CENTRIFUGAL CHILLER IS SURGING. SHOWING HOW TO PERFORM OIL FILTER REPLACEMENT ON RTHD.

  Рет қаралды 5,848

Jason Johnson

Jason Johnson

Күн бұрын

Пікірлер: 21
@Nighthawke70
@Nighthawke70 7 ай бұрын
The thing about huge chillers, during cold starts like this, there will be some surging. I watched a clip of a 950 Ton Trane Centravac centrifugal that's older than you and me put together start up after a long winters nap and annual, and it was surging like a SOB. It took awhile, but it settled into a stable state and everyone was happy. The turbine on it is as big as most jet engine intakes!
@petersmart1999
@petersmart1999 7 ай бұрын
Man,for years all I had was the Carrier 23xl/ 250 ton,6 in one bldg and 4 in another.You could not talk anywhere near the chiller room,they were sooooooo loud! Thx for the video
@jasonjohnsonHVAC
@jasonjohnsonHVAC 7 ай бұрын
That RTHD is pretty loud.....but not as loud as the RTHB. Any screws are loud as hell. Centrifugals are thankfully much quieter.
@Eddy63
@Eddy63 7 ай бұрын
Interesting vid JJ ... Thx
@jasonjohnsonHVAC
@jasonjohnsonHVAC 7 ай бұрын
It was interesting. In my happy place around chillers
@Android_Warrior
@Android_Warrior 7 ай бұрын
Just sign up for my HVAC school today, 12 weeks, wish me luck. 🤞🤞🤞🤞
@Nighthawke70
@Nighthawke70 7 ай бұрын
You need a TON more than that to set foot into a chiller. Your first jobs will be installing ducting.
@jasonjohnsonHVAC
@jasonjohnsonHVAC 7 ай бұрын
I wish you good luck and much success
@Android_Warrior
@Android_Warrior 7 ай бұрын
@@Nighthawke70 : But without school I'll go nowhere. Thanks for the heads up.
@Nighthawke70
@Nighthawke70 7 ай бұрын
@Android_Warrior I took two years at a technical college, got my universal and IMACA refrigerant usage cards, and they wanted to put my overweight butt up in attics to do ductwork, at best.
@Elruido702
@Elruido702 7 ай бұрын
I just finished a 12 month program I'm hoping not to start off as an installer everyones been saying that's where I'll start 😢
@subcoolHVAC
@subcoolHVAC 7 ай бұрын
Nice job burping that big boy! 🫧👊 Keep em coming 👍
@jasonjohnsonHVAC
@jasonjohnsonHVAC 7 ай бұрын
It still needs some work and it was struggling all day. It's quite humid here so she's struggling to make a dent on the building. Ended up shutting her down and firing up the other centrifugal after she started surging like 5 hours later. Thanks for the comment
@subcoolHVAC
@subcoolHVAC 7 ай бұрын
@@jasonjohnsonHVAC I’ve seen them take a few days here, have to deal with high humidity too
@NROhvac
@NROhvac 7 ай бұрын
Good work
@jasonjohnsonHVAC
@jasonjohnsonHVAC 7 ай бұрын
Appreciate the comment
@nick29766
@nick29766 7 ай бұрын
This is the same chiller that HVACTIME had a serge and trip the power.
@jasonjohnsonHVAC
@jasonjohnsonHVAC 7 ай бұрын
Yes sir. I work for the same company
@KeithSnyder-qc7in
@KeithSnyder-qc7in 6 ай бұрын
First you need to take the purge out of adaptive. Dumbest thing ever. 7 psi at 27% should of told you that there was air in the machine. Oil pressure is extremely low for a Trane machine. Yeah surging, adaptive mode calculates how long and when it should run. Auto mode starts the purge when the machine runs. Adaptive mode was thought for electrical efficiency. Dumd idea.
Oil System YK York Chiller
16:54
HVACTIME
Рет қаралды 18 М.
Lazy days…
00:24
Anwar Jibawi
Рет қаралды 9 МЛН
The Best Band 😅 #toshleh #viralshort
00:11
Toshleh
Рет қаралды 19 МЛН
Engineers Test the Most Popular Oil Filters
14:09
Brand Ranks
Рет қаралды 379 М.
TRANE RTAC Chiller compressor oil filter replacement
3:02
HVAC Tips&Tricks
Рет қаралды 11 М.
Trane CVHE Chiller Overhaul Rebuild
3:28
Thermetrics Corp
Рет қаралды 50 М.
Chiller Shaft Seal Repair on York YK Centrifugal
15:50
HVACTIME
Рет қаралды 35 М.
Mastering Trane Chillers: High Condenser Pressure
8:59
THE CHILLER GUYS HUB
Рет қаралды 3,5 М.
Trane Chiller Compressor Teardown Part 1
6:11
HVACTIME
Рет қаралды 14 М.
Chiller Surging During Centrifugal Chiller PM
14:19
HVACTIME
Рет қаралды 22 М.
Lazy days…
00:24
Anwar Jibawi
Рет қаралды 9 МЛН