Flex vs. Rigid Metal AC Duct - My preference may surprise you!

  Рет қаралды 185,078

Jordan Smith

Jordan Smith

3 жыл бұрын

Building Science Geeks love to hate on flex duct in HVAC systems. They take pictures of terrible flex duct installations in crummy attics and link to this TAMU article which says that if you crush it, let it sag between joists, and force 3X the recommended CFM through flex duct, the result is a drop of pressure in the system ( oaktrust.library.tamu.edu/bit... ).
Well, duh! Any product, when used incorrectly, will perform poorly.
I think the take away should be how small of a pressure drop there actually is even when the flex duct is crushed 45% AND sagged over joists for a long period using REASONABLE CFM rates - 1"H20 per 100' run. That is way better results than I would have predicted.
When installed correctly, flex duct moves air just as efficiently as rigid duct and is much easier and cheaper to install. Flex also has the advantage of being pre-insulated and eliminates joint work except at the terminations, reducing heat gain and leakage.
Yes, flex duct has to be installed correctly, but so does rigid ductwork.
Keep the flex duct liner tight, properly secured, the runs as short as possible, and eliminate as many tight bends as possible and you will have a great performing flex duct system.
In my opinion, the best bang for your HVAC dollar is to have a professionally designed system that is COMMISSIONED after install to ensure that the performance of the as built air conditioning system matches the designed requirements.
www.mtcopeland.com

Пікірлер: 416
@airmasterhvac
@airmasterhvac 2 жыл бұрын
36 year Mechanical contractor here. We specialize in airflow and are generally hired to "fix" hot rooms or "not enough air" issues. The absolute most flex I recommend is 6' which is to say use hard rigid duct sized correctly for friction loss and static pressure then the very last 6' of duct may be flex installed without any sharp bends. The only place I would use full runs of flex would be oversized returns but you need to be careful if it is installed with sharp bends then it may collapse upon itself. Hard duct is much better for airflow, rodents, you can have it cleaned on a regular basis without worry of damage and it can be easily modified in a remodel. P.S. that duct up to the left in the video with the sharp bend makes me cringe.
@Txpo50
@Txpo50 2 жыл бұрын
I noticed the same and I don’t even work in HVAC. The sagging duct just above his head isn’t great either and you can also see a crease in the 90 down. Good news for you is that’s job security
@vonne2376
@vonne2376 10 ай бұрын
Rigid has my vote too. But if you have an idiot working nearby check ductwork before they leave. 5 smashed rigid ducts I need fixing. South Tx rn is 105° Thanks a**hat!!
@DaraParsavand
@DaraParsavand 10 ай бұрын
I had rodent problems with my flex duct. Never again.
@user-zu3wc9jm2f
@user-zu3wc9jm2f 10 ай бұрын
😂😂😂😂on that duct that makes you cringe 😂😂😂
@paulmarc-aurele5508
@paulmarc-aurele5508 7 ай бұрын
I was in the HVAC business my entire career, the best Practice is to rough in your trunk and attach a 12” class 1 flex to your takeoff and run out with rigid. This method eliminates expansion noise and keeps airflow as designed.
@akeemhoque5976
@akeemhoque5976 2 жыл бұрын
Sir, let me tell you something - I am grateful for this video! I watched a lot of videos in the past and had a very hard time renovating my house and after seeing this I feel so much better and look forward to completing my projects. Thank you.
@andrewdiamond2697
@andrewdiamond2697 3 жыл бұрын
I use flex duct, but I add in metal elbows for 90 degree turns and usually add some metal going into the registers on the ends, so the flex is straight shots or gentle bends. The more important thing is to have the airflow calculations and cross-section sizes matched to the air handler total and the CFM needs for each room. There aren't very many bad HVAC materials, just misapplied and poorly installed ones.
@The1SimLash
@The1SimLash 2 жыл бұрын
Nice info. Can duct work go through the joist like he has it? Is that safe?
@andrewdiamond2697
@andrewdiamond2697 2 жыл бұрын
@@The1SimLash I haven't gone thorough I-joists with it. I've gone through I-joists with line sets between the condenser and evaporator, but not with ductwork.
@TheAnimeAtheist
@TheAnimeAtheist 2 жыл бұрын
@@The1SimLash If it's allowed in your area there's nothing "unsafe" about it
@TheAnimeAtheist
@TheAnimeAtheist 2 жыл бұрын
my only issue with interchanging them with 90s is at termination points, when moving from a 6 in flex to 6 in rigid, the friction rate is so different that you can screw with your desired exiting velocity with this transition. Sometimes you can account for this by going from a 7 in flex to a 7 rigid then 7-6 reducer then 6 inch rigid and then a 90 if you need.
@kadmow
@kadmow Жыл бұрын
@@The1SimLash - Notice the truss/beam supporting the span...
@markgordon4368
@markgordon4368 3 жыл бұрын
There is no way you can escape from the zombie apocalypse through an eight inch duct.
@JordanSmithBuilds
@JordanSmithBuilds 3 жыл бұрын
Best. Argument. Ever. Case closed. I'm only installing 24-in square duct from now on, making sure to have registers in all rooms that lead directly outside.
@markgordon4368
@markgordon4368 3 жыл бұрын
@@JordanSmithBuilds 💀💀💀💀🤣🤣🤣🤣👍
@MD-lm7fj
@MD-lm7fj 3 жыл бұрын
@@JordanSmithBuilds 36" you have to be A.D.A. compliant! And it allows room for the zombie slaying "devices"
@markgordon4368
@markgordon4368 3 жыл бұрын
@@MD-lm7fj after our government has obliterated our building codes England will start to look like casablanca without the sun lol
@lesliemcdaniel3263
@lesliemcdaniel3263 3 жыл бұрын
Hilarious! 😂
@williamwilliamson139
@williamwilliamson139 3 жыл бұрын
I like the presentation and I agree with you 100 %. I am in the process of installing a new central air system and you have influenced and convinced me about duct flex ductwork. Thanks Pal.
@MAGAMAN
@MAGAMAN Жыл бұрын
sucker.
@andrewcastor9279
@andrewcastor9279 2 жыл бұрын
Flex duct warranty is 10 years. I've heard it will last between 10-25 years before the Mylar liner starts to deteriorate. I would never use flex duct anywhere that it is enclosed like inside a wall or vaulted ceiling cavity. You will have to tear out stuff to get to access to it if it needs to be replaced. Like others have said, I choose to run trunk lines in metal with step down reducers along the way and only use flex for the last 5-6' to connect to the boot/register. You have to be careful not to use Ty-wrap on the outer insulation jacket because it will crush down the insulation and cause condensation to happen on the inner duct liner. Ty-rap the inner liner only! Tape and mastic the insulation jacket on flex. Flex needs to be stretched and held tight for 1-2 minutes before installing. It's literally in the flex duct instruction manual that nobody seems to read. Lastly, duct cleaning to remove dust over the years is sometimes needed. The various tools used to do this can easily poke holes via the high pressure air stream coming out of the rotating nozzle on older flex duct. Metal has it's own installation issues but won't be ruined from cleaning or aging like flex duct.
@Skatepordiversao
@Skatepordiversao Жыл бұрын
MAN that video is awesome! Tks for that! And I thought you had a chrome key behind you all that time, at the end you touched the duct and my mind was like “WOOOW what’s happening?!”
@lisalibeer7824
@lisalibeer7824 2 жыл бұрын
Well put! Will be opting for flexible ductwork in our house. You look exactly like one of my nephews. Felt like I was watching him talk. Thanks for posting this!
@davidnee7870
@davidnee7870 3 жыл бұрын
SMACNA standards address all these details in great details with scientific examples of various products. It recommends standards that are speced or specified on drawings by MEP engineers. Flex is to be used any the end of a run, tying in the duct to diffuser box. Testing and balancing is done upon completion, to record how each vent is performing and is adjusted or balanced by adjusting dampers, so everything works as speced by architect.
@danielmetts2953
@danielmetts2953 3 жыл бұрын
Matt Risinger is going to call you over this one.
@isleofgreg
@isleofgreg 3 жыл бұрын
Master Risinger has been glove slapped in the face. Now to regain his honor, he must challenge Master Smith to a duel.
@Somewhere-In-AZ
@Somewhere-In-AZ 3 жыл бұрын
I'm in the design process and watch a ton of Risinger videos. BUT, I like to hear what other professionals have to say. This guy has some good points. With that said, I live in a place that gets up to 118° in the summer and occasionally will see 20° in winter. Maybe, based on the farthest distance of 44 feet, I may go with a hybrid of the two. Metal for long straight runs and flex on the shorts. However, if the flex is pulled as straight and tight as possible, I've read that this minimizes friction and turbulence.
@Somewhere-In-AZ
@Somewhere-In-AZ 3 жыл бұрын
Meant to add that equivalent length plays a part in air flow as well.
@swissmade1497
@swissmade1497 3 жыл бұрын
I agree with you, it all comes down to planning and execution
@6stringsandapick
@6stringsandapick 3 жыл бұрын
Using some strategically placed elbows is nice in certain areas. The duct boot selection where it comes through the ceiling is also important. Starting from a basic, cheap system, what is the first thing to upgrade? (It's not the flex duct)
@jamescc2010
@jamescc2010 3 жыл бұрын
Can I find best good quality flexible ducts from homedepot or lowes? What brand and specs do you recommend for HVAC ducts in attic of 2-story home?
@kyleorr533
@kyleorr533 3 жыл бұрын
Is there such a thing as rigid plastic ductwork? I’ve seen some rust in mine but don’t want flex ductwork because of mice.
@behmcon
@behmcon 4 ай бұрын
The house we just built was designed with a rigid main plenum w/ flex duct branching off to the rooms... Cheers, great video!
@USAACbrat
@USAACbrat 3 жыл бұрын
I like to use blended system, rigid mains, flex runs.
@johntoups6338
@johntoups6338 2 жыл бұрын
i have a newer home in VERY HOT Southeast Louisiana. It's all FLEX. But i have just 1 room (our bedroom) that is hotter by 2-3 degrees. It's the longest run from the plenum, and it has one larger duct splitting in 2 registers in the bedroom. My main question is, can you wrap more insulation over flex duct? And if so, what should i look for? Figured maybe the long runs in the attic may be messing with the air temp inside the ducts.
@mohamadnohayli234
@mohamadnohayli234 2 жыл бұрын
In most of the projects I see in Canada the US, I see long flexible duct more than 20 feet going from the FCU to the air outlet. But it kept me wondering that in ASHRAE Fundamentals Chaper 21: Duct Design Page 21.7, it is clearly mentioned that for Commercial Systems, flexible ducts should be NO MORE THAN 1.5 M IN LENGTH, FULLY STRETCHED. How come ASHRAE don't allow it? I really appreciate your opinion about that and correct me if I am mistaken. Thanks
@idanny76
@idanny76 2 жыл бұрын
I have high static pressure on a new 3.5 ton heat pump. I know for sure the flex duct is the issue. I have two 12" coming out of the supply in opposite directions. I know I need an 18" for a 3.5 ton heat pump. I did a diagram layout of the duct in the attic. What would happen if I just replace the two 12" to 18"? Ignoring the downstairs, because everything is between the walls. The problem was even worse with an undersized return. The original and only return was a 24x18. The total static pressure on the unit was .9 W.C. I was able to drop the TESP to .66 by making the return 30x24. Since there is so much static pressure and the unit TESP is a .2 and I need an 18" for a 3.5 ton for 1400 CFM. How big does the supply plenum should be and what shape? Should the supply plenum split to 3 18" going out to each of the 3 distribution boxes? Do the other three distribution boxes also need to be larger? Looking at the triangle shaped supply plenum I have very little room up for a rectangle plenum. I think a 3 feet ductboard supply plenum should work. There is a foot from the Air handler to the ceiling and I think 2 feet from the attic floor to the roof. Now I am looking at two types of designs. Design #1 keeps the 18" ducts straight by having a single 18" coming out of the supply and then a distribution box splitting it to three 18". The sides would be coming out straight to the to side boxes and one going to the third box with a slight curve. Design #2 splits to three right at the supply plenum and goes to each box individually, but all three will have a slight curve. I will not be using any metal plenums..... it will be all flex duct and ductboard boxes, because of budget. I am not trying to make a perfect system, but trying to remove the restriction from the 12" undersized ducts installed and replacing the flex duct that was patched with mastic with new ones. Another question about the installation..... I have the flex duct running up and strapped to the roof for support. Since the supply plenum is low to the floor due to the roof..... Can the flex duct be run on the attic floor? Can you tell me which layout makes more sense and less restrictive? Thank you. Layouts: Current i.ibb.co/Ld9kmPM/Flex-Duct-Layout-and-Size.jpg Option #1 i.ibb.co/GHyS00g/2022-07-05-0002.jpg Option #2 i.ibb.co/PNN8mSB/2022-07-05-0001.jpg Air Handler Specs ibb.co/17VvF4B Video of attic kzbin.info/www/bejne/n3rReoFubtZrfbc
@GreatDivideSven
@GreatDivideSven 3 жыл бұрын
loved the video content. def going to watch more JS videos
@LIBERTY0RDEATH
@LIBERTY0RDEATH 3 жыл бұрын
As a union sheet metal worker who mainly does commercial and sky scrapers you actually did make some very valid points. I went into this video expecting to disagree. I think for residential flex duct is completely fine. As long as the runs are not super long and installed properly. Unfortunately so many of these track homes don’t have good installers and Like you said don’t commission, so rooms are not balanced correctly. Therefore some rooms are super cold or hot while others don’t get much air flow. Another huge factor is return location and return size. Do your research on who does your system. It’s worth paying top dollar for a system that is so important.
@deanburke3041
@deanburke3041 10 ай бұрын
Yea, yeah. I like to design the lowest static pressure possible to get uniform velocity and volume at every register. Everyone with a brain designs size for AC. I've used an old program from Carrier which works very well. You can adjust everything by the fan CFM to get everything the same static pressure & volume. I don't want to hear the air flowing from any of the registers.
@deanburke3041
@deanburke3041 10 ай бұрын
I can't remember the name of that program. It's from 1983. Airflow properties are eternal.
@deanburke3041
@deanburke3041 10 ай бұрын
They stole my computer.
@xitaliax30
@xitaliax30 Жыл бұрын
3 things. How do you clean out duct work ? Also dampers on that pipe? And is there air flow restriction since the pipe is not smooth on the inside like ridged
@fmdday
@fmdday 3 жыл бұрын
Flex doesn’t last forever, how will you replace it when it has outlived it’s useful life ? Never install flex in a inaccessible space. I guess you can cut the drywall out
@william.a.robinson
@william.a.robinson 3 жыл бұрын
Is that a beam behind you that has the square / rectangular holes and orange color on the ends? Or is that just a fur down for something else like a tray ceiling
@Clintotron
@Clintotron 3 жыл бұрын
Flex duct looks like the way I’d go, but I don’t need any ducting at the moment. Considering having my roof spray foamed. Any suggestions?
@benkuxhouse787
@benkuxhouse787 3 жыл бұрын
I’ve been an HVAC for 36 years flex duck for a long runs I don’t recommend ever at homes. I’ve seen too much friction loss causing low airflow throughout the house. If you want to use it for a short straight runs in a crawlspace you can. Rodents do like it as well. If anything goes wrong with that flex duct in finished ceilings you’ll have to rip all the sheet rock out to get to it. I’ve just seen too many issues over the years with too much flex on a job. If I was building my house I want rigid yes it’s gonna cost more but it will last forever and I don’t have to worry about friction loss. Builders are trying to make too much money on the HVAC part of the house and when the HVAC doesn’t work the house is a piece of shit. And I’ve seen that in multi million dollar houses where there’s really nothing can be done to correct the issues but cut the house up. You’re trying to save too much money on your houses HVAC in my opinion. Especially in this video where that flex duct is buried
@kennethbubser9601
@kennethbubser9601 2 жыл бұрын
This guy on video don’t know how to install metal duct or he would not be on here. I use flex only in crawlspace or attic. But my main trunk is metal wrapped on outside with r8 duct wrap or bubble wrap
@dbourgeois80
@dbourgeois80 2 жыл бұрын
You guys can't run duct as good as me and don't even know it!lol
@davidb8865
@davidb8865 2 жыл бұрын
Ben, how long is a "long run"?
@benkuxhouse787
@benkuxhouse787 2 жыл бұрын
@@davidb8865 over 6 ft
@tonyedwards9972
@tonyedwards9972 2 жыл бұрын
I've been doing duct for 30 yrs, flex or hard pipe, to me there's not much difference if done right
@tejas03usa
@tejas03usa 3 жыл бұрын
I have a question, for the return intake my contractor is not using flex or rigid ducting instead he's using the house framing with sheetrocks is that normal and good idea?
@seangilboy6053
@seangilboy6053 3 жыл бұрын
where do I find the covers on your ceiling discharge box?
@jose9153
@jose9153 3 жыл бұрын
What about dust accumulation in the duct? I was under the impression that it was much higher with flex duct due to the less smooth interior surface and that it is also more difficult to clean. Thoughts anyone?
@mlatouable
@mlatouable 3 жыл бұрын
Dr. Lsitburek also mentions this in his builder's guide. Similar to the comment about vermin infiltrating the ductwork and leaving evidence in the ductwork also.
@mitchellbarnow1709
@mitchellbarnow1709 3 жыл бұрын
Thank you so much! I always worried about the flex duct in my attic. My furnace is in my basement, with the living area on the first floor with one powerful outlet. The top floor has four outlets for the two bedrooms and the two bathrooms. I found that even if I completely close the living area outlet, there is almost no increase in airflow to the top floor. The furnace is a very tiny 14” wide, 45,000 btu, natural gas unit. There is no air conditioning and there’s so little airflow to the top floor, that it would be useless. There’s only some rectangular metal duct inside the wall to bring the air to the attic. It’s a house with an association, so I can’t just stick an package unit on the pitched roof. We’ve already covered the south facing roof in solar panels and north face the street. I use an inefficient portable hose outlet air conditioner on really hot days. A big swamp cooler would be awesome, because it’s extremely dry when it’s hot outside. It would only take a basic 120 volt outlet to power the water pump and the circulating pump. Thank you so much for your opinion, if you have time for some very basic thoughts.
@iancormie9916
@iancormie9916 3 жыл бұрын
Take a look at the pioes going up stairs and make sure it isn't crushed, blocked or have a closed damper in the system. Also look at the floor registers, if they are undersized or if they have run small lines to the upstairs rooms, you may have to upgrade them. While you are at it, beg, borrow or steel a radiant thermometer to endure you have insulation where it is supposed to be - ditto leaking ducts.
@dpeagles
@dpeagles 3 жыл бұрын
All metal ducting is loud. You hear the blower and all the booings of the metal expanding. Flex at the end of the run.
@doct0rnic
@doct0rnic 3 жыл бұрын
you sold me, I bought a house, the previous owner installed a quagmire of ducts, most rooms dont have any vents, I just need one maybe two long ducts to complete the rooms in the house, this looks like the easiest and most practical way of doing it.
@josephferron7672
@josephferron7672 2 жыл бұрын
I’m building my own home hiring contractors myself. I’m glad I came across this video. I hear people say use the the ridged. I’m going with the flex. Thank you for the tip.
@Faruk651
@Faruk651 2 жыл бұрын
do not use flex, it is crap.
@josephferron7672
@josephferron7672 2 жыл бұрын
What kind of reasoning to you have to back it up? What problem did you have with it?
@Faruk651
@Faruk651 2 жыл бұрын
@@josephferron7672 Just use your logic. How air acts, long term effectiveness. Only advantage of flex duct is that it is easier and cheaper. In every other aspect rigid duct is superior. You are building your own home. Do it the right way. This guy is a contractor and he is biased. Because he wants to get it done easy way.
@Faruk651
@Faruk651 2 жыл бұрын
Only go with flex if it is absolutely necessary. If rigid ducts can be run in your house, flex shouldn’t be an option. I never seen these flimsy flex duct in Canada. Must be a Murican way.
@josephferron7672
@josephferron7672 2 жыл бұрын
@@Faruk651 I greatly appreciate your response. I’m going to have 2 units. One for downstairs and one upstairs. My runs will not be no more than 30 feet. Installing in crawl space and upstairs will be all in the attic. No ductwork will be in walls. I also live in southeastern US.
@nightone9720
@nightone9720 2 жыл бұрын
I like doing the main plenum and then for long runs i like doing half the run in ridged, then I do the rest of the run in flex. I think it's a great way to save money and still utilize the best part of using flex duct aka (making a weird offset easier).
@marcosantonocito8997
@marcosantonocito8997 2 жыл бұрын
What are your thoughts on insulating ridged duct ? I m recently renovating my house and my system is located in the basement utility room I was thinking of making it more efficient also redirecting some of the ridges duct work . Any recommendations ?
@brandonammons3661
@brandonammons3661 2 жыл бұрын
Generally duct work in conditioned spaces do not have to be insulated.
@davidwooten3430
@davidwooten3430 3 жыл бұрын
What about the durability of metal vs thin plastic?
@mrklean93
@mrklean93 3 жыл бұрын
Someone should take a high quality plumbing camera and show what the elbows look like internally in an install, live, no demo's or lab conditions, real world conditions. I have a feeling that would gain a lot of KZbin traction.
@Lawiah0
@Lawiah0 3 жыл бұрын
"Save where you can, spend where you must."
@allengreen7483
@allengreen7483 2 жыл бұрын
My mobile home has flex in the crawl space. All chewed up by rats. We've been paying what adds up to thousands of extra $ over the last 5 years in utility bills since we moved here, but the rats have been really comfy and we found notes down there thanking us. We just got an inspection and figured it out, stupid me.
@billnipp2309
@billnipp2309 3 жыл бұрын
Im thinking of replacing my rigid takeoffs with flex because they have a few elbows which slow the airflow. Question is, should I replace those takeoffs with the same diameter as whats there or should I increase the diameter? thank you
@nickbrunette8292
@nickbrunette8292 Жыл бұрын
Dont do it, sheet metal will hold up better over time and the rigid takeoffs have less friction. If you wanted to do what your talking about upsize the takeoffs from a 6 inch to 7 inch rigid.
@ryanroberts1104
@ryanroberts1104 3 жыл бұрын
I have an interesting problem here in NC - all insulated flex duct in the vented crawlspace...the main trunk coming out of the air handler drips with water from the humidity. Even though it's insulated! It's usually 80%+ humidity down there, but I can't do anything about that unless I seal the entire crawlspace - it's just as humid outside!
@6stringsandapick
@6stringsandapick 3 жыл бұрын
Encapsulate the Crawlspace, that humidity will drop overnight!
@thetechbuilder2464
@thetechbuilder2464 3 жыл бұрын
The group of flex ducts like the one that was showcased in this video would deteriorate over a relatively short period of time. Well, all polymers deteriorate. But, the lifespan of ductwork to be around 30 years (depending on the conditions) or so is not adequate. The point about low performance increment is inadequate because people choose one product over the other for reasons not only performance, but also service life and maintainability as well as cost.
@aayotechnology
@aayotechnology Жыл бұрын
So which do you recommend?
@thetechbuilder2464
@thetechbuilder2464 Жыл бұрын
@@aayotechnology It depends on specific user requirements and needs. If the goal is to provide a makeshift housing, flexduct is extremely cost effective and easy to install. Many other uses for flex duct other than that. However, if you add longevity and maintenance into the desirable properties of your structures, along with other parameters (area size, etc, climate, type of structure, etc), rigid duct can be a better alternative. Usually such videos imply "best practices", but there is no solution that fits it all in reality.
@TeamCuellar
@TeamCuellar Жыл бұрын
Hi Jordan, I know this is an old vid but I am having an argument and hope you can settle it. When you run Flex Duct as you mention in your video, is there ever a time when an installer would put a joint in between a run from the main duct in an attic down through the walls and ceilings of a 2 story home to the final ceiling vent on the first floor? My assumption is, there is much less chance of a leak or blowout of a duct using flex duct to make that run because there would be no connections needed in any of the walls or ceiling/floor joists between the first and second floor. Just the initial connection point up in the attic of the 2 story home and the final vent at the bottom.
@davidbleil9934
@davidbleil9934 3 жыл бұрын
From a professional HVAC technician who is building his own house I'm not putting in any flex duct. A properly sized and installed sheet metal trunk system is the best way to go for even, quiet, and comfortable air distribution with long term performance. You're correct it needs commissioned for it to work properly, but it all starts around a good design and proper execution. Thus rarely happens and that's why people make the octopus nest for duct systems. Flex is quick to run and cheap to buy causing a poorly designed and executed system for as little money as possible. The main reason for cheaper installs and poor work is because the HVAC is the most expensive mechanical bill for the house. Plumbing and electrical are hard to cut the cost down that much. HVAC is always the easiest way to cut a large amount of cost out of the equation.
@jadfaris4119
@jadfaris4119 2 жыл бұрын
In short.. just be good at your job. I'm in hvac.. I 👍
@aayotechnology
@aayotechnology Жыл бұрын
Did you line those metal ducts with insulation or add it to the outside?
@davidbleil9934
@davidbleil9934 Жыл бұрын
@@aayotechnology I wrapped the outside for the duct running above my garage, but no insulation for the duct in the basement
@jl9678
@jl9678 3 жыл бұрын
I love the contra position. Instead of saying, like everyone else, spend 20k more to save $20 a year, you said, the extra cost is not worth the improvement in performance. America needs to hear this!
@jaandel1
@jaandel1 3 жыл бұрын
Mat risinger like to spend thousnd to save dollars juat to prove his point hahahha
@benkuxhouse787
@benkuxhouse787 3 жыл бұрын
I’ve seen jobs where there’s been way too much flex in the system doesn’t work. Flex no matter how you run it has friction. And I’ve seen friction loss caused equipment not to work not to cool A house. What I don’t like about this is that flex duck will be buried under a mountain of sheet rock and paint if anything goes wrong with it guys cut it all out to fix. If you have low airflow because of all that length of flex run there’s nothing you can do about it. I think he’s trying to save too much money on his installs probably have an illegal aliens installing flex all over the place. That’s how a lot of builders are and I’ve had her go out and tell the homeowners you’re screwed more than once in my career. And that’s also on Multi million dollar homes that the builder went cheap ridiculously cheap on the HVAC the most important part of the house
@lizardman1303
@lizardman1303 2 жыл бұрын
Feel thats the way solar power is
@jadfaris4119
@jadfaris4119 2 жыл бұрын
I am an hvac contractor. Flex is much more likely to suck. Poor airflow. This guy is full of shit. Once the squirrel chews it up..
@brandonammons3661
@brandonammons3661 2 жыл бұрын
@@jadfaris4119 good duct work isn’t cheap and cheap duct work isn’t good.
@BREich-7
@BREich-7 3 жыл бұрын
Had brand new metal duct installed in my home professionally. Everything had mastic and insulation with the silver supersonic tape on all the joints. Had it for many years not knowing that because of the high humidity location of our home, that insulation wasn't doing diddly squat other than becoming soaked. And I mean soaked - so badly that it began dripping and ruining drywall. Removed that soaked insulation, replaced it and at the end of that summer season, it was completely soaked again. Ripped it all out, replaced with flex and problem solved. Plus it's so much quieter and a conversation in one room is not transported to every room with a vent! Maybe hard pipe is great for low humidity locations or if it's inside the heated/cooled space. But lesson learned in the south!
@j.walker3498
@j.walker3498 3 жыл бұрын
Thats what i don't like about rigid, you get one little air leak in the insulation it starts making condensation soaking it which tears more places.
@ELIRAXPRT
@ELIRAXPRT 3 жыл бұрын
What area do you live in? I've never seen ducts have condensation in my area
@TheAnimeAtheist
@TheAnimeAtheist 2 жыл бұрын
@@ELIRAXPRT In super humid areas like the american south where the ceiling cavity is not sealed well or just in the attic you can have high humidity in there. At that point any improper insulation on the ducts will cause condensation to form on the rigid pipes. For many places in modern homes however, condensation from rigid duct can be a sign of improper AC function, rather than an insulation issue.
@grandnagel
@grandnagel 2 жыл бұрын
Might have been cheaper to leave the metal and spray foam the roof. Cheaper... And problem solved.
@tysleight
@tysleight 3 жыл бұрын
Mice love flex! If you live outside of the subdivision or in the beginning phase of one your going to get mice. I see lots of droppings in flex with custom exits for the mice. That has been what I've seen in remodeling homes. This is with mostly crawl space installation.
@GenZyannd
@GenZyannd 3 жыл бұрын
the biggest problem with flex in vented attic are those darn rodents. yes, thermal is an issue but not yet hazardous.
@TheRoadTaken
@TheRoadTaken 2 жыл бұрын
Playing devils advocate, couldn't the flex duct simply be replaced if mice become a problem?
@tysleight
@tysleight 2 жыл бұрын
@@TheRoadTaken yes, but who wants to come up with thousands of dollars to replace damaged ductwork.
@TheRoadTaken
@TheRoadTaken 2 жыл бұрын
@@tysleight flex duct in my area is not that expensive last I looked but maybe COVID has affected the pricing too.
@tysleight
@tysleight 2 жыл бұрын
@@TheRoadTaken mostly labor. Our area is years out, even unlicensed uninsured guys are booked out and can charge anything they want.
@T_157-40
@T_157-40 3 жыл бұрын
Question: can you spray close cell foam around rigid duct (metal) if its designed and sealed properly.
@AaronHope_Sow
@AaronHope_Sow 3 жыл бұрын
I'm just here for the 80's theme music
@GreatDivideSven
@GreatDivideSven 3 жыл бұрын
what about the green screen schtuff? the videos are like a modern soup with an 80s bouillon cube
@AaronHope_Sow
@AaronHope_Sow 3 жыл бұрын
@@GreatDivideSven exactly. Here for it all!
@JoeyRam.
@JoeyRam. 2 жыл бұрын
I have one of my rooms warmer than the other 2 guess rooms and is the second one after the master. I don't know what to do in this situation.
@steven7650
@steven7650 3 жыл бұрын
The metal coiling that provides the shape of the duct internally. IS also what creates all the texture internally breaking laminar flow and requiring more CFM to overcome it.
@FatManDoubleZero
@FatManDoubleZero 2 жыл бұрын
The "spiral wire" inside the flex tube can be thought of as being very similar to the "rifling" found in most gun barrels." The air flow over the "rifling" of the flex duct is therefore "spinning" or "rotating" causing the air to become more "dense" and "concentrated" - just like happens within a storm cell in nature . Further, the air flow dynamics and efficiency is most likely"enhanced" to a greater degree than it is "degraded" or "corrupted."
@impactodelsurenterprise2440
@impactodelsurenterprise2440 2 жыл бұрын
You have any source to back to up?
@steven7650
@steven7650 2 жыл бұрын
@@impactodelsurenterprise2440 just thinking back to fluid dynamics in undergrad.
@impactodelsurenterprise2440
@impactodelsurenterprise2440 2 жыл бұрын
@@steven7650 I was replying to fatman
@jesusc2me
@jesusc2me Жыл бұрын
I thought for sure that you were in front of a green screen. Mind blown at the lighting you have set up in there
@workingballer
@workingballer 2 жыл бұрын
By California Mech Code, I can only use 5 feet of flex duct for commercial applications. That's probably the main reason why I don't use flex for main trunks. I'm guessing long run of flex duct is allowed for residential homes?
@wjthehomebuilder
@wjthehomebuilder 3 жыл бұрын
I'd like to know what the cost is up front to properly design the duct system. Because, when you add that to the HVAC budget, it doesn't seem like it would be much higher to go with the VRF as you discussed in yesterday's video. I don't know. Maybe I'm lucky to have an HVAC guy that installs my mitsu mini splits to where I end up being into them for 1/2 of what the normal cost is. I don't do conditioned attics, therefore I will refuse to put a ducted system up there. So VRF has been the best choice for my houses. I do a single 18K BTU unit (20.5 SEER) for around $3000 installed.
@bamc3835
@bamc3835 3 жыл бұрын
is vrf the unit that replaces hvac units more commonly used? i am a lil confused so pls help...i thought at first ervs replaces the hvac unit but then found out that is only for fresh air supply
@wjthehomebuilder
@wjthehomebuilder 3 жыл бұрын
@@bamc3835 Watch Jordan's video from 2 days ago. VRF is 'variable refrigerant flow' which is the way a ductless mini split heat pump operates.
@jaimedpcaus1
@jaimedpcaus1 3 жыл бұрын
Great video. I seem to have "Flex" duct in my home attic. Three questions: 1) where do I check to ensure dust is not getting into the air flow? 2) From High to Low quality, which one is the best "Flex" duct to install in my home? and 3) How ( as a home owner ) do I know that the "Flex" is installed correctly (what can I check)? Thanks
@leeknivek
@leeknivek 2 жыл бұрын
Dust would enter on the return side of the unit, where your air filter should be.
@jaimedpcaus1
@jaimedpcaus1 2 жыл бұрын
@@leeknivek Great, I'll look into that.
@TheAnimeAtheist
@TheAnimeAtheist 2 жыл бұрын
1) dust will always get into your airflow that's what your filter is for. Other than visual inspection of an entire flex duct for the return, if you have a flexed return you probably don't, you really can't that well. 2) higher the rvalue the better I'd say, but don't quote me on that 3) Basically, no sagging, the duct should be taut. It also should not be cinched down by any hanging supports such that it is constricted. Any obvious 90s that are not using a rigid are also bad
@bamascubaman
@bamascubaman 3 жыл бұрын
Like you say, a lot hinges on the installation, if you are getting adequate airflow, cool. That corrugation inside the flex duct CAN NOT flow as much as a identical sized rigid duct. Immaterial if flex is going to be able to supply an adequate amount of volume but the difference is real & easily quantifiable.
@jagslion3
@jagslion3 3 жыл бұрын
Jordan, how much more would have rigged been on that project?
@guytech7310
@guytech7310 3 жыл бұрын
The inner plastic liner is going to fail over time as it become brittle and splits. Then your air is likely to get contaminated with Fiberglass, which you will be breathing in. You might get 8 to 20 years before the inner liner fails requiring replacement.
@ELIRAXPRT
@ELIRAXPRT 3 жыл бұрын
I know a facilities manager at a hospital that ran into that problem with some flex having particles entering the airstream. They now require hard duct as much as possible and only allowed flex where hard duct couldn't possible be installed due to clashes with other materials and in very short instances just to attach to a diffuser
@samuelkirkland8976
@samuelkirkland8976 11 ай бұрын
Sorry sir, but that is absolutely false. Polyester film does not get brittle over time, UNLESS it is exposed to ultraviolet light (usually sunlight).
@cheetahb5
@cheetahb5 3 жыл бұрын
I just completed a project re-doing the flex duct in my attic. Original builder did a piss-poor job, leaving metal supply and distribution plenums uninsulated and the flex was installed very sloppy and was only an R4.2. I built my own distribution boxes with proper design and insulation and replaced all the duct with R8 flex. I used hard elbows where it turns to connect to the ceiling registers and for turns coming off the distribution boxes. I made sure to stretch the flex tight to eliminate as much of the accordion effect on the flex walls to reduce airflow resistance as much as possible.
@gnarnal
@gnarnal 2 жыл бұрын
Did you notice a big difference in performance after the upgrade?
@cheetahb5
@cheetahb5 2 жыл бұрын
@@gnarnal in terms of air velocity, not too much. There are some issues with the design of the main take-off at the furnacethat I feel are impacting air flow. But the heat last winter was definitely much warmer than it had been. The upstairs was getting even hotter than before. So I’m that respect, it did improve. Much less heat transfer between the attic space and the ducts.
@fernando651
@fernando651 Жыл бұрын
is it harder to clean flex duct?
@saintmichael36
@saintmichael36 3 жыл бұрын
You are installing flex duct because you can make more money as a contractor on reduced time and material costs. • Centrifugal blowers do not push air as a positive displacement pump does, they circulate off of the pressure differential created through proper design. • Noise in ductwork comes from velocities that are too high which would be from undersized duct or a collapsed flex duct. • Installing flex duct in structures that will be covered in drywall will cost the owner a lot of money in the future as flex does not have the lifecycle expectancy of hard duct. • ASHRAE and ACCA have standards in place which recommend best practices for the greatest efficient and life cycle of the equipment. • Flex duct has a higher friction rate as compared to Ridgid duct which means you will pay more money in kw to move the same amount of air through flex rather than Ridgid. • Installing a high quality system usually involves training which is governed by standards. What training and standards are you commissioning your work against? If you had the money to build a brand new house, would you install flex or Ridgid and why? Give customers the best, give them what you would give yourself and if you are going to reference “not that much” or “not that big of a difference”, than at least have the decency to give actual numbers as a true technician would.
@helenjefferson438
@helenjefferson438 3 ай бұрын
Rigid is the correct spelling. Other points well taken.
@juggalo450
@juggalo450 Жыл бұрын
Is this better then Fiberglass duct
@sumtingwong4997
@sumtingwong4997 Ай бұрын
South Florida A/C guy here. My dad died and before I sold his house, I upgraded his AC unit. When I inspected the attic, I found his 28-year-old flex looking almost new. When I removed his air handler and was able to look up into his plenum, the inner liner looked great as well. Don't get me wrong I've replaced lots of deteriorated flex I'm just saying not all flex manufacturers are created equally. the brand you choose is also important.
@MAGAMAN
@MAGAMAN Жыл бұрын
i hear the higher efficiency systems wear out faster and end up costing you more money over time than the older systems. They are also much harder to get replacement parts for.
@jondowd11
@jondowd11 3 жыл бұрын
Who do you have validate system flows at the end of the project? Does the mechanical installer balance, or do you go with more of the commercial approach and have a NEBB certified TAB contractor balance the system?
@halbritt
@halbritt 3 жыл бұрын
Using a balometer isn't that complicated.
@jondowd11
@jondowd11 3 жыл бұрын
@@halbritt I've used them quite a bit in my job as an HVAC controls technician. I'm just curious if they go as far as having a third party validate the system.
@lsellclumanetsolarenergyll5071
@lsellclumanetsolarenergyll5071 3 жыл бұрын
Jordan agree to disagree. If you building typical USA stick houses flex duct is the best way to go. But if you building industrial buildings, Steel, or Concrete buildings than for sure ridged is much better on the main run's and only Flex at the end. Also on Mobile homes I go ridged for reason so animals can't destroy and also it's easier to maintain and service. So it really comes down to what building you have.
@stephenbrunner2543
@stephenbrunner2543 3 жыл бұрын
I replaced all my flex with hard metal. Why? Rodents eat through the flex duct. Got sick if dealing with it and ripped it as out. No more problems. My house has crawl space not a full basement which likely.make a difference.
@JordanSmithBuilds
@JordanSmithBuilds 3 жыл бұрын
Installation location definitely makes a difference!
@doct0rnic
@doct0rnic 3 жыл бұрын
@@JordanSmithBuilds is there a way to prevent this? I plan on installing this in a crawl space area.
@SophiaAphrodite
@SophiaAphrodite 7 ай бұрын
I would assume if you have gravity on your side these work just fine. Might not be the best option if you are pushing uphill.
@Ed-jg3ud
@Ed-jg3ud 3 жыл бұрын
U should do some pro/con videos with Matt Risinger on these topics. Would be informative and ripe for some humorous satire between u two:)
@ecostudio1044
@ecostudio1044 3 жыл бұрын
what is that wood "truss" behind you? and why is it orange on the face of it.
@timkr66
@timkr66 3 жыл бұрын
I think that is the LP stuff. I saw RR Buildings visited a house he was building using some new LP framing.
@JordanSmithBuilds
@JordanSmithBuilds 3 жыл бұрын
LP SmartStart LSL's. kzbin.info/www/bejne/rqDNomyig5WjZ7M&ab_channel=JordanSmith
@FrancoisEdmondOfficial
@FrancoisEdmondOfficial 3 жыл бұрын
Matt won't be too happy hearing this
@A-Sidhu
@A-Sidhu 3 жыл бұрын
It seems odd to have such large openings in the joist (TJI) webs from the ducting. Am I wrong?
@brianlorge906
@brianlorge906 3 жыл бұрын
Those floor joists are designed to be able to have large openings cut in them. Just not the top and bottom plates.
@A-Sidhu
@A-Sidhu 3 жыл бұрын
@@brianlorge906 That hole size is probably the max allowed depending on how far away it is from end supports(wall). I believe its max 8 inch diameter hole on a 12 inch deep TJI joist if supports are minimum 8 feet away. I personaly wouldn't do that to be safe. It just looks weird and sketchy. Thanks.
@samuelkirkland8976
@samuelkirkland8976 11 ай бұрын
You are absolutely correct. The building plan will give you the maximum size hole that should be cut in pre-fab joists, and it's alot smaller that shown in that video.
@LewisRenovation
@LewisRenovation 3 жыл бұрын
Seems to be a lot of videos about F1 installs when Lexus will do. Thanks for the video
@2point2
@2point2 3 жыл бұрын
🧐
@jl9678
@jl9678 3 жыл бұрын
F1 installs when toyota corolla will do and require less maintenance to boot
@junangeles
@junangeles 3 жыл бұрын
He explained flex duct better than my hvac installer. I have some questions if you dont mind.
@you2282
@you2282 Жыл бұрын
California is considering all rigid except the last 6 ft. Code here is a blower test so you won't get away with leaking ducts. So with metal ducting and better airflow you can have a smaller blower or at least set at a lower speed which means less energy used. But as an installer I love flex duct. Put the furnace in a central location pull all flex duct so no sags or bends and you can have a good system.
@ernieforrest7218
@ernieforrest7218 2 жыл бұрын
So aside from your personal views, or differences in cost of the system, what type of duct systems are used in schools and hospitals? And why is that?
@monteglover4133
@monteglover4133 3 жыл бұрын
The round rigid duct generates about half the turbulence of flex though most systems will allow for this I’m still a rigid user although I will agree that flex duct does antinuate wait sound much better. Ductwork in unconditioned space is to be avoided at all cost, well almost. 40 years in the frigid north.
@mikelliteras397
@mikelliteras397 3 жыл бұрын
So long as you size it correctly, you don’t pinch it or bend it too far, flex is better in almost every situation. When you size it you have to use a lower velocity also. So where you might get away with a 6 inch in metal pipe, you probably need a 7inch in flex. If you can run a board trunk line with flex take offs. In new construction, I would only use flex unless it’s a custom house with a correct budget. I would never use metal pipe, with wrapped insulation. There are very few people that will wrap it correctly and you will have condensation leaks, also people will set stuff on it and it will compress the insulation and leak where flex will move more and you’re less likely to leave something on it. You won’t use the difference in cost of the duct work on any extra electricity. There are so many other things that will cost you more money than using flex over rigid duct, especially when it’s sized correctly.
@jesselamb991
@jesselamb991 2 жыл бұрын
WHAT ABOUT DUCT CLEANING!! I have worked in HVAC/R and plumbing and heating for 15 years and have used my fair share of flex duct it most certainly has its place and application. I recently did duct cleaning for the first time and the rotary brush used to clean ducts would easily destroy that interior wire coil and get wrapped up inside the duct. My concern is that now that duct has a hole in it buried somewhere inside a finished home years after the install was completed and now has a damaged heat run that no longer delivers air. There ARE more commercial flex duct options that are made of a much more durable interior liner, in Canada it’s called SLP flex.
@spatton7875
@spatton7875 Жыл бұрын
In the southeast I very much prefer rigid for 1 simple but persistent reason. Rodents! The can’t get through rigid. I do use a short section of flex at the air handler for noise reduction and ease of install but rigids pros outweigh the cons in this area for that reason. Yes I know if the house is built correctly the likelihood of rodents getting in is less but they will get in at some point and it can be a huge pain trying to get them out. Oh and unfortunately very few houses are built with this in mind.
@mikimiki195
@mikimiki195 2 жыл бұрын
You drilled trough that joist is that ok to do I have to jump over
@Greck1982
@Greck1982 Жыл бұрын
They say that flex will eventually have cracks and it’s fiberglass insulation will ended up in the air, so it’s kind of unhealthy ?
@House_Of_Sports
@House_Of_Sports 9 ай бұрын
I would personally use metal elbows when using flex. Having flex bend at a 90 is terrible
@lajibarita2935
@lajibarita2935 2 жыл бұрын
😭 will you install in Hamilton tx no one come here
@scottbalkenbush2
@scottbalkenbush2 2 жыл бұрын
Size matters.....there are sizing charts available to assure that you are using the equivalency to rigid duct. Best practice installation is up the the installer. If installation is done wrong, It will not work properly. I have use flex for years, with no issues.
@dropcheekelbow9110
@dropcheekelbow9110 2 жыл бұрын
Only problem is you should only use flex in places you can access like attics, or crawlspace. You shouldn't bury flex in a wall or ceiling. -Sheet metal worker for 27 years and counting.
@geraldgilpin1966
@geraldgilpin1966 Жыл бұрын
This guy calls a 40 ft run of flex is a short run. That's rediculous.
@dropcheekelbow9110
@dropcheekelbow9110 Жыл бұрын
@@geraldgilpin1966 agree. 1/2 box max and be prepared to T.A.B.
@robwalker8530
@robwalker8530 3 жыл бұрын
My house has a hybrid system, rigid duct for delivery, flex duct for return.
@FrankSmith116
@FrankSmith116 3 жыл бұрын
I agree about everything you said except one thing. Longevity. I would have no problem with flex duct in a new build. Get 50-100 years down the house and there is no way that everything isn't going to have to get opened up to redo the work. I say plan for the long haul. That plastic in those flex ducts get brittle and deteriorate especially if they ever come into contact with condensation, or any pest in the home. When someone tries to tell me how to do something I always make them qualify their statement if its about aesthetics, functionality or longevity. Aesthetics is not the most important thing here assuming both jobs are done cleanly. Functionality is fine either way although there are arguments either way. On longevity I see it as no comparison. I say build things that might last for hundreds of years. All the building science goes out the window if you have to gut half a house to retrofit mechanics at a fairly early point in the life span of a house. Things go together best the first time and should stay that way as long as possible.
@mikelliteras397
@mikelliteras397 3 жыл бұрын
I’ve been back in attics that have 30 year old flex and rigid board, and there’s no difference, the worst is usually wrapped metal. I’m not talking about the old owl flex systems, but the Mylar systems. I’m in Ft Lauderdale where 130 deg attics. If I bought a 25 to 30 year old house, I would replace the ductwork anyway. I wouldn’t want other people’s mildew growing in my ductwork.
@rasi9845
@rasi9845 3 жыл бұрын
"or any pest in the home". Beware the rat & mice monsters. Even squirrels. Those tiny rodent teeth can tear up your peace of mind like crazy.
@Chrissers2010
@Chrissers2010 3 жыл бұрын
This is the type of video that needs data to have credibility.
@Zorlig
@Zorlig 3 жыл бұрын
I had flex ducts and very low airflow. I had them installed with metal elbows and airflow was greatly increased.
@halbritt
@halbritt 3 жыл бұрын
I think this is the part that matters. In some systems, flow velocity matters and must be managed accordingly. Rigid is more predictable in this regard.
@andrewdiamond2697
@andrewdiamond2697 3 жыл бұрын
I did the same. Metal elbows often correct flow and balance issues.
@TheAnimeAtheist
@TheAnimeAtheist 2 жыл бұрын
Yeah it's been shown that 90s especially hard 90s in flex are so detrimental to air velocity by having such a stupid high equivalent length that you pretty much have to use rigid 90s when you need to make a turn.
@freddya2900
@freddya2900 3 жыл бұрын
collects a lot of mold. very bad ,, cannot be cleaned. how do i replace it, imagine
@elevatedsciencesllc8089
@elevatedsciencesllc8089 5 күн бұрын
So if you're putting it in conditioned space why are you using insulated duct?
@ryanmcgowan3061
@ryanmcgowan3061 6 ай бұрын
*Flex can be more efficient than rigid.* Here's why: Flex can be routed often in a direct line to the registers with small bends under and around obstacles, whereas rigid will usually go at 90° angles, adding length to the overall system. Additionally, friction losses are usually measured in equivalent length, and just one fitting adds 10 to 100 feet of equivalent length. Between both of those factors, you're going to get *more friction on a rigid duct* than flex taking the shortest line with zero fittings. If there is a friction loss problem, it's also not a matter of what type of duct so much as what size you specified. If there's a friction problem, just go up one size. That's it. Also, a round duct will have less friction than a rectangular duct of equal section area because a circle is the absolute minimum surface per section area. So where you lose in flex due to the ribs, you gain due to geometry (assuming you're using rectangular rigid. If you compare rectangular rigid to flex, it's almost identical in friction. For instance, an 8" flex duct has a section area of 50 sq. in., and friction loss of 0.12 inches (100' @ 200CFM). A 5x10 duct is also 50 sq. in., and has a loss of 0.10 inches. A 0.02 inch difference is not perceptible, especially over 100 feet. Now add fittings to the rigid, and suddenly it's much worse than flex. The absolutely best flow you can get would be rigid round with very long press-formed sweeps going in a direct line to the registers as possible, and no one is doing that. So installed correctly, flex is ideal in most cases.
@jamesstiltner8885
@jamesstiltner8885 Жыл бұрын
In air craft ribbits are flush with the skin of the plain had it had the crinkle of the inside of the inside of the flex duct it may not fly do to air flow / efficiency use when needed only and quit the bull ship
@boedillard8807
@boedillard8807 2 жыл бұрын
It is me, or is there a lot of stuff going through the support structure of that house?
@indychuckluck
@indychuckluck 10 ай бұрын
Done right, I would take the flex duct .. thank for the video.
@ZergZfTw
@ZergZfTw 3 жыл бұрын
If you want to save money, just build a smaller house, air seal it well, and stick lots and lots of fluffy stuff in the walls and roof. Rigid vs. flex vs. VRF is arguing over pennies. There are much bigger thermodynamic fish to fry. Especially the way most US houses are built, too big, under air-sealed, under-insulated, and wore, over glazed with crap quality windows.
@robertrusso5525
@robertrusso5525 3 жыл бұрын
ZergZfTw Amen!
@jl9678
@jl9678 3 жыл бұрын
Who is the size police that determines if a house is too big, too small, or just right?
@sillyguy9828
@sillyguy9828 3 жыл бұрын
6 feet or less is how much flex is supposed to be used on commercial jobs but when it comes to houses they can flex the whole thing
@lyndacrockett2863
@lyndacrockett2863 4 ай бұрын
In indian river county florida every single house has a wall banner unit in the master bedroom because the design of the air conditioner prohibits equal cooling in all rooms. Nobody is addressing this.
@lizardman1303
@lizardman1303 2 жыл бұрын
Went up to the attic yesterday day my ducts look like a damn spider
Flex vs. Metal vs. Duct Board: Differences and Use Cases
5:35
Matt Risinger
Рет қаралды 68 М.
Ouch.. 🤕
00:30
Celine & Michiel
Рет қаралды 23 МЛН
Useful gadget for styling hair 🤩💖 #gadgets #hairstyle
00:20
FLIP FLOP Hacks
Рет қаралды 10 МЛН
Fast and Furious: New Zealand 🚗
00:29
How Ridiculous
Рет қаралды 44 МЛН
Discussing Ducts Types and Tips
17:24
HVAC School
Рет қаралды 79 М.
I Should’ve Known BETTER…| HVAC Install
13:05
Quality HVACR
Рет қаралды 289 М.
Rigid Metal vs Flex for HVAC Ducting
4:51
Matt Risinger
Рет қаралды 457 М.
Plenum Issues - Fixing Badly Installed, Leaky Ductwork In An Attic
5:27
Diversified Energy
Рет қаралды 152 М.
How To Install Ductwork In A Basement | DIY Finished Basement Renovation
32:16
New Construction HVAC - Here's My Favorite System
4:57
Matt Risinger
Рет қаралды 362 М.
HVAC Ducts Reality Check: Are Ductwork Systems Dumb or Essential?
11:05
Home Performance
Рет қаралды 96 М.
How to insulate Metal Ductwork with foil insulation - for HVAC installers
8:52
Clean Air Heating & Cooling
Рет қаралды 70 М.