Should electricians assume TN-S and TN-C-S are both PME earthing systems.

  Рет қаралды 10,814

eFIXX

eFIXX

Күн бұрын

Пікірлер: 24
@johnhoward2104
@johnhoward2104 4 жыл бұрын
According to the new EVC CoP, TN-S should be assumed to be TN-C-S unless the DNO confirms in writing that it is TN-S and will always remain TN-S - if not, assume it's TN-C-S!!
@bartman58
@bartman58 4 жыл бұрын
Clear as mud that Gary....I will stick to using my own common sense
@efixx
@efixx 4 жыл бұрын
Common sense is the best way:-)
@richardwilliamson3624
@richardwilliamson3624 4 жыл бұрын
Yeah, clear as mud 😂😂
@westinthewest
@westinthewest 3 жыл бұрын
Western Power advised me in November 2020 that they don't have records for the earthing arrangements in dwellings. They were not keen on arranging a visit to the property in order to investigate. ESQCR rules must have changed since this video was published.
@seprishere
@seprishere Жыл бұрын
I did ask (as a non-electrician but curious as the on-site arrangement looked a bit like TN-S) but I guess assuming it is TN-C-S is safe and when I did have my EICR (before moving in) the earth loop impedance reading was in TN-C-S bounds. I didn't pursue the matter. I was surprised they didn't actually know though!
@Orgakoyd
@Orgakoyd Жыл бұрын
@@seprishere Does ''TN-S should be assumed to be TN-C-S'' mean the lead sheathing of the cable that comes into the house is joined to the neutral of modern TN-C-S type cable in the street somewhere that takes it back to the distribution transformers star point? Because if the lead sheath is not connected to the neutral conductor at some point then the main earth terminal is not earthed as far as I can tell (other than through extraneous conductive parts).
@JasperJanssen
@JasperJanssen 2 ай бұрын
@@Orgakoydit’s only tn-s if the *entire* path to the transformer is separated *and* the DNO plans to never change that. Given that new underground cables are pretty much universally C in the UK, that means that even if it’s currently non-C any repair in the line at any point will change it to Tn-C-S. So as long as that’s true, assuming TN-S is essentially unsafe, at least in residential/small office context. Maybe if you’re a large industrial client with your own transformer, things become more complex than that.
@Orgakoyd
@Orgakoyd 2 ай бұрын
@@JasperJanssen Thank you for that. I’m always keen on learning more about this stuff. I read a western power PDF from 2019 that said they have standardised on a minimum service cable size, and minimum distribution transformer size going forward, so that the distribution grid is able to handle increase in load in the future. Also that all new cables, and any replacement cable going forward will be 3 phase, connected underground in the street and brought into the building ready for a 3 phase supply in the future, and also giving opportunity to swap phases around easily for balancing, whereas currently it’s not possible other than digging up the joint under the street.
@blower1
@blower1 2 жыл бұрын
Me: Does this property have a TN-S or TN-C-S earth system? DNO: Yes.
@darrenstevens8729
@darrenstevens8729 Жыл бұрын
Hi so if a swa circuit is fed from the consumer unit on a TN-C-S earthing system does the remote end of the swa change to a TN-S system
@efixx
@efixx Жыл бұрын
No, the earthing arrangement is defined by the means of earthing to the origin of the installation not a sub-main. Good question though.
@darrenstevens8729
@darrenstevens8729 Жыл бұрын
@@efixx thank you
@ismscsim
@ismscsim 2 жыл бұрын
I have a PME sticker on my board.... the earth is bonded to the neutral in the garden from an over head cable landing in the ground. The supply is fragile in high winds. Decided to go off grid and install my own earth. Can a locked mechanical transfer switch or isolator be installed on the consumer side or prosumer as I will be when offgrid? If I am off grid completly then I can up the no. of solar panels without restriction by the DNO. Any info on this is welcome. Cheers
@faithful5475
@faithful5475 4 жыл бұрын
Quick question folks Do we need to earth bond metal beam in a new extension and another one on loft conversion ? Same property.
@faithful5475
@faithful5475 4 жыл бұрын
@@sparkymacsparkface7497they are atm but they will be buried with plasterboard anyway
@faithful5475
@faithful5475 4 жыл бұрын
No unfortunately it doesn't have
@faithful5475
@faithful5475 4 жыл бұрын
Thank you sincerely for your advice I will give them a ring to make sure its correct 👍
@stevensmith4449
@stevensmith4449 4 жыл бұрын
If in doubt Bond it out!
@avfczoff
@avfczoff 2 ай бұрын
How can you test to confirm it’s TNC-S or TN-S?
@jessthorn9774
@jessthorn9774 4 жыл бұрын
hi im new to this what what is the bsen number for a switch fuse isolater at 125amp its 4 pole regards jas
@johncooper5293
@johncooper5293 4 жыл бұрын
There is no way the DNO can guarantee they haven't repaired a TN-S and therefore you must assume TN-C-S.
@muzikman2008
@muzikman2008 4 жыл бұрын
The truth is the DNO Don't really know what systems they supply either. 😂 Some Teflon shoulders going on... Ass covering.
EARTHING a SHED or OUTBUILDING - TT - TNS - TNCS
14:39
LEARN ELECTRICS
Рет қаралды 97 М.
How many people are in the changing room? #devil #lilith #funny #shorts
00:39
Smart Sigma Kid #funny #sigma
00:33
CRAZY GREAPA
Рет қаралды 38 МЛН
Подсадим людей на ставки | ЖБ | 3 серия | Сериал 2024
20:00
ПАЦАНСКИЕ ИСТОРИИ
Рет қаралды 584 М.
coco在求救? #小丑 #天使 #shorts
00:29
好人小丑
Рет қаралды 109 МЛН
Understanding Earthing Arrangements - TNCS, TT, TNS
5:59
Earthing vs. Bonding: What's the Difference?
6:38
eFIXX
Рет қаралды 73 М.
Netzsysteme erklärt! (TN-S, TN-C, TN-C-S, TT) ElektroM
3:35
ElektroM
Рет қаралды 139 М.
Generator Earthing Types - TN-S or IT?
14:57
John Ward (jwflame)
Рет қаралды 53 М.
How many people are in the changing room? #devil #lilith #funny #shorts
00:39