Conductor Insulation, NEC 2020 - [310.4], (19min:06sec)

  Рет қаралды 17,302

MikeHoltNEC

MikeHoltNEC

3 жыл бұрын

Factors that impact conductor sizing include not only conductor ampacity and equipment terminal temperature rating, but also the conductor insulation temperature rating. In this video we discuss Table 310.4(A) which provides information on conductor insulation properties such as letter type, maximum operating temperature, application, insulation, and outer cover properties.
This video is an extract from Mike Holt’s Electrical Calculations Training Library, based on the 2020 NEC. For more information about this product visit www.MikeHolt.com/examprep or call 888.632.2633.
For over 40 years, Mike Holt Enterprises has been providing quality electrical code training to help electrical professionals learn the Code, prepare for exams, and improve their electrical knowledge. Visit www.MikeHolt.com for exam preparation tips and training, instructor and curriculum support, continuing education options, free videos and graphics, and so much more.

Пікірлер: 23
@buddy6819
@buddy6819 3 жыл бұрын
Thanks so much Sir Mike Holt, be safe always, God bless
@MikeHoltNEC
@MikeHoltNEC 3 жыл бұрын
Thank you!
@davidredpath4781
@davidredpath4781 3 жыл бұрын
Awesome, Mike! Thank you!
@MikeHoltNEC
@MikeHoltNEC 3 жыл бұрын
My pleasure!
@abdullaalmamun7102
@abdullaalmamun7102 3 жыл бұрын
Thank you so much Sir great full video sharing for us. It is very helpful learning points NEC 2020
@pauloconnell7668
@pauloconnell7668 3 жыл бұрын
Mike, Hard and Extra Hard usage-Think construction sites also.
@trespire
@trespire 3 жыл бұрын
In metal work shops / manufacturing, flex cable doesn't hold up very well. Stepped on by work boots with metal chips in the soles, sheet metal scrap on the floors are like knives.
@victorco.6308
@victorco.6308 3 жыл бұрын
Very informative
@MikeHoltNEC
@MikeHoltNEC 3 жыл бұрын
Glad you think so!
@trilliondollarmogul5978
@trilliondollarmogul5978 3 жыл бұрын
The next generation.
@peterdiamond5677
@peterdiamond5677 3 жыл бұрын
What is ampacity rating of #12 AWG Copper THWN-2 at 60 Degrees Celsius?
@MikeHoltNEC
@MikeHoltNEC 3 жыл бұрын
See Table 310.16 in the 2020 NEC or Table 310.15(B)(16) in the other Code books.
@peterdiamond5677
@peterdiamond5677 3 жыл бұрын
@@MikeHoltNEC I see the ampacity rating of #12 AWG Copper THWN-2 in 310.16 under 90 Degrees Celsius ONLY?
@MikeHoltNEC
@MikeHoltNEC 3 жыл бұрын
Watch - kzbin.info/www/bejne/hX2seXifnr6SiNU
@vivianledonghae4eify
@vivianledonghae4eify 8 ай бұрын
🤯🤯🤯🤯
@ecospider5
@ecospider5 3 жыл бұрын
The statements on the nylon jacket was not clear. It sounded like if the nylon cover came off when pulling it that was ok. How can that be if when you enter a box you have to have the nylon cover enter the box a certain distance. This statement could have used some more clarification.
@MikeHoltNEC
@MikeHoltNEC 3 жыл бұрын
The nylon jacket is 'not' insulation, so if it gets damage or comes off, that is fine.
@carultch
@carultch 3 жыл бұрын
For the most common applications, it is OK if the nylon jacket comes off during the pull. The nylon will absorb the wear and tear, so the insulation beneath it remains intact. It also reduces the friction, from what it would be, if the PVC insulation were the only layer surrounding the conductor. In applications where you need protection from gasoline, oil and chemicals, that is where you need to be careful not to damage the nylon jacket.
@ecospider5
@ecospider5 3 жыл бұрын
That makes it sound like if you are going just a couple feet inside of a 2x4 wall you don’t actually need to use romex. You can just put in individual wires. White, black, and copper. Am I understanding this right or am I not understanding what the nylon jacket is.
@carultch
@carultch 3 жыл бұрын
​@@ecospider5 It's a different kind of jacket, than the jacket that is on Romex. Individual conductors are typically required to be in a raceway or enclosure, unless otherwise permitted in the NEC. The nylon jacket on THWN-2 is very thin, and does not serve the same purpose as the jacket on a multiconductor cable.
@MikeHoltNEC
@MikeHoltNEC 3 жыл бұрын
@@ecospider5 you can't run wires without being installed in a raceway or cable, see NEC 300.3(A).
Branch Circuit, Multiwire, NEC 2020 - [210.4], (19min:38sec)
19:38
MikeHoltNEC
Рет қаралды 233 М.
ИРИНА КАЙРАТОВНА - АЙДАХАР (БЕКА) [MV]
02:51
ГОСТ ENTERTAINMENT
Рет қаралды 9 МЛН
FOOLED THE GUARD🤢
00:54
INO
Рет қаралды 63 МЛН
Sigma Girl Past #funny #sigma #viral
00:20
CRAZY GREAPA
Рет қаралды 30 МЛН
MEU IRMÃO FICOU FAMOSO
00:52
Matheus Kriwat
Рет қаралды 42 МЛН
Why Knowing WIRE INSULATION Types Is Crucial
10:16
Electrician U
Рет қаралды 203 М.
Grounding, System and Equipment [250.4, 2020 NEC]
33:35
MikeHoltNEC
Рет қаралды 100 М.
Air Conditioners and the National Electrical Code (NEC)
22:58
Ryan Jackson
Рет қаралды 29 М.
Grounding Versus Bonding (26min:26sec)
26:26
MikeHoltNEC
Рет қаралды 245 М.
Choosing the Right Spark Plug Wires Based on OHMS of Resistance
20:20
Muscle Car Solutions
Рет қаралды 9 М.
Current carrying conductors in the 2020 NEC
22:04
Ryan Jackson
Рет қаралды 37 М.
Neutral-to-Earth Voltage (NEV), NEC 2020, (44min:40sec)
44:40
MikeHoltNEC
Рет қаралды 215 М.
How To Use The NEC, NEC 2020, (29min:15sec)
29:15
MikeHoltNEC
Рет қаралды 156 М.
ИРИНА КАЙРАТОВНА - АЙДАХАР (БЕКА) [MV]
02:51
ГОСТ ENTERTAINMENT
Рет қаралды 9 МЛН