Configuring Danfoss VLT HVAC Basic FC-101 for Air handling unit (AHU) and FAN Application
1-01 MOTOR CONTROL PRINCIPAL [0] U/f
1-20 MOTOR kW AS PER MOTOR NAME PLATE
1-22 MOTOR VOLTAGE AS PER MOTOR NAME PLATE
1-23 MOTOR FREQUENCY AS PER MOTOR NAME PLATE
1-24 MOTOR CURRENT AS PER MOTOR NAME PLATE
1-25 MOTOR RPM AS PER MOTOR NAME PLATE
3-15 REFERENCE RESOURCE 1 AS PER REQUIREMENT
3-16 REFERENCE RESOURCE 2 0
3-41 ACCELERATION TIME 40
3-42 DECELERATION TIME 60
4-12 MOTOR SPEED LOW LIMIT 0 Hz
4-14 MOTOR SPEED HIGH LIMIT 50 Hz
5-10 TERMINAL 18 DIGITAL INPUT [8] START
5-11 TERMINAL 19 DIGITAL INPUT NO OPERATION
5-12 TERMINAL 27 DIGITAL INPUT NO OPERATION
5-13 TERMINAL 29 DIGITAL INPUT NO OPERATION
5-40 FUNCTION RELAY 0 [ 5 ] RUN
1 [ 9 ] ALARM