I have Following Questions 1. For Intake, Do we require a sand trap Intake air louver or is Normal Weather Louver will work? 2. From which Standard did you get the Maximum Allowable Temperature? 3. The Intake Air flow-rate Which You have calculated, Does it require a separate Exhaust fan or Radiator Fan will Exhaust this Flow rate?
@DungNV_IBD6 ай бұрын
i have the same as 3. Pls repply.
@SalmanKhan-pb3fw3 ай бұрын
Very well explained sir. Thank you 🙏
@mohamadhanis95712 жыл бұрын
Great video.. but why you're using "exhaust gas flow rate" instead of "combustion air inlet flow rate" from the Caterpillar datasheet?
@smarnam Жыл бұрын
Wrong data taken
@jerinouseph1719 Жыл бұрын
I have the same doubt...
@mohdshadab-ug2ut Жыл бұрын
Thanks for informative video, do you have any video, maintain sound proof generator design.
@promotingcommonman2 жыл бұрын
Waqas bhi great video..
@MEPEngineeringTutorials2 жыл бұрын
Thanks Imran Bhai
@jabora58 ай бұрын
In a data sheet I have a btu per minute and kw per minute, in your calculation you have only in kw , how to coverts kw per minute or should I use it as kw directly ? Please advise Thanks
@matiascontrerasecheverria13 күн бұрын
Why don't you consider the heat of the radiator? , since this is finally also rejected in the room
@areenibdah20178 ай бұрын
Why you didn't consider the radiator cooling air flow into the intake calculations, you just considered the heat dissipation and air combustion?
@datngoba-m5f7 ай бұрын
I think this formula is only applicable for CAT genset. For Cummins, their datasheets are different, thus different and more simple formula. Intake louver size is calculated from the sum of cooling air and combustion air flow. By the way, I don't understand why you use exhaust gas flow rate in your calculation, I don't think it's correct. According to my understanding, you need to use combustion air inlet flow rate instead to calculate the intake louver. Exhaust gas flow rate is used to size the exhaust pipe, not the intake louver. Air and gas in the datasheet are different matter. Correct me if I'm wrong.
@engineeringdesignapplicati10104 ай бұрын
RIGHT
@neerajpant4459 Жыл бұрын
How do you calculate temperature at 122deg F by interpolation. Can you tell the formula?
@rangarajanramakrishnan32494 ай бұрын
How do we estimate the amount of Louvres required?
@reasmeingor19622 жыл бұрын
Hi sir. I have one doubt, regarding the T1 & T2. Does it constant values?
@MEPEngineeringTutorials2 жыл бұрын
T1 & T2 values as per geographical location. The values which I used here are as per UAE standard.
@azamalimohammed96742 жыл бұрын
@@MEPEngineeringTutorials Can you Share or Send a picture for UAE standard for T1 & T2 Temperatures
@aslsay8 ай бұрын
as site condition varies, not constant
@smarnam Жыл бұрын
Dear you taken exhaust flow rate instead of combustion air for engine please correct it
@datngoba-m5f7 ай бұрын
yeah I think it's not correct.
@noorulameen54002 жыл бұрын
1st Like and Comment
@franktchat2160 Жыл бұрын
Please, can you share with me this file ?
@MEPEngineeringTutorials Жыл бұрын
Please join channel membership and send an email request to get spreadsheet
@jahanzaibshafiq83832 жыл бұрын
Please Send Me This File Link here in the Comment.
@MEPEngineeringTutorials2 жыл бұрын
Kindly join channel membership to get access to this spreadsheet. Membership link is given in the video description. Thanks
@jahanzaibshafiq83832 жыл бұрын
@@MEPEngineeringTutorials You're saying about the Paid Membership. Okay.
@ammavvv2 жыл бұрын
You did not consider the net free area
@MEPEngineeringTutorials2 жыл бұрын
Louver area which I have calculated here is net area not gross area. If you want to check gross area of louver it would be twice of net area because we consider 50% net free area.
@ammavvv2 жыл бұрын
@@MEPEngineeringTutorials so 1000fpm is the face velocity?