How to inspect an electric panel with an infrared camera

  Рет қаралды 6,454

Structure Tech Home Inspections

Structure Tech Home Inspections

10 ай бұрын

How to inspect an electric panel with an infrared camera.
Update: UL 489 limits the allowable temperature rise above ambient to 90°F. You can find more information about this on the Schneider Electric website.

Пікірлер: 11
@CNHInspections-CentralNebraska
@CNHInspections-CentralNebraska 3 ай бұрын
I am glad to see there is an actual allowable temperature rise value (90f/108f) that I can reference in my reports along with an amperage reading on the circuit. I would not report a hot spot without this info. Thanks Ruben.
@Sparky-ww5re
@Sparky-ww5re 10 ай бұрын
An infrared camera and checking the current draw on the neutrals is also helpful for locating incorrectly wired multiwire branch circuits (L1 & L2 on same phase, neutral carrying the sum of both ungrounded conductors). Happens more frequently than you might think, particularly when tandem breakers are added and the panel is rearranged by someone unqualified.
@waynebethune9090
@waynebethune9090 26 күн бұрын
NETA table 100.18 is the standard for thermography maintenance and testing for heat.
@RichardFreeberg
@RichardFreeberg 4 ай бұрын
Great presentation! Thank you! Useful information and clearly presented/explained. Just discovered this channel and plan to watch several more. Some of the topics I'm not interested in, alt least for now. But various problems and situations often turn up when you own and maintain property, so who knows? Ok, maybe home inspectors. LOL
@Rhinomods
@Rhinomods 8 ай бұрын
Thanks for sharing.
@Electric_Sherlock
@Electric_Sherlock 2 ай бұрын
The UL standard regarding temperatures for molded-case circuit breakers is UL489. This has been known for years by any good electrician or electrical engineer.
@user-kc4ny2uq2d
@user-kc4ny2uq2d 4 ай бұрын
valuable information, appreciate the bible scripture in the background.
@Andre-oi8sq
@Andre-oi8sq 11 күн бұрын
What kind of camera are you using
@bcrum7358
@bcrum7358 5 ай бұрын
Circuit breakers and wiring have a maximum operating temperature that should be considered. The example I have is a 120/240V, 15A, Square D type QOT breaker that accepts 60° C (140° F ) or 75° C (167° F ) wire. There is also a full load current temperature rating molded into the case itself of 40° C (104° F ) indicating this as the maximum ambient operating temperature. When I do thermal imaging scans, I consider it a concern if there is a temperature rise over ambient of 40° C (104° F). Further, I will stop testing if the temperature reaches the temperature rating of the wire.
@pierrebelarge892
@pierrebelarge892 5 ай бұрын
A circuit breaker is rated at 75 degrees Celsius (167 degrees Fahrenheit). Conductors are also rated at 75 degrees Celsius - although there are now installations that can be at 90 degree Celsius (194 degrees Fahrenheit). A 20 ampere rated circuitbreaker at some installations can carry 20 amperes of current, although most installations will be limited by code to 16 amperes. When a circuit is properly installed and the circuit breaker is carrying 20 amperes, the breaker will rise in temperature to well over 100 degrees. This is not understood by many, and you would hear them say it would trip the 20 amp circuit breaker. Not so. Again, with the installation being properly installed, a 20 amp circuit breaker will not trip carrying a 20 ampere load. It will become very hot though. When you come across this situation, it is best to call a qualified electrician to trouble shoot the circuit, making sure the heat is normal and not caused by other electrical issues. Overcurrent protection can be very complex, such as rise in ambient temperatures as one example of the complexity. Your judgement sounds pretty good, except. Are properly trained to try and deal with all you are mentioning?? Leave it to the ones who have more experience, you will still be the hero. 85 degrees is not a "hot" conductor/breaker. Working in a live panel requires Safety glasses, long sleeve shirt and the proper gloves. it is an OSHA VIOLATION, NFPA 70E VIOLATION and a safety issue you may one day regret. It also tells me you are not properly trained which make you unqualified to the work. Call a licensed qualified electrician and your company will be as good as you believe it is.
@peaceandlove5855
@peaceandlove5855 4 ай бұрын
Can you suggest some norm to use for such inspection ?
Infrared scans for electrical maintenance (IR scans)
12:28
DIY Home Energy Audit with an IR Camera
18:14
Les Wilhelm
Рет қаралды 114 М.
Vivaan  Tanya once again pranked Papa 🤣😇🤣
00:10
seema lamba
Рет қаралды 23 МЛН
Must-have gadget for every toilet! 🤩 #gadget
00:27
GiGaZoom
Рет қаралды 11 МЛН
Super gymnastics 😍🫣
00:15
Lexa_Merin
Рет қаралды 108 МЛН
10 Cool Uses for a Thermal Camera
8:16
Word of Advice TV
Рет қаралды 24 М.
POV: How-to Electrical Inspection with Thermal Imaging
2:34
Kulas Fact Buoy
Рет қаралды 444
Asbestos and Home Inspections
15:24
Structure Tech Home Inspections
Рет қаралды 10 М.
4 Point Home Inspection:  Electrical Panel
7:36
Neil Olshefski
Рет қаралды 56 М.
Thermal Imaging Application and Operation - How they work!
10:01
GAMMA 5 STUDIOS
Рет қаралды 54 М.
Voltage Drop? Mini THERMAL CAMERA Showdown! (TOPDON vs. HIKMICRO vs InfiRay)
35:59
Pine Hollow Auto Diagnostics
Рет қаралды 43 М.
A Complete Guide to Emissivity for Thermal Imaging
6:12
TEquipment
Рет қаралды 33 М.
Exploring the world in infrared with a thermal camera
14:49
Matthias random stuff
Рет қаралды 106 М.
How to repair ungrounded three-prong outlets
6:37
Structure Tech Home Inspections
Рет қаралды 1,1 М.
Vivaan  Tanya once again pranked Papa 🤣😇🤣
00:10
seema lamba
Рет қаралды 23 МЛН