoel ..terbaek! Terima kasih kerana masih sudi replied. Kat rumah ada buat tambahan "3"+"1" utk."plug point"+"switch point" yg.di"looping" dari "1" plug point yg."ori"/"direct DB" pakai "1 mcd" yg."jarak" nya "25 kaki" dari "DB" manakala sekitar "3 kaki" antara "plug point" yg."ori" dan "tambahan". (Bermakna "circuit tambahan" tuh panjang nya 3 kaki). Berlaku "tripping" yg.mana "mcd" tersebut + "RCCB" jatuh."Wireman" yg."pertama" kata..kabel "neutral" di"plug point" yg."ori", "voltage" nya "dropped" dan kena "re-wiring". "Pasal" apa "dropped" dan di"mana"..jawapan nya "tak boleh tahu". "Wireman" yg."kedua" kata.."plug point" yg."ori" sudah boleh ber"fungsi" setelah "looping" tersebut di"tanggal"kan dan kena buat "looping" lain dari mana-mana "plug point ori" lain yg.paling dekat dgn."tambahan" tersebut sbb "tak tahu" pasal apa berlaku "tripping" samada "plug point" yg.di"looping" itu ber"masalah" atau "circuit tambahan". Oleh kerana mereka kata "tak tahu" apa sebab "tripping"..tiada "looping" yg.baharu & "re-wiring" dibuat dan buat sementara "switch point" tambahan tersebut di"hidup"kan pakai "sambungan" se"utas" kabel dari "plug point ori" yg."lain" dan "tap" di kabel "neutral" masing-masing. Mohon "nasihat" Tuan.
@petrusgoel
@petrusgoel Жыл бұрын
@@tanjong2021 saya jawab secara general dulu berkaitan wiring. Yang paling penting adalah keselamatan. Ok, pendawaian boleh dibuat dengan selamat dengan mengikut standard dan juga boleh juga selamat sekiranya tidak mengikut standard. Yang penting, wireman itu mestilah tahu teori dan praktikal. Teori ini akan membantu kita menjalankan kerja tidak mengikut standard. Ini kerana, standard kebiasaannya dibuat secara 'payung'. Contoh, mengikut standard ...soket mesti guna kabel 2.5mm. Kalau litar itu nanti hanya akan disambung pada 2 soket yang mana diketahui soket itu akan hanya digunakan untuk menghidupkan 2 kipas meja sahaja, maka...litar soket itu boleh menggunakan kabel 1.5mm. OK. Berkaitan soalan tuan, adakah mereka ada membuat Pengujian Rintangan Penebatan? MCB trip disebabkan oleh litar pintas (short antara L dan N) atau overload. Manakala kalau RCCB, ia disebabkan ada L atau N yang terkena E. Keputusan sekadar agak-agak tanpa ada buat pengujian boleh dipertikaikan.
@tanjong2021
@tanjong2021 Жыл бұрын
@@petrusgoel ..terima kasih atas pencerahan itu. "Plug point" yg."ori" tuh boleh jadi "overload" tak? Kalau "ya"..sy "tak faham" knp?..sbb "mcd"nya sudah "C32" dan "load"nya cuma sekadar "1" unit peti ais + "3" unit kipas + "6" unit lampu. Lagi satu..selepas "looping" ditanggal, "rccb" dah "tak turun" dan pulak "wireman ke-2" begitu "confident", buat "looping" kat lain-lain "plug point" dan hanya "wiring" dari "situ" dan ber"sambung" ke "circuit tambahan" yg.sediada shj. Dari "situ"..sy "faham" yg."circuit tambahan" sediada itu "tiada masalah", yg.ber"masalah" mungkin di"salah satu" antara "3" tambahan "plug point" tersebut. Manakala, "wireman pertama".."confident" yg."plug point" yg."ori"/"DB" itu sudah "problematic" tp "tak tahu" samada "circuit"nya ke atau hanya sekadar "plug point"nya shj.
@GO-su3lf
@GO-su3lf 2 жыл бұрын
bos, why live short to earth must use bulb to test?
@petrusgoel
@petrusgoel 2 жыл бұрын
use bulb as load/resistive load to reduce spark. You need to know that earth = Neutral separated by RCCB. Without bulb can do, but there might be spark occured....
@hadisalman5571
@hadisalman5571 2 жыл бұрын
Jenama total clamp meter bagus tak tuan
@petrusgoel
@petrusgoel 2 жыл бұрын
Maaf…saya tidak ada pengalaman guna jenama total.jadi tak dapat nak komen…terima kasih.
@FatimahSaad-b8e
@FatimahSaad-b8e 3 ай бұрын
U the best
@neodiy
@neodiy 3 жыл бұрын
The best of deep knowledge in electricity ...best bro... i have a question regarding how to wire the from sesco meter to double pole mcb switch...how do you wire them without turning off the high voltage from the meter line? I mean how do you even strip the insulator of such high voltage current without getting electrocuted. And what are the safety practiice that we need to take note to avoid accident? Perhaps a simple video would explain that perfectly. tq in advance
@piratedprivacy9052
@piratedprivacy9052 3 жыл бұрын
Sir, a competent electrician will know how to Pull the Cut-Out Fuse somewhere at meter board... If you're talking about the parts before Meter, ie Service-Cabling then adequate PPE and Insulated Tools to be used while working 'hot'.
@aigamanii
@aigamanii 2 жыл бұрын
Selamat petang cikgu. Boleh terangkan apakah itu pendawaian earth looping. Adakah pendawaian earth looping ini selamat dan apa kesannya. Adakah earth looping yg menyebabkkan apabila buat soket testing menggunakan elcb soket testing, semua lampu menyala pada soket tester dan utang merah tidak trip apabila ditekan.
@petrusgoel
@petrusgoel 2 жыл бұрын
Lampu pada Socket tester kebiasaannya akan menyala apabila pendawaian lengkap, termasuk ada Earth. Tetapi, apabila butang TEST pada socket tester ditekan, RCCB tidak trip? Ini disebabkan oleh rintangan bumi yang tinggi. Kenapa lampu pada socket tester menyala walau rintangan tinggi? Sebab socket tester kesan ada bumi, serta pemasangan polarity L dan N yang betul. Satu lagi punca RCCB tidak trip apabila butang TEST pada socket tester ditekan adalah masalah Neutral yang disambung ke bumi dari SUB Station yang lemah. Sebab itu satu pengujian Earth Loop Impedence Test perlu dibuat. Malangnya saya tiada alat uji berkenaan.
@aigamanii
@aigamanii 2 жыл бұрын
@@petrusgoel terima kasih cikgu. Tapi dalam kes rumah saya, wayar earth disambungkan ke wayar neutral. Bila saya buat elcb testing utk soket di tingkat bawah, RCCB trip, tapi untuk tingkat atas elcb testing tidak trip. DB tingkat bawah dan tingkat atas berasingan. Saya suspek wyreman buat bypass earth untuk tingkat atas.
@petrusgoel
@petrusgoel 2 жыл бұрын
@@aigamanii ooo…DB berasingan. Earth DB di atas ada RCCB? Earth di atas tu disambung ke mana?
@yeoschannel838
@yeoschannel838 5 ай бұрын
di awal video L & E . hairdryer sudah di on kan secara logiknya amp naik dari 0.78 kepada 2.79 , hairdryer 2amp dari 0.78ma iaitu kipas & mentol. apabila ujian N & E dijalankan. hairdryer telah dimatikan dan bacaan amp kembali pada 0.78ma.harap boleh jelaskan
@hasbu1
@hasbu1 2 жыл бұрын
Cikgu minta batuan, Saya test guna Rcd Tester (uni-t) dan socket tester tetapi RCD tak trip (socket tester semua lampu ok) - test trip di RCD it self boleh trip- keadaan rod bumi tidak tersambung Selepas Sambung rod bumi semua ok. Pertanyaan kenapa test trip di RCD boleh trip tetapi bila guna socket tester dan RCD tester tak boleh trip bila rod bumi tak sambung? Adakah test trip di RCD tu boleh trip jika rod bumi tidak tersambung atau ohm bumi terlalu tinggi
@petrusgoel
@petrusgoel 2 жыл бұрын
Ooo..ok. Test button trip kat RCCB tu tidak memerlukan Earth. Bila test button tu ditekan, ada perintang antara L dan N dalam unit RCCB akan menyebabkan ‘relay’ dalam unit itu tripkan suis RCCB. Socket tester pula memerlukan EARTH untuk tripkan RCCB. Itu adalah normal. Ya, test trip di RCCB/RCD boleh TRIP jika rod bumi tidak bersambung. Harap membantu.
@petrusgoel
@petrusgoel 2 жыл бұрын
Boleh tonton video saya yang ni untuk lihat RCCB trip tanpa adanya Earth. kzbin.info/www/bejne/rp-Wn5eMbaumb6s
@hasbu1
@hasbu1 2 жыл бұрын
@@petrusgoel terima kasih cikgu maksudnya yg ditulis untuk test monthly tak berapa tepat la! Sebab test trip ok actual condition tak semestinya so kena guna socket tester or RCD tester baru valid test? Betul ka cikgu
@petrusgoel
@petrusgoel 2 жыл бұрын
@@hasbu1 ya... Test monthly tu hanya untuk uji mekanisma RCCB sama ada akan trip kalau ada ketidakseimbangan arus antara L dan N. Kite perlukan ia beroperasi secara automatik dan itu memerlukan E.
@rokstar8424
@rokstar8424 2 жыл бұрын
Cikgu, kalo terus tukar rccb kepada kepekaan yang lebih rendah mungkin lebih cepat trip kan?
@petrusgoel
@petrusgoel 2 жыл бұрын
Dia akan TRIP kalau kadaran arus bocor tu sampai tripping value dia. Tapi tak boleh tukar suka suka.... Mesti ikut standard....
@azman4749
@azman4749 2 жыл бұрын
Kalau guna rccb 30mA, ada wayar extension yg basah, pun boleh trip. Kalau guna utk water jet cleaner dan percikan air kena pd wayar extension pun boleh trip. Saya dah kena bila tukar rccb utama kpd 30mA drp 300mA yg dipasang pemaju
@pakidena
@pakidena 3 жыл бұрын
AUTO SUBSCRIBED BOH
@petrusgoel
@petrusgoel 3 жыл бұрын
Terima kasih
@miormaarofmiormokhtar6224
@miormaarofmiormokhtar6224 2 жыл бұрын
Cikgu, boleh tanya jika wayar neutral dan wayar earth bersentuhan..dan berlaku kadang kala cut off fuse di luar trip..bukan rccb..minta penjelasan cikgu
@petrusgoel
@petrusgoel 2 жыл бұрын
Kemungkinan besar ia berlaku apabila Neutral floating (Neutral putus) dan itu yang bersentuhan dengan E. Neutral putus bermaksud neutral yang balik dari beban tidak bersambung semula dengan terminal N pada DB, menyebabkan ia juga sama seperti L. Ini kemungkinan yang menyebabkan cut out putus.
@Jefsams111629
@Jefsams111629 3 жыл бұрын
Salam tuan, adakah main switch dan rccb 3fasa boleh digunakan pada pendawaian 1fasa? Mohon pencerahan tuan, terima kasih.
@muhamadyusriibrahim5730
@muhamadyusriibrahim5730 3 жыл бұрын
Boleh.. hnya guna kan 2 cable iaitu LIVE + NEUTRAL .. cuma membazir and cost.. sbb equiptment untk three phase lebih mhal dari single phase..
@petrusgoel
@petrusgoel 3 жыл бұрын
Tq Muhamad Yusri... Ya.. Sams.. Boleh pakai. Pastikan sambung live pada satu fasa tu pada point yang betul. Kalo tidak, Test button tak berfungsi. Tq
@Jefsams111629
@Jefsams111629 3 жыл бұрын
Terima kasih atas pencerahan tuan
@blues4478
@blues4478 Жыл бұрын
Tuan..MCCB trip offload..adakah punca erthing nutral touching?
@petrusgoel
@petrusgoel Жыл бұрын
kalau MCCB tu jenis yang boleh trip kalau earth neutral bersentuhan...ia akan trip. MCCB ada beberapa jenis. Ada yang berfungsi sebagai overload/short circuit protection. Ada juga jenis yang dipasang elemen dalamannya supaya trip bile Neutral sentuh Earth. Pada DB ada dipasang Earth Fault Relay tak?
@agsabtubinjuaraagsabtubinj2336
@agsabtubinjuaraagsabtubinj2336 3 жыл бұрын
Ponsikai bosku....salam damai dr papar....minta maaf la byk² dulu,wiring d rumah sya ada sikit masalah ba...kabel soket neutral d rumah sya ada karen,pastu nda suda mau hidup tu soket...apa masalah dia tu...
@petrusgoel
@petrusgoel 3 жыл бұрын
Mungkin ada putus Looping Live dalam litar soket itu. Mau cari wireman pigi check.
@agsabtubinjuaraagsabtubinj2336
@agsabtubinjuaraagsabtubinj2336 3 жыл бұрын
@@petrusgoel owh...ba...trima kasih atas khidmat nasihat tu...smoga saluran kau ni trus maju jaya la....ponsikau gaman...
@petrusgoel
@petrusgoel 3 жыл бұрын
@@agsabtubinjuaraagsabtubinj2336 trima kasih singgah youtube saya ba
@zalilani7676
@zalilani7676 Жыл бұрын
Knapa tak trip cara fizikel tidak dbuat knapa..?.. Cuba buat semula la.
@petrusgoel
@petrusgoel Жыл бұрын
Apa maksud trip secara fizikal tu?
@ahmadaqmal9912
@ahmadaqmal9912 3 жыл бұрын
Tuan..kalau guna soket tester...bila tekan button ..x trip...apa masalah dia..? Dlm soket tester 3 lampu tu mnyala...
@petrusgoel
@petrusgoel 3 жыл бұрын
Socket tester boleh test sampai berapa mA? Adakah 150mA? RCCB 100mA? Kalau RCCB tidak trip.... ada kemungkinan rintangan elektrod bumi terlalu tinggi. Kalau tuan ada multimeter.... set VAC, Ambil bacaan di DB antara L dengan N, satu lagi L dengan E. Berapa bacaan? Share... Tq
@lorenintan7735
@lorenintan7735 3 жыл бұрын
Salam...bagaimana cara untuk merendahkan bacaan rod resistance supaya kurang dari 10ohm
@petrusgoel
@petrusgoel 3 жыл бұрын
Ada beberapa kaedah. Pertama: Pastikan elektrod ditanam di kawasan tanah yang basah/terdedah dengan hujan. Kedua: Tambah elektrod (sambung). Ketiga: Tanam beberapa elektrod pada jarak yang berbeza dan sambung bersama. Keempat: Penggunaan arang/garam/serbuk besi untuk perbaiki konduktiviti tanah.
@powerlines7156
@powerlines7156 3 жыл бұрын
@@petrusgoel maaf tuan.mau tanya apakah tidak merbahaya jika tanam rod Earth ke kawasan yg lembab?takut nanti ada live masuk disana..haha🤣.maaf tuan saja ja sya tanya..sebap sya pun mau tanam rod baru ni..sbp sya touch E dan N tapi tidak trip.
@petrusgoel
@petrusgoel 3 жыл бұрын
@@powerlines7156 bagus check RCCB dulu.... mungkin RCCB problem. Kalau tuan ada voltmeter, cuba ambil bacaan voltan antara L dengan N dan banding antara L dengan E.
@powerlines7156
@powerlines7156 3 жыл бұрын
@@petrusgoel RCCB sudah test tekan ada 1 butang test tu.lepas tekan butang test tu ok juga tu RCCB trip juga..kalau tuan suspek apa mslh ya mcm tu.
@petrusgoel
@petrusgoel 3 жыл бұрын
@@powerlines7156 tekan butang TEST itu tidak uji leak ke E. Kalau tekan memang trip. Tapi kalau berlaku leak ke E, mungkin RCCB tidak trip.... sebab satu, Rintangan bumi tinggi.... satu lagi RCCB tidak sensitif. Mesti guna RCCB Digital Tester baru tahu.
@milah1958
@milah1958 3 жыл бұрын
Kenapa bila buat RCD test pada power socket RCCB tak trip
@petrusgoel
@petrusgoel 3 жыл бұрын
Guna Soket Tester kah? Satu soket atau bila cuba di semua soket dia tak TRIP? Ketiga-tiga lampu kat soket tester menyala tapi bila tekan RCCB Test button, RCCB tidak trip? Kalau kes begini, confirm masalah rintangan elektrod bumi tinggi.
@nadziradnanguitar874
@nadziradnanguitar874 3 жыл бұрын
@@petrusgoel tuan, sy juga punya masalah sama. Guna socket tester semua lampu menyala (correct) kalau ikot pada panduan tester.. Tp apa bila tekan rcd tester, rccb tidak trip. Saya guna 2 tester yang berlainan nilai.. 1
@leleonet
@leleonet 3 жыл бұрын
Tumpang tanya tuan, saya ada clamp meter kyoritsu hijau tu, macamana cara untuk cek rintangan earthing di rumah saya ya, perlu clamp di mana2 kah
@petrusgoel
@petrusgoel 3 жыл бұрын
untuk rintangan earthing, atau earth rod resistance test....tak dapat ukur pakai clamp meter. Kena pakai Earth Resistance Tester.
@thronezofficial8811
@thronezofficial8811 Жыл бұрын
nk tnye 1 je.. ape itu neutral dan knp die xde api..
@petrusgoel
@petrusgoel Жыл бұрын
Neutral dan Earth tu adalah satu entiti yang sama. Terminal Neutral pada transformer 3 fasa disambung ke bumi. Ia adalah 'ZERO potential'. Sebab itu bila di letak test pen tak menyala. Untuk lebih detail, ia bukan 100% tiada arus, ia ada arus dan jadi merbahaya sekiranya berlaku 'floating neutral'.
@dyhamdydy5015
@dyhamdydy5015 3 жыл бұрын
nak tnya ni. Neutral dan life akan dismbungkn untk memanskn kattel kn. Pertanyaan di sini kenpa tak trip ah. Dan mcm mna proses pemnsn tu berlaku. Boleh tolong tk
@petrusgoel
@petrusgoel 3 жыл бұрын
Ooo... Dalam heater ada coil (gegelung). Rintangan gegelung ini rendah... sebab itu ia panas. Kenapa tidak trip? Sebab ada rintangan walaupun rendah ia tidak litar pintas...tapi bila panas, ia menggunakan arus yang tinggi. Sebab itu bila alat ada heater, arus tinggi / kuasa tinggi. Litar pintas = tiada rintangan....MCB trip. Harap menjawab ya... Tq
@azman4749
@azman4749 2 жыл бұрын
Elemen pemanas mempunyai daya rintang yg rendah dan tahap lebur yg tinggi dan nilai rintangan ditetapkan ditetapkan oleh pengeluar (dilihat dr nilai watt. Sebab itu tidak. Biasanya jika menggunakan palam 3 pin biasa, watt dihadkan agar arus yg diguna oleh alat tidak melebihi 13 amp utk keselamatan. Jika litar sso dikawal oleh mcb yg sesuai, maka mcb tidak trip. Namun jika tenaga yg dihasilkan oleh elemen pemanas tidak digunakan iaitu elemen tidak direndam dlm air ( asalnya utk tujuan pemanasan air) elemen akan mengalami pemanasan melampau dan boleh menyebabkan kebakaran walaupun mcb ataupun rccb masih berfungsi. Cerek dan periuk masak nasi mempunyai ciri cut off bila berlaku pemanasan melampau berdasarkan ambang yg ditetapkan pengeluar. Biasanya dikawal suis jalur dwilogam atau kawalan elektronik bagi alatan yg lebih moden.
@azreeahmat8396
@azreeahmat8396 2 жыл бұрын
Maaf tuan sya nk bertanya mengenai RCD tester, sya kerap guna untuk membuat pemeriksaan tetapi kali pertama sya mndapat bacaan di screen RCD display sya UF Hi, jd sememangnya RCcb tak trip meski da ganti baru, tetapi sya nk tahu kenpa bole dpat bacaan UF Hi..harap tuan dpt menjawab, da lama sya cri orang yg ble jawab tp tiada yg dpt bg penjelasan 😔
@petrusgoel
@petrusgoel 2 жыл бұрын
Biasanya bacaan HI diperolehi sekiranya RCCB tidak trip dalam masa yang ditetapkan. Ini biasanya disebabkan oleh rintangan bumi yang tinggi. Sekiranya rintangan elektrod bumi baik, kemungkinan ada masalah rintangan yang terlalu tinggi antara elektrod bumi rumah ke terminal bumi/neutral di substation. Satu lagi, kalau RCCB 100mA, tapi setting tester 50mA contohnya….ia akan keluar HI juga. Cuba tuan ambil bacaan antara Live dan Earth kat DB. Bandingkan dengan Live Neutral. Share sini..tq
@fatkhanmuhammad6613
@fatkhanmuhammad6613 2 жыл бұрын
jika berlaku ada kilat kuat trip langkah apa yang diambil bang?? tanam rood smpai dibawah 10 ohm kah??
@petrusgoel
@petrusgoel 2 жыл бұрын
Pada pendapat saya, itu adalah perkara biasa tuan. Kilat kuat RCCB trip. Bagaimana ia boleh berlaku? Kemungkinan besar ada tempias kilat pada bekalan voltan /kabel yang masuk ke rumah menyebabkan berlakunya ketidakseimbangan arus antara L dan N sekaligus me yebbkan RCCB trip. Ia adalah perkara biasa. Bukan masalah Earth. Sekiranya RCCB tidak Trip, ada kemungkinan barang dalam rumah akan rosak. Tetapi bukan bermaksud kerosakan tidak akan berlaku, ini kerana tenaga dari kilat sangat kuat ada kala sudah masuk ke dalam rumah, baru RCCB respon. Kecepatan arus dari kilat lebih laju dari respon RCCB. Kalau tuan nak protect barang dari rosak, pasang Surge Protection Device..SPD.
@fatkhanmuhammad6613
@fatkhanmuhammad6613 2 жыл бұрын
@@petrusgoel oke bang ,,jika ada tempias kilat masuk mengapa ada rumah yang trip ada rumah yang oke saja/tak trip..
@petrusgoel
@petrusgoel 2 жыл бұрын
@@fatkhanmuhammad6613 implikasi pada setiap RCCB berbeza beza. Setiap RCCB walau sama jenama mempunyai response time yang berbeza semasa diuji. Kadaran 'surge' ke rumah tuan dan rumah yang lain juga berbeza beza. Fasa bekalan pun berbeza. Mungkin surge tinggi pada Fasa Merah, tapi rendah pada Kuning dan Biru. Satu lagi, Bumi dan Neutral tu adalah sama. Mungkin rumah tuan dekat dengan punca neutral yang di tanam ke bumi dari tiang elektrik... jadi ia menyebabkan rumah tuan yang kena. Sekiranya hanya rumah tuan yang selalu trip masa kilat, pertimbangkan untuk tukar RCCB pada RCCB jenama Hager yang ada 'nuisance' tripping prevention.
@fatkhanmuhammad6613
@fatkhanmuhammad6613 2 жыл бұрын
@@petrusgoel @Petrus Goel oke bang terimakasih telah berbagi ilmu yang mahal ini,, sekiranya anda berkenan coba buat video tentang hal ini pasti ramai orang akan melihat video ini.. tapi yang saya belum faham banyak wireman yang membahas asal kilat RCCB trip dia akan buat tanam rod sampai bawah 10 ohm apakah itu efektif juga..sedangakan dalam DB sudah jelas EARTH sama neutral asing tidak ada sangkut paut..
@johannis8483
@johannis8483 3 жыл бұрын
Bang sy nak tanya...switch tested rccb tu x function...kena tukar ka?
@petrusgoel
@petrusgoel 3 жыл бұрын
Kalau tekan tak trip….sama ada tiada supply masuk atau ia rosak. Kalau ada supply, tekan tidak trip….confirm rosak. Kena tukar.
@awaludienmajumi7202
@awaludienmajumi7202 3 жыл бұрын
Tuan, adakah bila pembumian Nutra dekat substesen TNB terkena panahan kilat, ia akan memberi kesan pada sistem elektrik dlm rumah yg berdekatan dengan SUB.. sbb pembumian rumah ada link dengan pembumian nutral
@petrusgoel
@petrusgoel 3 жыл бұрын
Saya tak dapat bagi jawapan yang tepat untuk ini. Pendapat saya (mungkin kurang tepat) ya ada...electric surge dari kilat mengalir melalui bukan sahaja neutral, tapi Live sekali. MSB pun boleh trip. Kalau panahan petir dekat sub.... yang dekat dengan sub mungkin akan kena kesan yang lebih berbanding yang jauh. Sub Station biasanya ada over current relay dan protection lain manakala rumah hanya bergantung pada RCCB atau SPD kalau ada. Ini pendapat saya sahaja... mungkin tak tepat. Kena ada data ujian untuk sokong.
@awaludienmajumi7202
@awaludienmajumi7202 3 жыл бұрын
Ok tuan terima kasih atas jawapan, sy setuju dgn jawapn tuan ni, sebab ada wyerman guna pendapat ini, yang mengatakan rumah yang dekat dengan SUB, dekat dengan menara pencawang, atau tiang yang dibumi akan sangat berisiko dengan kilat, Kerana kilat yg mengenai kedua dua punca tersebut akan meresap kebumi dan pencari mencari pengalir yg ada di sekitarnya ia itu rod bumi rumah..
@FirdausKacang-il3ve
@FirdausKacang-il3ve 8 ай бұрын
Pertanyaan kalau sambom kan niyuter ke mccb dia akan terip tak saya baru belaja
@petrusgoel
@petrusgoel 8 ай бұрын
MCCB biasanya guna untuk 3 phase sahaja.
@roslanyusof1661
@roslanyusof1661 3 жыл бұрын
Tuan nak tanya kalau kita nak test earthdig .berapa kedalaman rod .perlukah kita kena tanam 3 penjuru rod
@petrusgoel
@petrusgoel 3 жыл бұрын
Tanam satu rod. Lepas tanam, uji kerintangan bumi pakai Earth tester. Kalau tinggi, boleh sambung... Ketuk masuk lagi. Uji.... Kalau masih tinggi, baru cucuk lokasi lain dan sambung dengan yang awal tadi. Setiap kali cucuk... Mesti ukur.
@powerlines7156
@powerlines7156 3 жыл бұрын
@@petrusgoel maksud nya tanam beberapa rod tapi dikawasan yg berlainan lepastu cable tu kasi link ja pergi ke semua rod yg kita tanam tadi kah tuan?
@petrusgoel
@petrusgoel 3 жыл бұрын
@@powerlines7156 tanam.... lepas tanam uji kerintangan. kalau tinggi sangat boleh sambung lagi sebarang. Kalau 2 batang masih tinggi, baru pacak lagi di lokasi berdekatan. Kena uji lagi.... Tanam di tanah lembap lagi bagus kerana air dalam tanah.... air mengalirkan arus Elektrik dengan baik. Kalau RCCB beroperasi dengan baik, tiada isu arus Elektrik mengalir secara 'terbuka' atas tanah.
@tanjong2021
@tanjong2021 Жыл бұрын
Kalau jadi mcm ni atau ada "shorting" atau "leakage", wireman selalu nya ambil "jalan mudah" suruh buat "re-wiring". Bukan kah kerja nya "wireman" itu kena cari "sbb" nya dan "betul" kan nya..kalau sekadar mai rumah, checking pakai pelbagai alat "testing"..at last suruh "re-wiring", bila disuruh cari..mcm-mcm alasan. Setakat "mmg.mcm tuh" ke "kerja" nya seorang wireman?
@petrusgoel
@petrusgoel Жыл бұрын
Ada banyak jenis wireman. Ada wireman yang mahir buat wiring, ada yang boleh buat wiring dan buat testing, ada yang boleh buat wiring, testing serta troubleshooting. Boleh guna meter tidak semestinya pandai troubleshooting. Ia juga bergantung pada pengalaman. Masalah berbeza beza. Saya walau dah lama buat wiring, troubleshooting, testing...ada kala masih jumpa masalah baru. Keputusan untuk selesaikan masalah sama ada dengan cari masalah dan betulkan atau cadang pendawaian semula itu bergantung pada 'wireman' tadi. Proses pendawaian semula lebih mudah berbanding mencari masalah. Masa cari masalah adakalanya lama dan selesaikan upah kecil. Wiring baru, tak pening kepala....upah lebih besar. Jadi, ia bergantung pada anda untuk memilih. Wireman pula...mereka buat bisnes.
@tanjong2021
@tanjong2021 Жыл бұрын
@@petrusgoel ..terbaek! "Reply" yg."baik", "jujur" dan "profesional". Sy "simpul" kan.."re-wiring" itu "business oriented". Jadi, para pelatih di"ajar" utk."jujur" dgn.berusaha utk.cari "sbb..punca..solusi" ke atau "business oriented"?
@petrusgoel
@petrusgoel Жыл бұрын
@@tanjong2021 kita ajar pelatih/pelajar untuk bersedia masuk alam pekerjaan. Bila mereka bekerja atau buka syarikat sendiri, pastinya mereka belajar sesuatu dan mendapat pengalaman. Dalam perniagaan, mereka yang menentukan untung rugi. Memang kita ajar berkaitan kejujuran, tapi bisnes ada kala boleh berlaku sebaliknya. Cadang wiring baru waima boleh buat troubleshooting tu tidak juga boleh dikatakan 100% tidak jujur, mungkin itu cara terbaik yang lebih mudah dari sudut perniagaan. Pengguna 'berpengetahuan' itu juga boleh membantu dalam membuat keputusan sama ada buat maintenance atau pilih untuk buat wiring baru. Saya lebih suka memberi penerangan kepada pengguna berkaitan setiap keputusan yang saya buat/cadangkan. Contohnya kalau saya disuruh repair alat elektrik, saya akan bagitau kos beli alat ganti dan upah berbanding beli alat elektrik baru. Biar mereka pilih.
@nazrisan
@nazrisan Жыл бұрын
Adakah normal kalau tiada load tapi mcb trip bila earth dan neutral bersentuhan.
@petrusgoel
@petrusgoel Жыл бұрын
MCB atau RCCB?
@kucing-fu8uh
@kucing-fu8uh 3 жыл бұрын
salam tuan, nak tanya apa akan jadi jika neutral sentuh earth dengan arus yg besar tapi pembumian rumah ada masalah, pasti RCCB tidak trip dan apa yg akan terjadi?? adakah berlaku litar pintas dan menyebabkan kebakaran atau berlaku perkara bahaya yg lain?
@petrusgoel
@petrusgoel 3 жыл бұрын
RCCB tidak trip dan semasa sentuhan itu dibuat... semua kabel Earth dalam rumah menjadi Neutral. Sekiranya 'arus bocor' neutral ke Earth itu berkekalan dan RCCB gagal trip kerana masalah rintangan bumi yang tinggi atau RCCB tu rosak... Litar pintas antara L ke E akan menyebabkan berlaku spark sama seperti pintasan L ke N. Kalau MCB pula problem.. tidak trip atau Jam.... kabel boleh lebur/cair. Banyak implikasi lain... Pasang RCCB tapi pembumian teruk itu seolah olah RCCB duduk sebagai boneka sahaja.
@kucing-fu8uh
@kucing-fu8uh 3 жыл бұрын
@@petrusgoel terima kasih
@rizalhanapiah56
@rizalhanapiah56 2 жыл бұрын
tuan.maaf nak tanya...neutral dari transformer ke bumi elcb tak trip walau on dryer..bermakna elcb trip bila neutral lepas elcb short pada bumi sahaja??
@petrusgoel
@petrusgoel 2 жыл бұрын
YA, Sepatutnya RCCB trip sekiranya Neutral yang telah keluar dari RCCB dipintas/bocor ke bumi. Dengan syarat, kadaran arus bocor itu hampir, sama atau melebihi nilai tripping pada RCCB.... contohnya 100mA.
@rizalhanapiah56
@rizalhanapiah56 2 жыл бұрын
oh begitu...terima kasih tuan
@petrusgoel
@petrusgoel 2 жыл бұрын
@@rizalhanapiah56 sama sama
@shah3184
@shah3184 2 жыл бұрын
Nak Tanya tuan. Klau earth touch neutral ada reading 1.5v adakah dia normal
@petrusgoel
@petrusgoel 2 жыл бұрын
Sepatutnya 0V….Sebab Neutral dan earth adalah sama punca. Walau bagaimanapun, ada kala wujud ‘beban’ dalam sistem talian yang menyebabkan adanya beza upaya seperti 1.5V itu. Ia normal. Kalau nak semak, mungkin boleh bermula dengan menyemak bacaan rintangan elektrod bumi dahulu.
@bedjack4088
@bedjack4088 Ай бұрын
Cikgu..Sy nk tanya..bila kita touch N + E ..adakah dikategorikan selamat.? Lebih² lagi Genset bergerak.sbb utk dapatkan bacaan 10ohm atau bawah 10ohm memang sukar berbekalkan rod sebatang..😅.. jadi sambungan N+E dibolehkan ke atau tidak?
@day_nien5827
@day_nien5827 3 жыл бұрын
nak tanya Tuan, apa tujuan earth dan neutral digabungkan? dan jika seperti kotak agihan dirumah adakah selamat menggunakan kaedah tersebut? sbb setahu saya kalau earth touch neutral akan trip...minta tunjuk ajar Tuan..Terima kasih
@petrusgoel
@petrusgoel 3 жыл бұрын
Jawapan dia ada dalam video saya yang ni tuan... Tuan tonton ni ya. Terima kasih. kzbin.info/www/bejne/fKrdf6qootNphZI
@day_nien5827
@day_nien5827 3 жыл бұрын
Terima kasih Tuan,atas ilmu yg di kongsi kan..ouh ya Tuan ni tenaga pengajar ka,sbb tengok video tuan macam dekat institut pengajian
@petrusgoel
@petrusgoel 3 жыл бұрын
@@day_nien5827 ya... kongsi ilmu dengan students dgn orang luar sekali.
@day_nien5827
@day_nien5827 3 жыл бұрын
Terbaik lah tuan👍
@bullohsemak8959
@bullohsemak8959 Жыл бұрын
Saya salah tngok ke . Klau separate transformer tidak di bumi . Bumi yg di cantumkan dgn neutral tidak manjadi sebagai alternative laluan kembali ke transformer
@petrusgoel
@petrusgoel Жыл бұрын
untuk eksperimen atau demo ini, saya cantumkan earth dan neutral …ya. Yang mana neutral yang disambung ke bumi adalah dari transformer manakala neutral kat busbar yang digunakan untuk tripkan RCCB adalah yang keluar dari RCCB. Ini bertujuan untuk membuat pengasingan dengan tujuan supaya RCCB boleh beroperasi apabila berlaku ketidakseimbangan arus melebihi nilai sensitiviti RCCB. Saya ada maklumkan pada awal video bahawa cantuman itu dibuat untuk simulasi ‘ideal case’ yang mana rintangan bumi 0 atau hampir 0 ohm. Konsep RCCB yang beroperasi berasaskan arus mampu menjayakan demonstrasi ini dan boleh dilihat apabila beban menggunakan arus di bawah 100mA , RCCB tidak trip dan apabila 200mA ke atas (melebihi 100mA) ia akan trip. Keputusan pengujian ini menunjukkan laluan alternatif balik ke transformer itu wujud, sebab RCCB mengesan ketidakseimbangan arus. Kalau pintasan antara E dibuat ke N yang berpunca dari transformer, RCCB tidak akan trip kerana neutral kat transformer dan E itu sama. Satu lagi, pengujian menggunakan Digital RCCB Tester juga berjaya. Konsep cantuman N dan E ini bukan asing. Ia digunakan dalam sistem TN.
@bullohsemak8959
@bullohsemak8959 Жыл бұрын
@@petrusgoel trima kasih saya sudah paham
@syanofa_pelbagai_ilmu
@syanofa_pelbagai_ilmu 3 жыл бұрын
Buat kat mna tu bos
@petrusgoel
@petrusgoel 3 жыл бұрын
Kat bengkel wiring... Poli kuching
@sundaymorning1170
@sundaymorning1170 3 жыл бұрын
Tuan. Nak tanya sikit. Ada masalah mcb trip tapi rccb tak trip. Untuk plug 13a. Mcd c32.
@petrusgoel
@petrusgoel 3 жыл бұрын
MCB Trip sebab short circuit atau overload/penggunaan arus melebihi 32A. Short circuit maksudnya L jumpa N. RCCB hanya akan trip kalau L atau N bocor ke bumi E...(L atau N bersentuhan dengan E)
@jilusanan5056
@jilusanan5056 3 жыл бұрын
Selmat pgi tuan. Saya mhu tanya kenapa wayar netuaral dan wayar earth ada bacan arus 10 volt bukankan sepatunya dia 0 volt saya guna clamp meter untk cek volt wayar 2. Harap tuan dapat membantu
@petrusgoel
@petrusgoel 3 жыл бұрын
Tuan baca arus atau voltan. Kalau voltan, memang antara Neutral dan Earth ada bacaan.... seboleh bolehnya hampir 0V. Kalau 10V, kemungkinan ada masalah rintangan elektrod bumi yang tinggi. Kalau bacaan arus, 10 Ampere pada Neutral tu normal. Kalau 10 Ampere pada E itu masalah besar. Boleh confirm kah bacaan mana satu?
@jilusanan5056
@jilusanan5056 3 жыл бұрын
Maaf tuan maksd saya 2 10ac karan bukan 10Amp tapi kadang2 pandai turun sampai 4.5ac. ada ka ini masalah wayar bumi rosak atau pun masalah rod bumi tk dpt 10 om ke bawah.
@jilusanan5056
@jilusanan5056 3 жыл бұрын
Klu dapt tuan buat viedo supaya mudah di fahami terima kasih tuan
@petrusgoel
@petrusgoel 3 жыл бұрын
@@jilusanan5056 kemungkinan ada masalah pembumian... Elektrod bumi. Nanti ada masa saya buat video
@muhammadirfanrusli4073
@muhammadirfanrusli4073 2 жыл бұрын
Jadi macam mana nak bagi rccb itu trip kalau nuetral dan bumi lampu bersentuh??
@petrusgoel
@petrusgoel 2 жыл бұрын
Kalau tiada beban lain yang disambung pada litar yang sama hidup, kemungkinan RCCB tidak trip sebab tiada pengakiran arus balik melalui neutral Yang di kongsi. Sekiranya ada beban pada litar yang sama hidup dan berlaku sentuhan antara Neutral dan Earth, RCCB mungkin akan trip sekiranya arus yang mengalir ke bumi itu lebih dari kadaran tripping RCCB. Contohnya 100mA....
@MrKIMPHY
@MrKIMPHY 3 жыл бұрын
Cikgu, kalau nak buat ujian yang sama, tapi tiada isolation transformer, apa jadi ya?
@petrusgoel
@petrusgoel 3 жыл бұрын
Kalau tiada isolation transformer boleh buat juga. Hanya bila kita buat test... nanti mungkin RCCB pada MAIN DB akan trip. Satu lagi, kita tak dapat buat simulasi Neutral disambung ke bumi.... kerana pembumian Neutral sudah dibuat di sub station.
RCCB Trip Apabila LIVE dan NEUTRAL Tidak Seimbang
19:11
Petrus Goel
Рет қаралды 10 М.
Bagaimana kahwinkan  dengan betul MAIN SWITCH & RCCB
20:32
Petrus Goel
Рет қаралды 945
УДИВИЛ ВСЕХ СВОИМ УХОДОМ!😳 #shorts
00:49
SIZE DOESN’T MATTER @benjaminjiujitsu
00:46
Natan por Aí
Рет қаралды 8 МЛН
Beat Ronaldo, Win $1,000,000
22:45
MrBeast
Рет қаралды 96 МЛН
Pengujian Pembumiaan | Earthing Tester
8:25
DIY Asal Boleh
Рет қаралды 15 М.
Wiring baru tapi bila guna beban elektrik Rccb Trip - Inspection Dan Troubleshoot
15:13
IAZ ELEKTRIK POWER ENTERPRISE IAZ ELEKTRIK
Рет қаралды 1,5 М.
Lagi Kes Trip Lambat. Ada Benda Kacau Ke?
21:55
IAZ ELEKTRIK POWER ENTERPRISE IAZ ELEKTRIK
Рет қаралды 25 М.
Pemutus litar untuk 'NEUTRAL RETURN' kenapa tidak praktikal?
9:57
Petrus Goel
Рет қаралды 1,3 М.
RCDs: Neutral - Earth Faults
11:32
John Ward (jwflame)
Рет қаралды 449 М.
PAKAR KILAT : Bila Kilat Sikit Je Pun DB Akan TRIP
22:31
MAH BAYU ENGINEERING SDN BHD
Рет қаралды 6 М.
Batal projek tebatan banjir - KEBODOHAN YANG SANGAT TIDAK BOLEH DIMAAFKAN!
11:03
NEUTRAL ADA API : TROUBLESHOOT PART 3 l AZ ELEKTRIKAL
8:52
AZ ELEKTRIKAL
Рет қаралды 28 М.
Pembumian Neutral dan Implikasi pada fungsi RCCB
31:55
Petrus Goel
Рет қаралды 8 М.
Ujian litar pintas kabel life, neutral dan ground
11:53
ABR USAHA ELEKTRIK
Рет қаралды 23 М.
УДИВИЛ ВСЕХ СВОИМ УХОДОМ!😳 #shorts
00:49