Struggling to understand why you adjust the TRV window when you change the fault current. Surely the TRV window is just a function of the breaker itself?
@phuctranhuu72004 жыл бұрын
We usually using statistical (100 simulations) to calculate TRV and RRRV. When switching breaker in real-life, we have to consider the probability of the waveform (switching when in top of the wave sine is different than switching when the sine wave is zero)
@henrygras57324 жыл бұрын
Hi Phuc Tran Huru, Right, however, this will depend on the situation. Circuit breakers interupt the current close to current zero-crossings. This is a physical limitation. Therefore, even if you change the switching time, the breaker interupts at zero-crossings. The exception is when the breaker chops a large current, like vaccum CB may chop up to 15A. For example, disconnecting an unloaded transformer. Do you agree with that?
@phuctranhuu72003 жыл бұрын
@@henrygras5732 Yes I agree with that
@victorfedorov22953 жыл бұрын
Do you have a typical model of 3 fase and 1 case cable in wbline block?
@alejandraandrade5063 жыл бұрын
Can I pass measurements from emtp to matlab?
@pedrocamargos20883 жыл бұрын
yes. You can salve .mat type variables output from PLOTXY