Differential Relay Testing (Micom P643)

  Рет қаралды 19,118

RELAY PROTECTION ELECTRICAL

RELAY PROTECTION ELECTRICAL

Күн бұрын

Пікірлер: 20
@ravindrayogi3196
@ravindrayogi3196 Жыл бұрын
Why we take is1.002 and is2 3pu and k1 is 30 % and k2 50% .how it comes
@relayprotectionelectrical
@relayprotectionelectrical Жыл бұрын
Is1 is set as minimum as possible in order to give sensitivity to differential relay but it is so chosen that due to mismatch of tap position it should not operate. Again next slopes are given to maintain stability due to through fault. You can go through video kzbin.info/www/bejne/b6TGaoqpntagd5Y
@Kiran-nb5xi
@Kiran-nb5xi 2 жыл бұрын
Very nice 👌
@mkhoirun918
@mkhoirun918 Жыл бұрын
When Id is set to 0.3 In, what is In here? since transformer has 2 In. first In for LV side, second is In for HV side
@rjshtk
@rjshtk Жыл бұрын
For HV side, In will be the full load current of HV side expressed in secondary terms. Similarly, for LV side, In will be the full load current of LV side expressed in secondary terms.
@Technicalguy_123
@Technicalguy_123 Жыл бұрын
Sir i have doubt that we need to inject HV LV value after multiplying with matching factor? Or without matching factor as relay will multiply with matching factor internally?
@relayprotectionelectrical
@relayprotectionelectrical Жыл бұрын
Go through the playlist for differential relay. I think you will have clear Idea about above kzbin.info/aero/PLawO3DDAIgHGsFxFjkech1CgGBWgArtok
@anilshemade6048
@anilshemade6048 3 жыл бұрын
Plz explain Is1 and Is2.
@ranjansahu2362
@ranjansahu2362 4 жыл бұрын
Well done sir
@surendrakverma555
@surendrakverma555 2 жыл бұрын
Very good. Thanks 🙏🙏🙏🙏🙏
@souvikdasgupta6363
@souvikdasgupta6363 2 жыл бұрын
How did u get end section 1 value as. 67?
@relayprotectionelectrical
@relayprotectionelectrical 2 жыл бұрын
Please go through the following video kzbin.info/www/bejne/b6TGaoqpntagd5Y
@happysingh-gk2dj
@happysingh-gk2dj 2 жыл бұрын
Hello sir, I designed a differential relay , I want to discuss with you .how can I contact with you
@sreehari2969
@sreehari2969 2 жыл бұрын
how did you get 0.67 in chara. can you explain
@relayprotectionelectrical
@relayprotectionelectrical 2 жыл бұрын
Kindly go through this video kzbin.info/www/bejne/b6TGaoqpntagd5Y
@bablukumar-hz9nr
@bablukumar-hz9nr 2 жыл бұрын
Distance protection relay testing and configuration pls sir
@relayprotectionelectrical
@relayprotectionelectrical 2 жыл бұрын
Thank you for your comment. I will definitely upload video on Distance Relay testing and configuration.
@prabhakarrayalaseema333
@prabhakarrayalaseema333 2 жыл бұрын
Very low voice
@relayprotectionelectrical
@relayprotectionelectrical 2 жыл бұрын
Use headphone for better hearing
Differential Relay || How to Draw Slope of Differential Relay
16:32
RELAY PROTECTION ELECTRICAL
Рет қаралды 14 М.
DIFFERENTIAL RELAY || Slope Testing ( Micom P 64X) IN HINDI ( PART-1)
18:23
RELAY PROTECTION ELECTRICAL
Рет қаралды 2,6 М.
"Идеальное" преступление
0:39
Кик Брейнс
Рет қаралды 1,4 МЛН
$1 vs $500,000 Plane Ticket!
12:20
MrBeast
Рет қаралды 122 МЛН
Matching Factor and Per Unit (PU) Current for Differential Relay
8:46
RELAY PROTECTION ELECTRICAL
Рет қаралды 2,6 М.
Basics of Protection Relay Testing
1:33:52
Minaatral Power Systems
Рет қаралды 17 М.
Inside the V3 Nazi Super Gun
19:52
Blue Paw Print
Рет қаралды 2,6 МЛН
Testing Transformer differential Protection  7UT86  SIEMENS SIPROTEC 5
20:56
RET670 transformer differential protection relay testing calculations
18:33
Power System Engineering Solution (PSES)
Рет қаралды 6 М.
Differential protection
8:53
stephen brooks
Рет қаралды 141 М.