Cooling Tower Setpoint For Chiller

  Рет қаралды 39,294

HVACTIME

HVACTIME

Күн бұрын

Пікірлер: 45
@HVACTIME
@HVACTIME 7 ай бұрын
chilleracademy.com/p/intro-to-chillers Get support today.
@antonkorolev8059
@antonkorolev8059 Ай бұрын
Thank you so much for your videos! While I was watching, I also thought to calculate the lowest due point of mix air temperature in all the AHUs by measuring mixed air temperature and mixed air humidity, then reset the chiller’s chilled water supply temperature based on that say 5-7 degrees lower, so not to run the chiller at 42 and below when not needed when tryin dehum the space
@mikee2923
@mikee2923 3 жыл бұрын
Excellent explanation. You’re on top of your game. I live in the rust belt and this sounds like a good idea up this way since our temperatures usually cool off at night. I don’t do much chiller work anymore and when I did it was usually in large retail stores that mostly had water cooled screw chillers. The issue I mainly had was getting them started in the morning when the tower water had cooled off overnight when the chiller had shut down. They usually had tower bypass valves that would recirculate condenser water until it warmed up then would start pushing the water out to the tower as it warmed. However they rarely worked because the energy management company didn’t understand how these chillers operated. They usually only installed the condenser water temperature sensor on the outlet of the condenser to the tower and controlled the bypass valve and tower fan off this one sensor. I fought with them for a couple years trying to explain to them why I had to make rounds on an almost daily basis resetting the chiller at multiple locations due to this. They didn’t want to hear they were wrong. As you could probably guess they would see a high temperature on the condenser loop from their 1 sensor, turn on the tower fan and close off the bypass valve and dump a lot of cold water into the condenser which would cause it to fail on oil pressure. At 1 location I experimented and switched their strap on sensor to the water inlet which somewhat improved things by at least sensing the cold water from the tower sump would turn the fan off and begin to recirculate water again until the loop temperature stabilized. Couldn’t convince them to add a sensor to the tower sump to control the fan and relocate the sensor as I did to control the bypass from that. So I just continued to do my daily route to reset the chillers until we eventually lost the contract. It was easy money while it lasted. I pass by one of the stores I used to take care of often and rarely see the cooling tower fans running on a 90 degree day. I guess they showed me👍
@santoscruz8
@santoscruz8 Жыл бұрын
I want to say, thanks for your input and may God bless you and your families.
@joshstevens9826
@joshstevens9826 2 жыл бұрын
The tower sp at 80-85° is a decent rule of thumb. The true answer is the manufacturer spec. The carrier 19xrv, under low load situations in mild weather, are looking for 60-65° condenser water. Also the york mc2 likes low condenser water temps. Know your equipment before making changes.
@antonkorolev8059
@antonkorolev8059 Ай бұрын
Good point. But then you can still reset the SP based on the WB-T, but just that wiggle room - “from - to” would be based on the manufacturer’s recommendations
@edwardcrane7520
@edwardcrane7520 Ай бұрын
Excellent video 👏👏👏
@sergiodjf
@sergiodjf 2 жыл бұрын
Great explanation & visual animations!💯👏 For lift control, you should control both condenser water temperature & water flow. All chillers have min & max flow and you can adjust those parameters for peak performance.
@jarredallen
@jarredallen 3 жыл бұрын
I have experienced many centrifugal chiller plant with fouled up condenser tube. I always advice my customers engineering and chiller plant operator to monitor condenser leaving temperature versus condenser saturation temperature. if the difference is greater than 10 fahrenheit, its time to punch the condenser tubes. and I also detest recycled water for cooling tower use.
@HVACTIME
@HVACTIME 3 жыл бұрын
Approach will give you the most accurate/earliest determination of fouled tubes. And approach isnt as subjective to chiller load like differential is
@nakiapringley5391
@nakiapringley5391 Жыл бұрын
Great video brother 💯💯
@neilvestervictor180
@neilvestervictor180 3 жыл бұрын
great information
@mwdub02
@mwdub02 3 жыл бұрын
You’re the man!
@olol3765
@olol3765 Жыл бұрын
20years ago received a new building and i tried to explain to engineer this issue he would admit, especially in GTA in April
@greghawkins7317
@greghawkins7317 3 жыл бұрын
The York ymc2 chillers can run inverted. Had our 800ton ymc2 running with a 45 degree leaving chilled water temp and a 42 degree entering condensing water temp.
@robertpeters9438
@robertpeters9438 2 жыл бұрын
All the heat energy of the loop plus the power used by the chiller and tower must be rejected by the tower. The most efficient might be a giant coil, but completely impractical. So, we use enormous surface area in the droplets of a cooling tower to exchange heat with the added bonus of cooling from evaporation of part of the water. It is a tradeoff as to how big the pond or tower must be vs energy used in the spray and moving air through the field of the spray. Now, the chiller/compressor must raise the water temperature high enough that the water spray or waterfall can reject the total heat of the combined system. Many factors such as cost of electricity, cost of space for a pond, cost of maintenance on various system components all factor into the optimization of initial cost vs operational and maintenance costs.
@stlbrian33
@stlbrian33 2 жыл бұрын
Great video.
@thomascrane8130
@thomascrane8130 Жыл бұрын
What temperature outside should we not run a chiller? If it is used for cooling only? And what temp of the return air should it be before cooling enabled please
@elderfarmstead
@elderfarmstead 3 жыл бұрын
Great info! Thanks.
@nakiapringley5391
@nakiapringley5391 Жыл бұрын
Great video! Can those rule of thumbs set points be used on other air cooled chillers? Please keep videos coming as I am just getting into centripetal chillers.
@hvac8826
@hvac8826 7 ай бұрын
Worth information 🎉❤
@genegonzalez4713
@genegonzalez4713 2 жыл бұрын
lift determines the actual work the chiller compressor is doing. the closer the approach the less energy consumption, and vice versa, remember that chiller efficiency is to produce a large amount of TR tons with the least amount of energy consumption
@espinozajc64
@espinozajc64 3 жыл бұрын
Excellent 👍
@simohvac9222
@simohvac9222 3 жыл бұрын
very good info
@northface484
@northface484 6 ай бұрын
Thank you...Can you tell me what surge sounds like...I run a 900 ton York Chiller....And when we have a low load the Chiller makes a steady groaning noise for minutes at a time...Is this considered surge...???
@HVACTIME
@HVACTIME 6 ай бұрын
A surge will be a high-pitched squeal with a bit of a swoosh, a low-end grumbling sound is considered a stall. We get into these kind of topics in my introduction to chiller's course at chilleracademy.com, there's a community group in there once enrolled you'll have access to where we can discuss these things in detail. I also have a course dedicated to York's YK centrifugal
@northface484
@northface484 6 ай бұрын
@@HVACTIME Thank you...!!!
@SoutheastHVAC
@SoutheastHVAC 3 жыл бұрын
Thank you!
@alihatami4162
@alihatami4162 Жыл бұрын
In yk's we cant go under 7.5 barg condenser pressure because evaporator pressure drops and we must open hot gas.
@j.b3377
@j.b3377 3 жыл бұрын
Thank you…great info
@bobpetereson5177
@bobpetereson5177 2 жыл бұрын
I'm curious as to what you would do if you had a York yk, and those OWT's are so high that you can't possibly have condenser water below 85 degrees. During the summer here in m.d., we commonly experience that with our yk's.. I'm not sure I've ever observed surging. (our cw setpoint is 44 degrees). I do however constantly see what appears to be surging in low load conditions this time of year in the morning. The chiller will be running around 24% and sound like a dying whale. I never see that hot gas bypass operate either. Very confused about this.
@Angelo-yj7bp
@Angelo-yj7bp 7 ай бұрын
what happens if you set limits between 60 and 80 and you wet bulb is above 80 without adding the 5 degrees yet like it happens in south florida?
@HVACTIME
@HVACTIME 7 ай бұрын
The maximum setpoint of 80f would be the maximum even when the temperature raises above 80f. Technically once you’re above 75f the setpoint stops increasing. The tower would keep its fans a maximum to try to keep up and maximize the water cooling at the high wet bulb.
@ricardobmascardojr1608
@ricardobmascardojr1608 2 жыл бұрын
What is the best or ideal energy efficient running 700tons York chiller. We have 3 700 tons chillers and 3 cooling towers but cold weather we only run one each, but hot weather two each. Thank you
@allanfolkes6019
@allanfolkes6019 2 жыл бұрын
Because 80°c is like 26°c we have 2 York here so should the condenser water not cross 80 in C°/F°
@allanfolkes6019
@allanfolkes6019 2 жыл бұрын
Hi good day the temperatures your in reference to on this video is C° / F°
@HVACTIME
@HVACTIME 2 жыл бұрын
I do everything in F
@jasonjohnsonHVAC
@jasonjohnsonHVAC Жыл бұрын
C to F= C°×1.8+32
@donsvideos1985
@donsvideos1985 Жыл бұрын
Thermal storage, how about 39deg f chillwater? Oh 134a gas
@Noypihvac
@Noypihvac 3 жыл бұрын
Did you able experience chiller use geothermal cooling system?
@HVACTIME
@HVACTIME 3 жыл бұрын
No
@Noypihvac
@Noypihvac 3 жыл бұрын
@@HVACTIME here in the cayman island most centrifugal chiller plant runs thru geothermal cooling. 78f condenser inlet water temp york yk chiller. Some exixting plant are also converting from cooling tower to geothermal system..
@billnipp2309
@billnipp2309 Жыл бұрын
60 degree tower water in the summer time??? good luck with that.
Trane Chiller Surging THEN ELECTRICAL Main TRIPS
19:02
HVACTIME
Рет қаралды 46 М.
Water Treatment Training for Cooling Towers, Chillers and Boilers
21:43
Что-что Мурсдей говорит? 💭 #симбочка #симба #мурсдей
00:19
We Attempted The Impossible 😱
00:54
Topper Guild
Рет қаралды 56 МЛН
UFC 310 : Рахмонов VS Мачадо Гэрри
05:00
Setanta Sports UFC
Рет қаралды 1,2 МЛН
HVAC Chiller Approach Explained
15:21
HVACTIME
Рет қаралды 52 М.
Chiller - Surge
9:16
The Engineering Mindset
Рет қаралды 181 М.
HVAC Tech School: Understanding Chiller Surge
10:08
ControlTrends Smart Buildings
Рет қаралды 308 М.
Homemade Autocascade Refrigeration System (plus Anhydrous Ammonia)
15:57
Hyperspace Pirate
Рет қаралды 116 М.
Cooling Tower PM Basic's HVAC Training for HVAC Technician
34:57
Production Chiller Not Keeping Temp And Flow Issues
29:42
HVACR Survival
Рет қаралды 13 М.
Troubleshooting With Sat Temps, Superheat, & Subcooling! 5 Possible Problems!!
18:48
Chiller Training: Water Cooled Chillers Mechanical
1:47:10
HVACTIME
Рет қаралды 19 М.
Что-что Мурсдей говорит? 💭 #симбочка #симба #мурсдей
00:19