Please to consider ambient temperature derating in cas operating over than the standard design temperature (IEC 30°C)
@thushanmadusanka88902 ай бұрын
Excellant brother...
@utkdimebag3 ай бұрын
Hi, at 19:36, if 90% loading is allowed, means 0.9 x rating = 1200 kVA which gives rating as 1333.33 kVA. I didn't understand why you used 10% of 1200 to calculate that? To me my approach seems more straightforward. But then our results differ. Please clarify, thanks!
@mohamedriyas4496 ай бұрын
Good presentation brother
@vanithareddy4462 жыл бұрын
In primary side we are having 2voltages like 11kV and 33kV which one we have choose
@electricalconcept329 ай бұрын
Your power supply authority which voltage level provided that voltage has to be chosen
@vanithareddy4462 жыл бұрын
And how to deside steps like 7steps 5steps tap changing in trafo side pls let me know
@electricalconcept329 ай бұрын
I will make separate video on it. Thankyou for suggesting the topic
@juliuscastillo2241 Жыл бұрын
Hi engineer. May i know how to calculate the required incomer breaker size for main mdb as per dewa regulation. TIA
@electricalconcept329 ай бұрын
I am making G+ 4 building design and already publish 5 videos on that please follow all those video to know how to calculate MDB main breaker size