Excellent diagnostics and very interesting part functionality and failure tutorial 👍👍👍
@drlfter3 жыл бұрын
Fantastic video and I appreciate that you took the valve apart and thoroughly explained how it works. People like you are a godsend for others just getting started in refrigeration or someone with a curious itch. I've subscribed and will be watching more of your videos. Thank you and keep up the great work sir!
@axiomteck4 жыл бұрын
the best HVAC and refrigeration videos, nice that you explain all the details of each component's great work. looking forward to seeing more and more
@RodrigoRamirez-fc5hv2 жыл бұрын
How do you check to see if it is working.
@Mgear12174 жыл бұрын
Great video. Thanks for sharing.
@ebbyt004 жыл бұрын
Thanks for the video, I am wondering what was the symptom of the bad injection valve? how did you narrow it down?
@donalddperez4 жыл бұрын
Ebrahim Tirgardoun the compressor was overheated and fried. While the compressor was running, it was hot and the injection valve was not feeding. Put a thermocouple on the outlet of the valve and one on the top of the compressor. It’s supposed to open when it gets hot. Don’t know the exact specifications but you’ll see the valve temperature out drop when it feeds and cools the compressor. Simulate a hot compressor by covering part of the condenser. Thanks for the question 🤙
@isaaccampos72763 жыл бұрын
Thank you for sharing
@shellopoy43983 жыл бұрын
the 3/8" connection is connected to liquid line right?
@mikemalone6103 Жыл бұрын
How did you( test ) to determine the valve wasn’t functioning as designed?
@DRCProductions Жыл бұрын
Verify valve is opening and closing to valve set points. See chart and verify. If it is working the there is a different problem occurring. Put a thermocouple where the valve sensing bulb is located, It’s nice to have Bluetooth sensors so you can run graphs.
@mikemalone6103 Жыл бұрын
I spoke with Copeland and they they said depending on my compressor, it can be the 193degree or 256degree ( I believe) it’s stamped on the side of the valve body… it does have a SOV upstream so that it only get liquid when the contactor is pulled in.
@mikemalone6103 Жыл бұрын
And I felt another similar injection valve to it nearby on another unit, and it was sweaty cold keeping the dlt closed and the discharge line tolerable
@christianbudds26752 жыл бұрын
At what temp did the valve begin to feed?
@westsidehvac10973 жыл бұрын
How do you determine the valve is bad?
@DRCProductions3 жыл бұрын
The compressor label on the top was brown from over heating. It was running but bypassing discharge gas internally. it was very hot and the valve was not feeding. Years of experience has taught me to use my free tools. Sight, smell, feel and hearing. Changed the compressor and valve then tested the valve which began to feed after I restated the compressor, when in doubt change it out.
@ericdvorak70302 жыл бұрын
Are these adjustable like a txv is?
@DRCProductions2 жыл бұрын
No they are not adjustable. They come in different temperature ratings calculated by Copeland. 🤙
@ericdvorak70302 жыл бұрын
@@DRCProductions kind of what I thought, got one barley passing liquid with the compressor shutting down on internal temp, valve bulb probably leaked down. Thanks for the quick reply.