I believe you are talking about dirt inside the pipe. Generally in many applications like Sea Water intake/ Sewage Application / brine solution dirt or slurry is part of medium.. hence an accuracy deviation is very less. Infact if installation is done properly then it is negligible. Yeah, you have to make sure the water flowing through should not be filled with heavy particle. It may damage the liner inside the sensor.
@bjorngriffiths86903 жыл бұрын
Is there any reason why totalizer 2 looses data when power has been removed or the head is removed but totalizer 1 doesnt loose its data
@davinderbhatti11 жыл бұрын
Regarding your calibration point. You can verify the flow values with flow verificator. In case you just want to tweak a bit + or - percentage of flow, then you can do that in service menu ˃˃˃˃ Correction Factor then enter the desired percentage.. Make sure u r doing this properly, as any change in percentage will also change it in flow outputs... hence, your plc/controllers will also behave in same way...
@HHafis-ik2rv2 жыл бұрын
i want to ask for help… about siemens flow meter mag 5000/6000… how to set/trimflow m3/h..for example..my pump is 1200m3/h… i want to set it to 1000 or 900m3/h… how to make it… set that where to use on mag 5000/6000fm. one more question… what when I turn off the pump reading is not zero… even 30.7m3/h… how do I want zero again… thank you very much.
@bitrusijudigal77584 жыл бұрын
Pls, I have a C02 ASCO flowmeter that's displaying Power on ...LUI ver 2.22. When ever theres power outage, and all the keys doesn't respond. I read through the manual but, can't find anything in relation to that. I need help pls....
@iosystems12255 жыл бұрын
Excellent ... thank u so much for this valuable tutorial
@engr.samsulalam85794 жыл бұрын
Sir I in my field there is a Siemens Mag 5000 flowmeter. Recently show on flowmeter is '' power on'' LUI Ver 2.22" is it possible to repair.
@RollyMacale11 ай бұрын
I have mag 6000 my problem is the totalizer can be reset it shown acces denied
@kukumungil4 жыл бұрын
how to change the unit to m3/second
@Rajasekar-gj7sj7 жыл бұрын
How do we get pulse output from TX, we have taken digital pulse to a digital counter omoron hc7x, when flow meter running am not able to get pulse o/p. Used 1 volume /pulse and with pwm of 520ms
@aaaaazzzz1008 жыл бұрын
Could you give my steps for Configuration and setting for Siemens F M Mag 8000
@tele12345tele11 жыл бұрын
If the pipe is dirty, or not properly cleaned, flow may not be correct. How can I calibrate the flow if I know How much should be.?
@mdaadilfiroz35254 жыл бұрын
kzbin.info/www/bejne/ZoTUiaWVac2coas
@mdaadilfiroz35254 жыл бұрын
Watch this video for flow meter calibration
@ahmedb5129 Жыл бұрын
Je veux des explication en francais
@hectorespinoza61166 жыл бұрын
I have a MAG5000, do you know if it possible to use the 4 to 20 mA aut to replicate de instant flow on a external digital display (i dont want to use the kit for remote mounting, it´s too expensive here)