Thank you very much, was looking for this because we're replacing MM440 to G120 on Profibus.
@mongiAa2 ай бұрын
good effort, godd explaination, continue with upgrade simovert vc to sinamics G120, Thnaks
@maximjones14468 ай бұрын
How you determined the hexes command for Cotrol ON/OFF = 047E and other commands? Where is the its sources?
@williamcernich58892 ай бұрын
I was wondering the same..
@mughal16484 ай бұрын
Thanks a lot. We are going to replace old Siemens MM to SINAMICS G120. I was looking such video,
@muhammadshehbaz77654 жыл бұрын
amazing video, really helpfull for engineers. keep making videos.
@muhammadshehbaz77654 жыл бұрын
but not able to download file properly, sir please the problem.
@EASYPLCTRAINING4 жыл бұрын
Any error in download ?
@muhammadshehbaz77654 жыл бұрын
Now able to download
@Khatu_ki_sarkar71 Жыл бұрын
Very very helpful for beginners
@a_sava Жыл бұрын
Thanks for sharing this. You saved me a lot of time.
@mirzamansoor2434 жыл бұрын
Thanks for uploading this type of Videos.
@engmohamedrefaat56794 жыл бұрын
Thanks for your efforts need video about communicate s7 1200 with abb acs 550 or acs 580
@rsinurat21444 жыл бұрын
Same🙏🏽
@raviprabhat23923 жыл бұрын
Please upload a similar video for S7 300 communication with Parker 590 or 690 plus drive..please
@louzehimolevy41534 ай бұрын
Hello sir, I appreciate a lot your in making tutorials. And also I would like to take an online PLC training with you if possible.
@andreicaza61453 жыл бұрын
I am getting a Fault F1910 and I do not know why. I am using your codes 047E, but the moment I put "HIGH", it gives me that fault. Do you know why?
@imranmirza57753 жыл бұрын
thanks brother super effort ................... please suggest me TIA Portal version which you are using in projects...........?
@EASYPLCTRAINING3 жыл бұрын
V13 mostly
@imranmirza57753 жыл бұрын
@@EASYPLCTRAINING Thanks
@ngoile8763 жыл бұрын
i don't have g120x on Tia, Could i choose others? is it ok?
@EASYPLCTRAINING3 жыл бұрын
No , check online on siemens website forum for correct gsd file
@palanipps Жыл бұрын
Sir one doubt could you plz?. the Gsd file is common for all Siemens model drives or different gsd files for other model Siemens vfd?
@maheshbhilare64304 жыл бұрын
Thanks for vedio.... Make one vedio on how to tak wincc flexible running back-up with its Recipe... I have tried ... But not able to restore it's old recipe
@inaramara2416 Жыл бұрын
please sir , from where you are getting those codes for words ?
@souravdas25062 жыл бұрын
very nicely explained, thanks
@umarafzal49264 жыл бұрын
its very help full thank you soo much sir please can you tell theirs only one perameter p918 we need to set on drive side and after that our plc to drive communication is done.?
@dhavalmaheta34282 жыл бұрын
Helpful video thanks
@rajendravaidya64823 жыл бұрын
How to solve CU busy errors
@motor5193 жыл бұрын
Parameter to Drive g120 ??? . For setting profinet
@newkhmer3591 Жыл бұрын
What program in the OB121?
@iqbalmehedi34234 жыл бұрын
nice video. please make SCADA for this motor control.
@AzhaguRK9 ай бұрын
Thank you ❤❤❤
@kiranchoudhari47174 жыл бұрын
Good information 👍😊 brother I understood 💯
@kiranchoudhari47174 жыл бұрын
But the Google drive file doesn't opening even in laptop
@EASYPLCTRAINING4 жыл бұрын
Let me check once again .....
@jobsinpakandgulf621 Жыл бұрын
Sir 067F was missing reverse bit
@aarifbobade24032 жыл бұрын
Good knowledge.But i was searching one thing.i replace one of simens drive but its showing BF Fault.i have copy the prameters by bop and paste with another.I thing communication issue.can you help me.
@EASYPLCTRAINING2 жыл бұрын
What is drive model ? Is it profibus ? Check the drive profibus address in the parameters , old and new drive address must be same , ..... check the Dip switches for the profibus address under the BOP . Set these dip switches same as old drive....
@EASYPLCTRAINING2 жыл бұрын
After setting profibus address , power cycle the drive , OFF and after 2 minutes turn it ON
@aarifbobade24032 жыл бұрын
@@EASYPLCTRAINING Thanks for your value response.Yes profibus ethernet cable,no dp switch, model no is 6SL3210-1KE11-8AF2.What is parameter for profibus address.
@charlesmwangi164 Жыл бұрын
How do you trouble shoot Siemens VFD
@bobeldukla3 жыл бұрын
Super. Thank You very much....
@alrazi668710 ай бұрын
why we add standard telegram ftn?? what is the need of this ftn here?? pls anyone expain
@mohdirshadshaikh4443 жыл бұрын
Very well explained!! I would like to know if I want to run/stop the drive via digital inputs only and speed reference to give only via profibus, what parameters do i need to set for that? As of now when I established the communication via profibus then now I'm unable to start the drive via digital inputs!! Please help me with this
@EASYPLCTRAINING2 жыл бұрын
All PROFIBUS DIP switches = OFF --> Address defined in P0918 is valid otherwise the DIP switch setting has priority and P0918 indicates DIP switch setting. check address in OLD drive paramter p0918 and put this address in new drive and save it and power OFF and ON the drive.
@muhammaddanishhameed98654 жыл бұрын
Bhai, servo motor control with plc par bhi video banayein.
@EASYPLCTRAINING4 жыл бұрын
Sure
@jmmedia6793 жыл бұрын
Why did you use TIA portal...could it not be done in simatic manager?
@EASYPLCTRAINING3 жыл бұрын
Yes
@jmmedia6793 жыл бұрын
@@EASYPLCTRAINING same procedures can be followed to configure it with simatic manager.. right?
@EASYPLCTRAINING3 жыл бұрын
@@jmmedia679 sometimes somatic manager don't have gsd files for new drives , thats why better to use tiaportal.
@vorapobautomation97604 жыл бұрын
How to Communicate siemens S7 300 PLC with Sinamics s120 VFD Drive via profibus/Profinet using TIA Portal on VDO ?
@gouravgaming55413 жыл бұрын
Sir, please make a video on SIMOCODE programming with s7-300 plc and control from HMI TP-700 Comfort. It will be really helpful.
@ameysawant56954 жыл бұрын
sir, can you please tell me, how you calculate that hex value to control drive.
@EASYPLCTRAINING4 жыл бұрын
kzbin.info/www/bejne/ppqwnWp9mN13epo
@bakilsorory35164 жыл бұрын
thanks brother nice video
@Bigmallone4 жыл бұрын
thank you for the video
@bezzila3 жыл бұрын
Thanks Super!
@tayyubindustrialcontroleng84474 жыл бұрын
Awsome👍
@kgauravb4 жыл бұрын
👍👍
@anikdebnathopu80823 жыл бұрын
Tnx bro
@EASYPLCTRAINING3 жыл бұрын
Please ask your friends to subscribe also
@vorapobautomation97603 жыл бұрын
How to Communicate siemens S7 300 PLC with Sinamics s120 VFD Drive via profibus/Profinet using TIA Portal ?
@EASYPLCTRAINING3 жыл бұрын
My friend give me some time , I will make a video , you can search in Siemens forum .... there are lot of topics that will help you