Sir, Which make DC selection switch available in the market
@Technicalcobra2 ай бұрын
Why required double DC supply or separate DC for CRP
@relayprotectionelectrical2 ай бұрын
Because in CB there exist two trip coil... And in CRP there exist two main relay for voltage level 66 KV and above i.e. Main-1 distance relay and Main-2 distance relay .. therefore separate DC supply are given for main-1 and Tc-1 and main-2 and Tc-2 because failure of one DC will not impact relay and cb operation during fault condition.
@relayprotectionelectrical2 ай бұрын
Please enroll for course on Transformer Protection on udemy www.udemy.com/course/protection-used-for-power-transformer/?couponCode=931DB6D9C361B37E48B6
@Technicalcobra2 ай бұрын
@@relayprotectionelectrical what have position of DC selection switch in normal condition if both DC source available? Independent..........?