In this case, the supply pipes from each boiler were cold and the return pipes to each boiler were warm. We thought for sure it was something common to both boilers like an air pocket.
Пікірлер: 26
@royvoorberg71656 ай бұрын
Yup, an other simple failure that was a BIG head ache. Well done.
@boilerroomdetective6 ай бұрын
Thanks I never thought both would be frozen
@dougoest30566 ай бұрын
Great catch Ray. Pesky check valve built into the pump is almost unnoticeable!
@boilerroomdetective6 ай бұрын
It caught me off guard I never saw both do that before. Happy New year Doug
@nethoncho6 ай бұрын
Thanks for your weekly videos
@boilerroomdetective6 ай бұрын
Most welcome Thanks for watching
@josephlomeo34356 ай бұрын
Great video. Happy New Year.
@boilerroomdetective6 ай бұрын
Thanks You too
@Raphael_NYC6 ай бұрын
Well done. Love this. Thank you. raphael nyc
@boilerroomdetective6 ай бұрын
Thanks I appreciate it
@jamestamu836 ай бұрын
Good catch for a sneaky problem. At our facility we've plumbed the air vent discharge lines down to a floor drain. Once had a vent stick open and we sprayed chilled water all over the mechanical room. That install is CLEAN, by the way. Someone took care to install it properly.
@boilerroomdetective6 ай бұрын
Yikes that would make a mess
@mattstiglic6 ай бұрын
Those damn plastic IFC inserts man. Theyre a godsend when you need one, and a pain in the ass when they go bad. Cheers from one boiler guy to another.
@boilerroomdetective6 ай бұрын
It was a lesson I will never forget Thanks
@CommercialGasEngineerVideos6 ай бұрын
Cool channel. There's some good content out there but it's finding it which is tricky. Then it's trying to find the time to watch it. Keep up the good work. Happy new year
@boilerroomdetective6 ай бұрын
Thank you very much Happy New year to you as well
@l.crossjr6 ай бұрын
I purchased several of your books. These videos make the information sink in really well. Great content
@boilerroomdetective6 ай бұрын
Thank you very much I appreciate it
@VictorHernandezBlueprint6 ай бұрын
Yes. Those internal checks are not as good as regular individual check vales. Glad you figure that case out!
@boilerroomdetective6 ай бұрын
I learned that on this one Thanks
@boby1156 ай бұрын
Great catch Ray 👍. Now let’s go a step further and look at some unrelated issues. At 2:45 of your video , did anyone catch the venting problem? (If so, what’s the problem?). Did anyone notice the way the boiler’s gas piping was installed ? (If so, what’s the problem?) . Always great to watch your videos , keep up the great work. And let’s see if we get some answers on my questions (?) 🤔
@boilerroomdetective6 ай бұрын
I did catch the flue inside the flue I was concerned but saw they installed the flue inside the larger pipe Weird I know
@angrybeavers11756 ай бұрын
Might as well change that vertical mounted circulator too since they can't be installed with the motor up and it will go bad.
@boilerroomdetective6 ай бұрын
Thanks I will look into it
@Shawn_RHVAC6 ай бұрын
The circulators with check valves suck!! Always fail