This is the first video that mentioned the exhaust pipes. I have been trying to figure this out for 3 days and that comment did it. I have a 2 year old. Nuff said. Anyways I went to Lowe’s and bought a washing machine drain hose, hooked it up to my shop vac. And 5 minutes later I sucked out too many rocks and clumps of dirt and my furnace is running great! Thanks again!!!!
@HVACRSurvivalАй бұрын
🫣🤣👍👍 good to hear you got it figured out.
@BillyN31 Жыл бұрын
Nice! Most techs rush to say it’s a bad switch when it’s usually something that the switches are designed to prevent.
@ryanmcananey62452 жыл бұрын
Always great when the customer spends the money for top tier equipment the the install gets all hacked up. Nice fix looks a lot better
@HVACRSurvival2 жыл бұрын
Thank you!
@richardlabat5357 Жыл бұрын
Perfect video!!!!! some of these air switches has two contact - one on the front one on the back check both! On my Carrier unit the yellow jumper powered both switches - then there was a brown (signal to control board) and orange (signal to control board) two different outputs signals. Inducer housing pressure and collector box pressure (check all 3 tubing- green, black, and black square tubing vacuumed sensing signal). Blow them out (toward the inducer housing) and you can check them with a OHM meter by gently sucking on the hose and hearing them click. Make sure the hoses are good and tight - a very small vacuum leak can cause them to not work!
@williamgildea83483 жыл бұрын
Please keep the residential videos coming. You are one of the best technicians on KZbin. Every little bit helps.
@HVACRSurvival3 жыл бұрын
I wish I was, I know the brands I service best, it's the off brands and new equipment that will take me more time to figure out. But with a little time I usually get it. Thanks 4 the kind words👍👍
@wayneschneyer86993 жыл бұрын
As a retired Carrier distributor service manager I have two things to offer. The fix was a good one and kudos to you for your professionalism and ethics. Now to item two: Carrier has what is called a concentric kit that allows both pipes to exit the same hole. 4 inch hole. The exhaust goes out the middle of what looks like a cone/ funnel, and the intake air is drawn in from behind that cone. Very nice looking too. In your case, this, had you known of it, would have solved all the issues you correctly pointed out in your valuable video. When time allows you may find it worthwhile to talk to the Carrier distributor near you and get some info on this kit. I doubt, with so many hackers around, this will be the last time you and other professionals run into this issue. Also as others have correctly pointed out, the requirement is 12 inches above any anticipated snow load. Thanks again for leading the way. Wayne Schneyer
@HVACRSurvival3 жыл бұрын
Thanks Wayne, I appreciate you taking the time to watch it and leaving me a note. I myself have the concentric kit on my furnace and generally most new installs that we do would normally get one of those. I believe there was a previously installed furnace that already had been vented out. Otherwise I'd never recommend running the exhaust stacks behind the condenser like was done. Unfortunately I would have had to drill a new hole or try to saw the whole bigger to fit the concentric out and then figure a way to block off the previous two exhaust penetrations, I'm not sure that would go over well.
@StarbuckinАй бұрын
@@HVACRSurvival Why is the air intake tube going outside??? The one for my Bryant gas furnace goes up out of the furnace a short distance up and draws intake air just above the furnace INSIDE my basement.
@bikerbobcat3 жыл бұрын
Residential HVAC tech here and 5yrs in I'm not quite a 'new guy' but always so much to learn. Good video. A lot of my customers are going to youtube first to understand what is wrong with their systems. Sometimes that's bad but often it saves a lot of explaining.
@HVACRSurvival3 жыл бұрын
I try to not look like a DIY channel but most of the time it's the same stupid things wrong over n over. I appreciate you watching!
@charleschambers14033 жыл бұрын
I’ve had this issue in a unit for 3 days straight thanks for the tips
@HVACRSurvival3 жыл бұрын
Your welcome👍👍
@britishsterling49772 жыл бұрын
thanks buddy...5am here and the windchill is -10F furnace has been out for hours watched your video and i had it back up and running within 30 minutes of watching your video
@HVACRSurvival2 жыл бұрын
Cool, just been sure to check it for all the heat exchanger problems there known for.
@chartmaster54403 жыл бұрын
Thanks for your videos helped me fix my error 31 on my carrier
@HVACRSurvival3 жыл бұрын
Awesome!
@tonydelgrego29063 жыл бұрын
Good solution on what you had to work with. Stay Safe
@HVACRSurvival3 жыл бұрын
It was a losing battle. I still wasn't happy with the pipes that high or far apart. But that was a install screw up but I didn't want to say that in the video.
@Eddy633 жыл бұрын
Nice repair Rick ... In the snow ...
@larrydurkee57413 жыл бұрын
When we used to install the Carrier furnaces here in Ontario the requirement was 12” above the highest expected snow level and 12” of separation between inlet and outlet. There was only two acceptable terminations, two pipe as described above and concentric. Not sure that has changed. Also anything that include risers above the snow had to be insulated. I remember getting tagged by the inspector at the time for less than 12” between. Made me fix it before unlocking the meter (new install).
@adamradley44073 жыл бұрын
Yes here in ontario 12" min between fresh air and exhaust if under 100kbtu. Over 100kbtu its 3". 12" above expected snow fall and usually around 3" outdoor vent before you have to insulate it. It is usually in the manual as different makes and btu values have different requirements. As far as the ones in this video I can definitely see it recirculating depending on wind which will shut it down. Also exhausting near/ below ac is a no no. Condensation and ice will build up on the unit. Personally our dispatchers send the home owners to check venting before we are sent out. Saves us those snow in boots situations lol
@larrydurkee57413 жыл бұрын
@@adamradley4407 thanks. It has been years since I have installed one. Put a two stage in my house in 2013. Love it. Have had to replace the inducer motor, not a failure but got very noisy, could hear it upstairs. Other than that it has been great. Did you mean three feet before insulation? I used to have to hate insulating them. Put one out under a deck and extended it the width of the deck, insulated with 1/2” Armaflex.
@HVACRSurvival3 жыл бұрын
Running pipes a long distance outside under a deck in northern climates would likely result in the exhaust pipe accumulating ice build up inside the pipe and eventually restricting it enough to cause pressure switch lockout.
@adamradley44073 жыл бұрын
@@HVACRSurvival we have run up to ~15' of 2" vent hooked up to 70-90 kbtu furnace without an issue but you really have to make sure you are sloped well and fully insulated. I have run close to 30' of 3" through an unheated garage on a 110kbtu successfully. Granted it is not ideal to run long lengths outside but sometimes it is the lesser of the evils ;) Make sure it is well insulated and sloped very well.
@TechnicalLee3 жыл бұрын
Good fix, much better than before. One thing I would have done is make the intake shorter than the exhaust by 6-12". That way you won't get recirculation even with a lot of horizontal wind since heat rises, it will go over the top of the intake.
@wayneschneyer86993 жыл бұрын
Absolutely buddy, I hear that. I just didn’t know if you were either a Carrier dealer or knew about the kit. We need guys like you out there doing the wonderful work and sharing the right information to the rest. A lot of guy seem to follow you as well as learning the right way. Great job and a lot of responsibility to keep up and improve the image and public perception of our trade. Wayne Schneyer
@HVACRSurvival Жыл бұрын
Sorry I didn't respond sooner, sometimes reply's get hidden. Thanks for the supportive words!
@christiansommer9143 жыл бұрын
Sweet video as always. Glad all the snow here is gone, man that snow can ruin your hole day sometimes.
@HVACRSurvival3 жыл бұрын
The snow is still here🤣. Thanks 4 checking it out!
@SOLOOJESUCRISTO3 жыл бұрын
Be blessed, thanks you for teaching me for Freeeeeeeeee...................................
@HVACRSurvival3 жыл бұрын
I've been very blessed, your more than welcome, I'm just glad your getting something from these videos.
@HVACUncensored3 жыл бұрын
Finally catching up on some videos. Good work Rick. Keep kicking ass with the videos brother.
@jakewesley6404 Жыл бұрын
Loved the video. Im looking at a carrier weathermaker 9200 uhe with similar symptoms. Comes on for 1 to 5 minutes shuts off. Blower is not turning on but duct by heat exchange gets fire hot. Then it trips. Im assuming its the capictor or the blower motor. Great vid!
@HVACGUY3 жыл бұрын
Thanks for the videos. We still don’t see many of those down here.
@KadirYildiran3 жыл бұрын
nice work Rick👍👍 As always ... professional💪💪
@Ted_E_Bear3 жыл бұрын
Rick is on the way to save the day. !
@HVACRSurvival3 жыл бұрын
🙈😂
@WRP036082 жыл бұрын
Thanks for this helpful tutorial.
@HVACRSurvival2 жыл бұрын
Glad it was helpful!
@Atekcs Жыл бұрын
2 Questions- 1. Why did you move the exhaust and intake pipes closer together? 2. Why were you considering installing a "T" ?
@HVACRSurvival Жыл бұрын
They are less likely to recirculate when they are closer together, also a tea causes it to linger around the air intake and potentially recirculate. I almost never use a tee, sometimes a tee will help keep winds from being driven directly back into the pipe, this would happen more when you have winds coming from a particular direction like from the West for my area.
@Atekcs Жыл бұрын
@@HVACRSurvival Gotcha. Thanks for the explanation.
@neilvestervictor1803 жыл бұрын
polishing the tud great work Rick
@HVACRSurvival3 жыл бұрын
You caught that🤣👍👍
@neilvestervictor1803 жыл бұрын
it's a pleasure watching you guys get the job hopefully I will be advancing my self too
@HVACRSurvival3 жыл бұрын
@@neilvestervictor180 Everyday is a new day and a chance to be a better you.
@neilvestervictor1803 жыл бұрын
it's been a year working on the chill water system now I run it by my self now taking care of the fan coils and mortuary walk in freezer and walk in cooler
@HVACRSurvival3 жыл бұрын
@@neilvestervictor180 it all comes with time. Keep it up man👍👍
@hartsfire57063 жыл бұрын
that looks really good for what you have to work with.
@HVACRSurvival3 жыл бұрын
Hopefully I was able to express this is not what I wanted but there was only so much I could do with it. That's why I teeter tottered on what to do. There was no good remedy.
@hartsfire57063 жыл бұрын
@@HVACRSurvival i got a good laugh about deep snow. i am in central PA and my horses have snow to there belly's in the fare pastor and yet love to play in it.
@donnierobertson30883 жыл бұрын
Great job and video like always
@HVACRSurvival3 жыл бұрын
I appreciate you watching and commenting, it's hearing my videos are useful that helps drive me to continue. Thanks 4 the support!
@mikemc7540 Жыл бұрын
Thanks for great videos.
@HVACRSurvival Жыл бұрын
Holy cow Mike! Thank you! I really appreciate that you appreciate my videos🤜🤛👍👍
@chrisrouleau6933 жыл бұрын
Nice clean repair
@HVACRSurvival3 жыл бұрын
Thanks Chris👍👍
@tuffram21653 жыл бұрын
I highly recommend just coming straight out and doing a slash cut on them like a 45° angle cut but I guess with the snow line you can't do that up North.
@HVACRSurvival3 жыл бұрын
I used to do the 45° angle cut on the Lennox Furnaces more than anything. It really depends on what height it comes out at whether or not you have to do a riser like that. Normally I don't need to do that riser.
@gregbowman35983 жыл бұрын
Good one Rick 👍
@hvacir91763 жыл бұрын
nicely done as always, thanks for the video
@RJMaker3 жыл бұрын
Much better, Thanks for the video... No concerns with corroding the condensing unit on a not so windy day?
@HVACRSurvival3 жыл бұрын
That's why I raised the stacks to attempt to avoid that. This was a bad location of the stacks with no good choices. I just made the best of it.
@jeffreysettles8280 Жыл бұрын
What's your advice or opinion about condensation when you have the exhaust Line running up through the roof on a two-story house.
@HVACRSurvival Жыл бұрын
What do you mean? is it leaking?
@wd85573 жыл бұрын
Some city's in Michigan want your exhaust with a 90 on it.
@HVACRSurvival3 жыл бұрын
We only 90 down for air intake. You're saying they want you to 90 down for exhaust? I've never seen that in any install manual but of course I've only done Lennox, Rheam and Carrier
@wd85573 жыл бұрын
@@HVACRSurvival Doesn't matter what brand it is, they want it 90 down. The city of Livonia hit me on that and they want it glued. I'll do it then come back after it passes inspection and re-do it.
@gocubsgo50553 жыл бұрын
Hardest furnace to do maintenance on. Still not a fan of their trap and getting burners out to clean when exhaust runs through the furnace.
@HVACRSurvival3 жыл бұрын
The trap was changed a couple years ago, just remove a 1/4 screw and pull it out.
@gocubsgo50553 жыл бұрын
@@HVACRSurvival yea the model you're on the hose clamps are a pain. The trap needs hose from inducer and collector box removed to either blow through or remove it completely to clean. I've had it to where I blew through inducer hose only to clear it and it was still plugged on collector box side, theres a divider inside of the trap. New carrier models trap is a bit better but still not easy to remove and deal with their clamps.
@HVACRSurvival3 жыл бұрын
@@gocubsgo5055 the key is a good pair of square headed linesman with the grip to hold the clamp.
@kevinsklow34733 жыл бұрын
Great video! Since I’m newer at HVAC, I had to wonder why you mentioned running both those pipes closer together... wouldn’t that be more of an opportunity for the intake to pull in exhaust as opposed to having them further apart?
@HVACRSurvival3 жыл бұрын
You would think that further apart would be better but it's not. Think of how concentric kit works, the intake is right behind the exhaust. It was more of a issue with certain furnaces. The worst use to be the Lennox Pulse for this but with the current draft motor design furnaces it's not as bad but shows up when it gets too single digit temps. The hot gas exhaust can frost closed the intake.
@kevinsklow34733 жыл бұрын
@@HVACRSurvival thanks for the feedback, I appreciate it. Seems like the concentric kits are more for difficult installs or aesthetics... trying to take every opportunity to learn the right way. Lotta hackery out there
@HVACRSurvival3 жыл бұрын
@@kevinsklow3473 you'll learn the most as you screw up. Most things I point out or stress is things I got burnt on / callback 😁.
@Firefighter_-uc5ns2 жыл бұрын
At 2:15 you pulled the black tube off and felt for vacuum. I did that one unit flashing code 3-1 and went to feel it I don't have much vacuum on the line even after it's pulled off but the system let the valve and ignitor ignite and start operating. What is my next step? What needs replaced? What is the actual problem here? Thank you in advance
@pip123111 Жыл бұрын
Hey did you every figure this out
@craighvac18083 жыл бұрын
Do the vents being closer together make a difference even with proper terminations?
@HVACRSurvival3 жыл бұрын
You less likely to get recirculation with them closer.
@craighvac18083 жыл бұрын
@@HVACRSurvival ah makes sense, I always wondered why..dont do many resi installs
@TechnicalLee3 жыл бұрын
Closer also means they're in the same pressure zone and less likely to trip pressure switches during wind gusts.
@HVACRSurvival Жыл бұрын
@@fukashima6586 Without showing you its hard to describe. It just works
@hank68872 жыл бұрын
I'm a service technician, I've racked my brains half the day on a 58mxa120-f-15120, the problem I'm having is the cfm is not coming on for call for heat only when I pull wire off vacuum switch it comes then I put it back on and it goes through heating cycle like normal until its satisfied and won't work as normal , I've already changed the board . Any help would be greatly appreciated. Thanks
@HVACRSurvival2 жыл бұрын
You said your working on a 58mx furnace yet you cant get the CFM to come on? Condenser fan motor?
@hank68872 жыл бұрын
Yep only when I pull wire off vacuum switch briefly then it comes and I put it back on ,and it goes into heat sequence, first time I've been on this machine at this location. In missing something. Thanks
@hank68872 жыл бұрын
Combustion fan motor, is what I'm calling cfm , thanks
@hank68872 жыл бұрын
Or induced draft motor ,
@HVACRSurvival2 жыл бұрын
@@hank6887 email me what you checked so far. hvacrsurvival@gmail.com
@dean358310 ай бұрын
The pipe needs to have a strap every 6' or less to hold it up, not just glue and hope it will hold up. Just a personal opinion
@HernanAnzola3 жыл бұрын
Hi! Do you know where I can buy used hvac tools online?
@HVACRSurvival3 жыл бұрын
eBay and Facebook Marketplace
@KG-yn9qi3 жыл бұрын
So why would you want the intake next to the exhaust? Seems you would want them apart from each other!
@HVACRSurvival3 жыл бұрын
Recirculation happens when it's further apart. there's a buffer area where you want to be, best to be close together when properly vented or a large distance apart but usually in the same pressure zone. as always follow the owner's manual and do like they ask. I've experienced this first hand
@TechnicalLee3 жыл бұрын
Having them close together in the same pressure zone makes it less likely that the wind will trip the pressure switch on a windy day since they will experience the wind gust equally. If the pipes are further apart a wind gust may produce different pressures in the pipes and cause issues.
@RayRay-nb7tn3 жыл бұрын
I thought in the installation instructions its suppose to be a minimum of 6in and a max of 12in apart center to center? That pitch is incorrect also.
@HVACRSurvival3 жыл бұрын
Sounds right to me. There wasn't much more I could do😒
@RayRay-nb7tn3 жыл бұрын
Understandable if you are limited to what you can do, you just do your best. I like how you talk through the call. It gives us subs an idea or young techs what to think about when working through the call. IMO you should continue to do this on all videos. You do a great jobso just keep doing what you are doing. See you tonight on the show. If she is up to it please bring your biggest supporter tonight, The Young Flute Lady. Lolol
@throttlebottle59063 жыл бұрын
that was a lot of standard elbows in total, maybe hitting length limits and the snorkels should be strapped to the wall =p as should have the original ones, regardless of the whizz-poor gluing job. a strap would have kept if from flopping over. I could see there being a wind induced issue with the terminations further apart, in combination with the condenser blocking/guiding wind. you were dealt a bad hand for sure
@mikegirard43883 жыл бұрын
Elbows are standard, not sweeps. They are allowed by have 2x the equivalent feet. Might check total equivalent feet to install manual.
@HVACRSurvival3 жыл бұрын
I'll definatlty check that if she starts having lockouts. 🙈 I forgot to check the book....they had more elbows then what's normally needed.
@CognitiveDisonance2 жыл бұрын
What is the purpose of the Tee?
@HVACRSurvival2 жыл бұрын
I assume you're talking about the pressure switch test that I might have done? (It's been a while since I've seen the video.) If it was for the pressure switch, if it was, then It was me to monitor it accurately while it's in the circuit.
@CognitiveDisonance2 жыл бұрын
@@HVACRSurvival Thank you for your reply. However the component I was asking about is the Tee on the outside of the building. What is it's purpose -- why not simply terminate outside the building with a straight piece of pipe, or an elbow?
@HVACRSurvival2 жыл бұрын
@@CognitiveDisonance I went through and watched the video "completely"without fast forwarding. I mentioned why I used the tee and it was noted in the title.
@CognitiveDisonance2 жыл бұрын
@@HVACRSurvival I dont know how I could have missed that. Thank you again -- I appreciate you taking the time, and effort, and your willingness to help :)
@ThePeavey233 жыл бұрын
The secondary heat exchanger is on its way out.. watch out for the smell
@Jon-hx7pe3 жыл бұрын
it may not be, could fail this season or last years.
@HVACRSurvival3 жыл бұрын
I have been seeing most failing around 2002-2005 or older, that's 15-16 years, things wear out. My only complaint is building the heat exchanger, if it were assembled like the new version or most any other brand. That's what takes the most time.
@Jon-hx7pe3 жыл бұрын
@@HVACRSurvival in my view, if any heat exchanger makes it to 20, it's a success.
@HVACRSurvival3 жыл бұрын
@@Jon-hx7pe i agree👍
@j.d.62213 жыл бұрын
Some sloppy installation there, con any do what you can do; great work Rick!
@HVACRSurvival3 жыл бұрын
I think the furnace was a change out that was reconnected to existing exhaust pipes and ductwork.
@timliu26083 ай бұрын
how about code 33?
@HVACRSurvival3 ай бұрын
It’s usually down there on the door. Pressure switch or limit switch trip generally, I can’t remember which one it is off top of my head.
@bama539 Жыл бұрын
Another great system but bad install. They should have had the PVC in concentric or closer together. How on earth did they get away with this work.