Electro-Pneumatic Positioner series 830 calibration

  Рет қаралды 12,847

Engineering solution

Engineering solution

Күн бұрын

Пікірлер: 22
@humanbeing4097
@humanbeing4097 Жыл бұрын
Very helpful video bhai,keep it up.
@soban5
@soban5 Жыл бұрын
Wonderful explanation. Very helpful.
@blackbow919
@blackbow919 Жыл бұрын
superb way to explain...just cleared my concept.. thanks you 💥🔥
@nawajs
@nawajs Жыл бұрын
welcome
@blackbow919
@blackbow919 Жыл бұрын
specially that no need for any 24 volt or 230 volt ..just need mA source... in other videos they were not clearing that concept..thank you again ❤️
@shivanijaiswal8765
@shivanijaiswal8765 Жыл бұрын
I agree
@nawajs
@nawajs Жыл бұрын
thanks
@cijj84
@cijj84 10 ай бұрын
if you are testing from a loop calibrator make sure you select 4-20ma with 24v supply if you are not using the normal powered loop of the PLC
@khalidbenslimane-u3r
@khalidbenslimane-u3r Жыл бұрын
I want to know the adjustment of the SMC VL10 modular valve, when I touch an adjustment screw the valve remains in the open position, even if it is switched off
@ravikeshyadav889
@ravikeshyadav889 Жыл бұрын
Thanks sr 🙏 aap ne calibration kr ke dikhaya
@kishoreKumar-wt4vi
@kishoreKumar-wt4vi 7 ай бұрын
Good post sir. 50 % command then 40 % open what do sir
@SurajSingh-wk1tk
@SurajSingh-wk1tk Жыл бұрын
Sir span adjustment kab krte h or span kya h
@instrumentpower6380
@instrumentpower6380 7 ай бұрын
Sir span ko kitne me set karte hai
@jackyshikhar
@jackyshikhar Жыл бұрын
Which make valve is this ?
@afsarhussain985
@afsarhussain985 Жыл бұрын
Please about your location
@dhananjaybhendkar6132
@dhananjaybhendkar6132 Жыл бұрын
Hi I want solution for electro pneumatic model series no 830 At4 ma valve is open and giving full scale deflection And 20ma valve give zero deflection what should i do
@vsaktharhussain
@vsaktharhussain Жыл бұрын
1.Check 1st air to open or air to close . 2.Check inside the Positioner cam. 3.check mA while giving comand from dcs.
@BismoiBaruah
@BismoiBaruah 9 ай бұрын
👍
@vsaktharhussain
@vsaktharhussain Жыл бұрын
Lot of things not covered 🙂
@alocin110
@alocin110 Жыл бұрын
I cannot understand what kind of calibration they are doing here. No one does 4.5psi. It looks they have no technical knowledge to how to calibrate a valve actuator. He did 4ma, and 4.5ma and adjusting zero and span at 20mA. That is wrong. You should check the valve position at 4mA and then adjust zero, then 20mA and adjust span. Then try 4mA, 8mA, 12mA, 16mA and 20mA for 0%, 25%, 50%, 75% and 100% respectively with the corresponding air pressure of 3psi, 6psi, 9psi, 12psi, and 15psi. Adjust zero and span twice. What they are doing is wrong and this not how calibration should be. I hope they will understand this comment.
@aamirmohyuddin3220
@aamirmohyuddin3220 Жыл бұрын
Yes i agree with you
Electro Pneumatic Positioner
17:52
Pt Sushil
Рет қаралды 52 М.
Which One Is The Best - From Small To Giant #katebrush #shorts
00:17
РОДИТЕЛИ НА ШКОЛЬНОМ ПРАЗДНИКЕ
01:00
SIDELNIKOVVV
Рет қаралды 3,7 МЛН
小路飞嫁祸姐姐搞破坏 #路飞#海贼王
00:45
路飞与唐舞桐
Рет қаралды 29 МЛН
Epic Reflex Game vs MrBeast Crew 🙈😱
00:32
Celine Dept
Рет қаралды 39 МЛН
Control Valve Positioner Working# Working of Electro Pneumatic Positioner.
10:52
J.S. Electrical & Instrumentation
Рет қаралды 11 М.
파워제넥스 포지셔너 켈리브레이션
8:01
Jaeseong Koh
Рет қаралды 63 М.
Practical demonstration of Electro Pneumatic Flushing System (EPPFS)
6:39
Sealdah Mechanical Carriage & Wagon Department
Рет қаралды 5 М.
ABB smart positioner auto calibration in தமிழ்
3:50
Instech தமிழ் instech TAMIL
Рет қаралды 11 М.
Which One Is The Best - From Small To Giant #katebrush #shorts
00:17