Can you this usung xinje servo drive ? Please help me
@bartplackle32002 жыл бұрын
Quick question where did you find the modbus register definition, have a 9100 but cannot find it anywhere, much much thnx !
@ATOcom2 жыл бұрын
The special registers defined by each manufacturer have different meanings, so you need to find your manufacturer.
@makhgalsurenmyagmarsuren44515 жыл бұрын
How to know detail info about debugging software
@mitchimal3 жыл бұрын
Where can I find the manual with the 485 protocol for this VFD? It looks similar to the VFD I have not it's written horribly so I'm just a bit stuck. Cheers
@ATOcom3 жыл бұрын
If you buy a VFD from the ATO, then you can obtain the manual from us.If it's another brand, our manual doesn't seem to be of any use to you.
@mitchimal3 жыл бұрын
@@ATOcom well the codes look pretty similar but fair enough. This looks like a Chinese made unit?
@chickenz46043 жыл бұрын
what is the difference between using analog input output vs RS485 for communicating between PLC and VFD?? thx
@ATOcom3 жыл бұрын
When you know what an analog quantity is and what a digital quantity is, you will know it.
@chickenz46043 жыл бұрын
@@ATOcom it is not about digital , so you prefer to use RS485 for this type of application?
@ATOcom3 жыл бұрын
@@chickenz4604 Each has various advantages. RS485 (Modbus RTU protocol) is more suitable for centralized control or remote control. Many automated control systems use this control method.
@hassanabualrub4538 Жыл бұрын
how 0F A0 = 40 which converter you used?? if dec to hex 40 = 28
@ATOcom Жыл бұрын
0FA0 Hex=4000, you can regard it as 40.00Hz
@ATOcom Жыл бұрын
0FA0 Hex=4000 decimal
@tramtran55624 жыл бұрын
I'm newbie in Modbus. I don't know at 5:17s, you receive response data frame is 00 14, why is it 2.0 ( not 20) ?
@ATOcom4 жыл бұрын
The hexadecimal system is used here, 0014 (hexadecimal)=20 (decimal).
@tramtran55624 жыл бұрын
@@ATOcom Thank for your reply. But I read manual reference then I see the value must be 2.0 (not 20). I don't know that stuff.
@ATOcom4 жыл бұрын
@@tramtran5562 Under normal circumstances, the returned data can only be used after conversion, whether it is hexadecimal conversion or magnification conversion, as long as they are related, we can use it. Assuming that 0.1A is used as a unit (or accuracy), then 2.0A is equivalent to 20 units, which is 0014 Hex.
@saimakhan3588Ай бұрын
how can we do this esp32?
@МетодиПетков-щ1ф2 жыл бұрын
Hello. Thank you for this video. Can you explain me how convert P3.09 to hex number?
@ATOcom2 жыл бұрын
P3.09 is just "Communication configuration", why do you want to convert it to hexadecimal? Are you using ATO brand VFD?
@МетодиПетков-щ1ф2 жыл бұрын
Thanks for the reply. I see it's just for setup, but I had to give you an example to help you understand my question. The registers are described in this format in the user manual. I want to receive information about current, voltage, ask about the type of error, etc. How can I convert the registers set in this format ("P3.09" only for example) to hexadecimal numbers so that I can communicate with RS 485? Now I'm researching to choose which device to buy.
@ATOcom2 жыл бұрын
@@МетодиПетков-щ1ф 1. About communication. We don't need to convert P3.09 to hexadecimal. In the parameter expression of P3.09, it has units digit, tens digit, and hundreds digit. Each different decimal number represents a different meaning, such as P3. 09=163, its corresponding meaning is "Modbus RTU protocol, 1-8-1 without parity format, 9600bps". Different data have different meanings. We only need to correspond these communication data with the control terminal to communicate. These are common practices. 2. Information about reading or writing. Our user manual will show the special storage area inside the ATO VFD, we only need to read the data in the storage area or write the data to complete what you want. However, this part of data reading and writing are all in hexadecimal (machine language). 3. For more detailed instructions, please refer to our official manual, www.ato.com/Content/doc/GK3000-VFD-user-manual.pdf 4. Purchase link: 1-phase to 3-phase, www.ato.com/single-phase-to-three-phase-vfd 3-phase to 3-phase, www.ato.com/three-phase-vfd
@alfaelectricalsrajkot99014 ай бұрын
HOW CAN I INCREASE MY HZ TO 60 MAX WITH RS485
@abdelkarimkhelifi863 Жыл бұрын
Please i need this software
@z_review52472 жыл бұрын
Why 00 14 hex is 2 not 20?
@yashjoshi5 жыл бұрын
Can you please share the name of software used on PC?