I work for a 3rd party testing company. I did infrared scans today and the electrician opening up the equipment for me dropped the cover onto the lugs inside the transformer and it tripped the panel feeding it. It also tripped the main breaker in the main electrical room. Why did a feeder panel trip the main?
@Brainfiller
@Brainfiller Жыл бұрын
Could be a couple of reasons. 1) Did the main have ground fault protection? Sometimes if it is ground fault, depending on the settings, the main may trip in addition to the feeder. 2) Higher magnitude faults can cause the instantaneous of overcurrent devices to trip. So it is possible that the current caused the feeder and the main to trip. To be sure, that would require reviewing the devices and the respective time current curves. Thanks for your comment. 3) I hope no one was hurt. That could have been disastrous. 4) NFPA 70E provides much needed guidance for safe work practices. Thanks for your comment!
@510purple
@510purple Жыл бұрын
@Brainfiller thanks for responding. Thankfully, no one was injured. As for the main breaker, I'm pretty sure it has ground fault. And that would make sense because it was more of a ground fault than a short circuit.
Coordination Studies | Determining Device Priority | Training Module 15
10:42
Brainfiller Arc Flash Training
Рет қаралды 3,7 М.
Coordination, Overcurrent Protective Devices
14:23
MikeHoltNEC
Рет қаралды 10 М.
Players push long pins through a cardboard box attempting to pop the balloon!
00:31
Чистка воды совком от денег
00:32
FD Vasya
Рет қаралды 4,9 МЛН
Миллионер | 3 - серия
36:09
Million Show
Рет қаралды 2,2 МЛН
The IMPOSSIBLE Puzzle..
00:55
Stokes Twins
Рет қаралды 199 МЛН
Variants in BTCO Starters Explained
6:26
BTCO Starters
Рет қаралды 3
Overcurrent Protection Basics | How to Set Overcurrent Elements in Protection Relays
16:02
Circuit Breaker Selective Coordination Common Questions and Misconceptions
55:22
Bentley EasyPower Software
Рет қаралды 10 М.
Protective Device Coordination The Easy Way   Part 1  Introduction to the Basics
43:16
Electrical Engineering Knowledge Sharing
Рет қаралды 803
Overcurrent, Overload, Short Circuit, and Ground Fault
6:54
Dave Gordon
Рет қаралды 924 М.
What is the Difference Between a Short Circuit and a Ground Fault?
16:18
Circuit Breaker Trip Curves Explained
19:39
Altech Corporation
Рет қаралды 58 М.
Protection Coordination of Circuit Breakers - Example Calculation
9:57
Players push long pins through a cardboard box attempting to pop the balloon!
00:31