Brand : Daikin model : MKS80QVM ERROR : No error Symptom: Running after 45minutes,Fcu auto off and auto on back,outdoor LED 1 & 2 light up. Cause : Thermistor failure Symptom,thermistor short circuit. #bonmj #daikin #inverter
Пікірлер: 108
@Techhvac2 ай бұрын
Sir .Bon Mj Your technical Video's very useful for technician. Great job Thank you so much 🙏🇶🇦
@BonMjАй бұрын
It's my pleasure
@vladimirmakhney54072 жыл бұрын
Hello. A very good tip, I'm sure many technicians didn't even know about it
@BonMj2 жыл бұрын
Thanks
@JDT7381262 жыл бұрын
Bon your videos are excellent! Thank you
@BonMj2 жыл бұрын
Thanks
@robinsonguanzon80922 жыл бұрын
Thanks Sir Bon Mj ❤️ A big help to us technician, A far areas and urban areas..🙏🙏🙏
@BonMj2 жыл бұрын
Welcome
@Achabab2 жыл бұрын
I never find this problem before😂😂😂, first time some one share this information in KZbin. You are the best⭐⭐⭐⭐⭐
@BonMj2 жыл бұрын
Thanks
@carlocurotto75552 жыл бұрын
That’s a great tip thank another fantastic video
@BonMj2 жыл бұрын
Thanks bro🙏
@jagannath38392 жыл бұрын
This is very good helpful information thanx sir.
@BonMj2 жыл бұрын
Thanks
@birin.68842 жыл бұрын
Hey, thanks for everything. explain his picture and I'm good.
@estanislauboavidabelo49752 жыл бұрын
thank you, please continue to upload the video.
@BonMj2 жыл бұрын
Thanks bro
@februaryoakkar9382 жыл бұрын
Thank you sir
@Blueblurr1122 жыл бұрын
Great video thank you.
@BonMj2 жыл бұрын
Thanks
@alanwong27612 жыл бұрын
👏 bravo bro 👍
@linaung1272 жыл бұрын
Hello sir, nice troubleshooting, thanks
@BonMj2 жыл бұрын
Welcome
@narayanaya5519 Жыл бұрын
Very useful information
@BonMj Жыл бұрын
Thanks
@arunramachandrana10252 жыл бұрын
Very good information
@BonMj2 жыл бұрын
Thanks
@khaidang8614 Жыл бұрын
❤
@shreekanay6982 жыл бұрын
Thanks Boss.
@BonMj2 жыл бұрын
Thanks
@Didik-cq8wy Жыл бұрын
Trimakasih bos
@BonMj Жыл бұрын
You Dari mana? Terima kasih banyak nonton video saya
@karimchiu7527 Жыл бұрын
Thank Sir Bon
@BonMj Жыл бұрын
Welcome
@arafteknikac2 жыл бұрын
Thank you so much
@BonMj2 жыл бұрын
Thanks
@sarfarajshaikh45822 жыл бұрын
Nice one bro
@BonMj2 жыл бұрын
Thanks
@hafeezdaikin25172 жыл бұрын
Thank you boos 👍
@BonMj2 жыл бұрын
Thanks
@aselajayasundara16692 жыл бұрын
Thank you sir 🙏
@BonMj2 жыл бұрын
Thanks🙏
@karaors89702 жыл бұрын
Thank you bro
@BonMj2 жыл бұрын
Thanks bro
@tabresztabu5622 жыл бұрын
Tq Boss 🙏
@BonMj2 жыл бұрын
Thanks🙏
@mdtuhintalukder50122 жыл бұрын
Thank you....
@BonMj2 жыл бұрын
Thanks
@winmaung4558 Жыл бұрын
Thank sir
@BonMj Жыл бұрын
Welcome
@jamestan79012 жыл бұрын
👍 👍 👍
@JDT7381262 жыл бұрын
Hi Bon, could you please provide a source for many of the common manufacturers thermistor resistance/temperature values? I cannot find any for the LG brand.
@user-vz6mu7iu7j Жыл бұрын
hi sir im p paul kolkata i lick you video
@peramaraj276310 ай бұрын
Normally daikin compressor discharge thermistor range 13 to 15 kilohms right ?
@antoinetuyongo65272 жыл бұрын
Bonjour , comment je pourrais avoir la version française
@MrRandyj722 жыл бұрын
That would be hard to find on the system unless its in cooling mode developing condensation at the time you are checking. Did the error code send you in the direction to check the thermistors? Last question did you full change the harness or just dry and seal the bad thermistor?
@BonMj2 жыл бұрын
Just happen after running 45minutes. Only outdoor LED 1&2 on when stop running,indoor auto off and will auto on back after for awhile. We replace the new harness.
@Achabab2 жыл бұрын
@@BonMj thank you share your knowledge 🙏🙏🙏god bless you
@BonMj2 жыл бұрын
@@Achabab welcome
@alembattlerealmsgamefowl66313 ай бұрын
sir inverter daikin 1.5hp ,indoor fan motor stay in low speed what maybe the reason o the problem ? even we changes to high speed in the remote fan speed still low,thanks for the reply
@BonMj3 ай бұрын
Any coil choke
@azadabduellahal8116 Жыл бұрын
Same can happen Mitsubishi system
@zse0118 Жыл бұрын
Hi Sir! What's the reason you put the thermistor in the water and than you checked the countinity again?
@BonMj Жыл бұрын
Put in the water just show the thermistor is short circuit when water go in to the parts. When the thermistor locate at suction pipe,the water will go into the parts after gas pipe condensation.
@zse0118 Жыл бұрын
@@BonMj Thank you so much for your answer.
@ThesecretS_a_n_3_12 ай бұрын
Daikin Indoor fan motor no running a6 alarm coming I replace indoor motor and indoor PCB board also but still have a6 alarm ? What is problem
@BonMj2 ай бұрын
Check thermistor
@arasanairconsolution4u9 Жыл бұрын
Hai sir ,vrv 3 Daikin system one outdoor 3 indoor ,all running good but , standard compressor Haven't run even one FCU haven't achieve room required temperature.please advise
@BonMj Жыл бұрын
May be already by pass. Check mode2
@peramaraj276310 ай бұрын
@@BonMjalready bypass how to find ? Bro
@janshaw54722 жыл бұрын
这种情况好难被发现!感谢老师!contiuniry中文是什么?
@BonMj2 жыл бұрын
谢谢你。去了两次才发现
@BonMj2 жыл бұрын
Continuity 是联系的,比如wire用meter 量continuity 。
@errantpmd3765 Жыл бұрын
Sir. My aircon.. cut in compressor n fan for 30min for 3 room. Is it thermistor of outdoor? I saw your ismike series, u change the indoor thermistor... May I know if is the same logic? Mine are toshiba
@BonMj Жыл бұрын
What is your setting temperature
@errantpmd3765 Жыл бұрын
@@BonMj sir.. even in the lowest also the same.
@errantpmd3765 Жыл бұрын
@@BonMj correction sir. Is 30sec..not min.
@BonMj Жыл бұрын
@@errantpmd3765 may be outdoor pcb problem
@errantpmd3765 Жыл бұрын
@@BonMj sad.. :( Thought is some thermistor...
@randypatcho6051 Жыл бұрын
How to apply your company sir
@narayanaya5519 Жыл бұрын
If short thermistor what could happen PCB
@BonMj Жыл бұрын
For this case intermittent blinking, pcb ok.
@gothandaraj8602 жыл бұрын
Hi sir vrv 3 Daikin AC e2 error and E3 error how to make rectify
@BonMj2 жыл бұрын
E2 may earth leakage E3 high pressure sensor/high pressure switch
Hi sir I have problem is Diakin air conditioning vrv system celling saspanded units have the error UF this error what is the problem sir thanks
@BonMj2 жыл бұрын
You change indoor pcb?
@govindarasugovindarasu74402 жыл бұрын
@@BonMj no sir
@BonMj2 жыл бұрын
@@govindarasugovindarasu7440 check indoor all fcu voltage or pcb faulty
@mycountrymyvlog12 жыл бұрын
i need job i am air conditioning and refrigeration mechanic
@nagarajvenkat84762 жыл бұрын
Hi sir I have problem daikin package unit error E 32 how to rectify this problem sir
@BonMj2 жыл бұрын
Check Compressor 1
@nagarajvenkat84762 жыл бұрын
Thanks sir
@azizullahkhanpathan2693 Жыл бұрын
Hello sir I am Aziz. I have a Daikin 1.5 ton inverter split AC. My AC is showing C3 error code. Can you please tell me what C3 error code is and how to solve it . Model no FTKZ50U
@BonMj Жыл бұрын
Try check i door thermistor. Actually this error is water level sensor problem
@azizullahkhanpathan2693 Жыл бұрын
Thank you for your reply sir 👍
@azizullahkhanpathan2693 Жыл бұрын
I will check
@azizullahkhanpathan2693 Жыл бұрын
@@BonMj Hello sir my AC is Daikin inverter split AC it is showing C3 error code will you please confirm what is the issue in it C3 means?????
@azizullahkhanpathan2693 Жыл бұрын
In the split AC water level sensor will be there ?????