When I connect pressure transducer it's showing some pressure instead of zero how to set it zero
@generaltechnologyknowledge51653 жыл бұрын
Dear sir, You can adjust the small resistance on analog expansion module. Thanks
@waleedellafi8286Ай бұрын
Hi ,, We are using S7-200 with an expansion module 6ES7223-1BL21-0XA0 and we would like to replace this module with a newer version 6ES7223-1BL22-0XA0 since the older version is no longer produced. Do we have to make any hardware configuration to when installing the new expansion model?
@namasthethalir2 жыл бұрын
Sir cotrust thermocouple module can we connect siemens s7-200 plc
@shahaalom68913 жыл бұрын
If I add an expansion modules , do I have to configure the hardware in software or direct give serial address.
@generaltechnologyknowledge51653 жыл бұрын
Dear sir, For PLC S7-200 we no need to configure the hardware configuration, but the address will count continue from main CPU. Thanks