HOW To flush a heating system with mains water easily!

  Рет қаралды 156,193

mmplumber

mmplumber

Күн бұрын

This heating system water definitely needs a clean! It looked like the flux needing flushing out or maybe a bacteria process is going on.
The easiest way to connect mains water to flush is though a magnet installed onto the pipework but this system doesn’t have one. Easiest thing for me to do is remove a radiator and connect onto the radiator valves.
Using some fittings from Tesla I’m able to connect hoses from the outside tap using hose lock!
Turn off all the radiators and flush one by one. Can even turn the boiler valves off to stop it going through or open just the boiler and close the rads to flush just the boiler.
Very simple way to flush pipework!

Пікірлер: 51
@petertapp1963
@petertapp1963 6 ай бұрын
Just use flexible tap connectors to attach to the valves
@MrMedicalUK
@MrMedicalUK 6 күн бұрын
I like the kicks on the copper that how i do them More bends the better
@tomsanders8714
@tomsanders8714 6 ай бұрын
Ok never mind the comment on the shorts version of this. Fantastic idea. Going to flush my system like this
@mmplumber
@mmplumber 6 ай бұрын
👊👊👊 good to keep the system clean
@KdeB
@KdeB 4 ай бұрын
I have been meaning to text you for so long. This past year you have helped me so much. Your videos are as clear as crystal compared to lots og guys on here, Thank you so so much for everything you do and everything you teach, you are the ultimate tradesman. From and an Irishman in London. If you are ever in London, hit me up I owe you lots of beer.
@rudebwoy6570
@rudebwoy6570 6 ай бұрын
I attach hose to a doc then put boiler in high rate , opem the doc and open the filling loop , watwr pumping round hot to free all that crao in rads and dumping thru doc , very affective and quick ! Add some mc5 before hand .
@Dylan-wo8yl
@Dylan-wo8yl 20 күн бұрын
Does it not mean any of the crap from the radiators is flowing though the boilers heat exchanger ?
@ya00007
@ya00007 4 ай бұрын
All that soldering. Just get two flexis, and 2 bits of copper pipe and attach the flexi to the lock shield valve. then attach the copper to the flexi, the other end of copper attach to hose pipe. job done. do this for both valves on the radiator side.
@deniskundrat7161
@deniskundrat7161 6 ай бұрын
Not sure how effective approach to flush the system would be by just opening a filling loop on boiler and flushing out through drainage valve under radiator ? This is a DIY man question, I might be missing something in my understanding. Thanks
@Baldylocks-w2j
@Baldylocks-w2j 5 ай бұрын
It would be as effective as shown in the video. Mains flushing does have its place with cleaning out new installs or recent installs. I would say using a Kamco with appropriate chemicals is better for systems really sludged up - especially on microbore, the high flow and turbulence really dislodges all the shit.
@lewiscook431
@lewiscook431 2 ай бұрын
Works an absolute treat mate. Continues water flowing through the system.
@LegendaryStee
@LegendaryStee Ай бұрын
​@lewiscook431 once you drained the system and all vent valves in rads are open would you need to close them again before opening the water valve?
@raulmartinezmoreno558
@raulmartinezmoreno558 6 ай бұрын
Buen trabajo me podria decir que es la pasta blanca que le pone a las roscas gracias
@acurrentname
@acurrentname 6 ай бұрын
Maybe you could use one of the top outlets on the radiator and then connect other hise to another radiator, closing one rad valve on each radiator, save taking radiator off? I have also wondered about using the filling loop under the boiler to flush system out? Anyway good video, thanks
@paulmurphy5396
@paulmurphy5396 5 ай бұрын
Brilliant idea going to try it should I let it run through the boiler as well or just the system thanks 👍
@1stevew
@1stevew 7 ай бұрын
Great video!!! Good use of the snazzy drain cock.... and very easy to send the water round in the other direction as well 👍
@mmplumber
@mmplumber 7 ай бұрын
Yeah I did love them valves for quick connection
@wr3099
@wr3099 7 ай бұрын
Good luck balancing those radiators again
@mmplumber
@mmplumber 7 ай бұрын
Doesn’t take long
@jameswright7375
@jameswright7375 7 ай бұрын
Great idea. Quick question. Do you need to have the pump running at all, or just pet the mains pressure do all the work?
@wr3099
@wr3099 7 ай бұрын
You don't want the pump running at all here. Probably do it damage it it was. Mains pressure is plenty to shift the crap
@davewright9312
@davewright9312 Ай бұрын
​Mains pressure alone will only shift some of the crap.... When I had a recent boiler install the plumber did a power flush and as well as the power flush he used a type of rubber hammer in a sds drill to agitate all the crud in each rad.. The amount of stuff that came out was unbelievable... BTW many manufacturers insist on powerflush on new install to validate warranty​@@wr3099
@tomsanders8714
@tomsanders8714 5 ай бұрын
Ok I do have a question about the parts. What is the male thread with the free nut called? Got everything else from my plumbers merchant but they don't know that. Thanks in anticipation and for all your vids.
@jaffplumbs26
@jaffplumbs26 7 ай бұрын
Wouldn’t a non return valve instead of an isolation valve be better to prevent cross contamination? Great idea though I’m definitely giving this ago
@mmplumber
@mmplumber 7 ай бұрын
Outside tap has one on the inside mate
@jaffplumbs26
@jaffplumbs26 7 ай бұрын
@@mmplumber aw tidy 👍
@rustyshillford1967
@rustyshillford1967 7 ай бұрын
What torch tip is that mate? I want one of those
@rayc1503
@rayc1503 6 ай бұрын
Javac flexi torch and imho it's shite. Mine is bust after falling out my bag. It's a weak torch.
@williamdgmartin
@williamdgmartin 7 ай бұрын
Hi, what blow torch is that? Where did you get it? Thanks
@mmplumber
@mmplumber 7 ай бұрын
Javac flexi torch
@talmanyurkovich4486
@talmanyurkovich4486 Ай бұрын
My hot water has stopped working and some of my radiators don’t heat at the top. I’ve tried to bleed them but some of them no air or water comes out. It’s an old system with no motorised valves and a header tank in the roofspace. I cleaned out the header tank as it was full of rusty crap. I want to try this flushing method but not sure how. And if the system is blocked or air locked will it even work?
@techtinkerin
@techtinkerin 6 ай бұрын
Easy if youre a qualified plumber with all the tools!😂 Nah just kidding, I used to see my dad and grandad doing something similar when I was a kid except they just filled it up from another tap near the header tank and drained it a few times. 😎👍
@littlejoeypeakdistrict7546
@littlejoeypeakdistrict7546 4 ай бұрын
Dint mention a non return valve on feed pipe from the tap not very good if it ets into the main stream water
@b1h2u3p4
@b1h2u3p4 7 ай бұрын
If open vent do you isolate vent and cold feed.
@mmplumber
@mmplumber 7 ай бұрын
Cap off the vent and shut off cold feed or cut a valve in
@TomTKK
@TomTKK 6 ай бұрын
Bloody 'ell everyone's got a opinion or advice to share haven't they? You smashed it mate, not like you needed me to tell you that anyway 🍺
@p.c.c9290
@p.c.c9290 6 ай бұрын
Trv needs a lock cap on otherwise they leak when removing rad .
@MagicDoughnut
@MagicDoughnut 5 ай бұрын
No they won't. Will only leak if they have frost protection and the temperature will drop below 5 degrees C.
@tunnel7
@tunnel7 6 ай бұрын
Why do they all use that gunge on compression joints it dont need it???
@mmplumber
@mmplumber 6 ай бұрын
It does! I fix leaks daily on compression from people not using it
@martinwarner1178
@martinwarner1178 6 ай бұрын
@@mmplumber Too true. I tried to tell people the same, then I saw their valves leaking....would they listen! No they know better. Good video, going to do mine the same, on old open vent system.
@grahamshillingford8229
@grahamshillingford8229 6 ай бұрын
I have an open vented system, I thoroughly clean the header tank out first & I just attach a hose to one of the lowest rads & let the water out onto a drain & it just runs through until its clear I then switch to another downstairs rad & repeat & do this to all downstairs rads until they are all clear. I open each radiator up fully,one at a time, for 5 or 6 minutes as I go along. It drains faster than it fills so I syphon more water from the main water tank in the loft... no fancy tools needed. I'll be doing it again probably late March...
@mmplumber
@mmplumber 6 ай бұрын
@@grahamshillingford8229 if you turn off the cold feed and cap off the vent you can do it this way. Your best to force it round a circuit to make sure it gets to all rads
@CaPiPwNsKi
@CaPiPwNsKi 7 ай бұрын
Sweet
@mmplumber
@mmplumber 7 ай бұрын
Thanks mate!
@ricardoa.m1322
@ricardoa.m1322 7 ай бұрын
Please stop driking water from heating circuit the last thing that we want it is that you get sick cause of that 🙏 about the powerflush you don't have a powerflush machine if you don't get yourself one straightaway cause they are simpñy brilliant no matter if its fernox,kamco,nostrom they all do the same exact job
@mmplumber
@mmplumber 7 ай бұрын
Thanks for carrying and watching the video dude
@ricardoa.m1322
@ricardoa.m1322 7 ай бұрын
@@mmplumber Thanks to you,they are so nice to watch sometimes I just watch your videos to relax that's how good they are ,but like I said before please do not drink heating circuit water even if it's pristine you are simply a topman I don't know even where did you get the time to edit and upload. Thank you so much for your splendid work and for your dedication 👍👌😊
@mmplumber
@mmplumber 7 ай бұрын
@@ricardoa.m1322 really does mean a lot you like them mate is there anything you would like to see different? Are you happy the videos are in portrait?
@ricardoa.m1322
@ricardoa.m1322 7 ай бұрын
@@mmplumber I like them so much cause you made things look much easier as they really are and not just that everything is so neat and clean and our job as you know is so dirty and messy. I like your videos cause you show your work but probably in the next future you will have to show yourself even that I think it's better to keep anonymity. Would be great also if you are doing some sealed system to show us,or some Air source or if you deal with HIU for example
@rzyrafa11
@rzyrafa11 5 ай бұрын
all the crap i caused by radiators, should have let the water go through the whole system including radiators
ADEY MAGNACLEANSE CLEAN HEATING SYSTEM SLUDGE
21:49
plumberparts
Рет қаралды 248 М.
❌Разве такое возможно? #story
01:00
Кэри Найс
Рет қаралды 3,8 МЛН
🩷🩵VS👿
00:38
ISSEI / いっせい
Рет қаралды 27 МЛН
How and Why to Flush Your Heating - Easy DIY
10:40
The Diligent DIYer
Рет қаралды 72 М.
New kitchen sink tap & plumbing
7:16
mmplumber
Рет қаралды 170 М.
Plasterboard HACK | Every DIY'er Should Know
11:29
On The Trowel
Рет қаралды 560 М.
DIY Central Heating System Radiator Flushing.
19:05
The Repairer
Рет қаралды 14 М.
HEATING SYSTEM SLUDGE REMOVAL PART 1 | Flushing & Chemical Cleaning
25:44
M J Tiff Plumbing
Рет қаралды 18 М.
How to flush Out a Radiator.  The Best Way, Getting the Best Results.
11:39
HEATING SYSTEM CLEANER.. Which was BEST? PART 2 | Mains Water Flush
19:11
M J Tiff Plumbing
Рет қаралды 11 М.
How to drain down a central heating system | chemical flush | add inhibitor
10:13
How to empty the heating system without a drain cock
7:47
dereton33
Рет қаралды 7 М.
❌Разве такое возможно? #story
01:00
Кэри Найс
Рет қаралды 3,8 МЛН