Without much noise around, explained in a simple practical way...Thanks Rictor
@30mAkills Жыл бұрын
Shifting potential spike towards right and left is wrong.
@kyoritsu78862 ай бұрын
Hello, this is Kyoritsu Japan. It is so honor that you used our product. We highly trust we can learn more from your excellence in feedback on electrical equipment. If you don't mind, we can contact via email.
@haseebali4992 ай бұрын
Great You from Kyoritsu Company Right
@fje1948 Жыл бұрын
The video I was looking for! Excellent explanation of the test. Thank you so much! Ps: The background music is pleasant and appropriate!
@MrSyahryzal3 жыл бұрын
Mudah untuk difahami... Lama mencari video earthing test untuk menambah ilmu. Terima kasih boss
@salumhongo3955 Жыл бұрын
You demonstrate this critical task to look easily, Thank you very much a learn a lot through your video.
@manjunathamanju62043 жыл бұрын
Thank you Sir this video very useful for all Electrical engineers
@muhdyunus38943 жыл бұрын
Video paling sng difahami...tq sgt2
@castertroycabillar28633 жыл бұрын
Thanks for this very informative vedio. More power.
@sanjeevraghav37002 жыл бұрын
Very nice vedio 👌👌kudos to your effort 🙏🙏👌
@30mAkills Жыл бұрын
Shifting potential spike towards right and left is wrong.
@muhdsolihin26412 жыл бұрын
should be disconnecting earth cable from house to ground chamber first. so you will get the purest ground resistance.
@pankajmishra43 Жыл бұрын
Hiiii... You mean, first disconnect the earth cable from earth pit?? OR Can we shutdown the entire system before measuring earth resistance?? Pls guide
@Sim_Tiby Жыл бұрын
Disconnect the earth cable.
@DiReal_Donclassy Жыл бұрын
Of course he must have done that before starting the test otherwise the resistances of home equipment will distort the result
@foonglikwei39132 жыл бұрын
This teaching very useful and very easy to understand. Thanks and appreciate it 😊
@30mAkills Жыл бұрын
Shifting potential spike towards right and left is wrong.
@o-techtips38713 жыл бұрын
Thank you very much for your sharing very informative tips☺️
@electroboy3607 Жыл бұрын
Good job..🎉 im practical test
@sanjeevraghav3700 Жыл бұрын
Appreciate 👌👌you have done share gr8 experience with kyoritsu instrument 💐 This is sanjeev raghav from kyoritsu
@rictorrictor888 Жыл бұрын
Thank too .kyoritsu always the great equipment ..
@30mAkills Жыл бұрын
This method is not FOP.
@fazrulchanneltv91572 жыл бұрын
Tq Sir. Clear and easy to undrstand. This place is like "Bukit Bendera" 😅
@rictorrictor8882 жыл бұрын
Yes bro..bukit bendera..tqvm
@PbaY.4 жыл бұрын
mantap tutorial nya .👍👍🌟🌟🌟
@electroboy36074 ай бұрын
Good interesting vedio😊😊😊
@kanthasamymuthusamy7392 жыл бұрын
Simple explainations.Easy to underdstand
@30mAkills Жыл бұрын
Shifting potential spike towards right and left is wrong.
@kirotomato73163 жыл бұрын
easy to understand,thank you sir for wharing the information for us
@anthondiy2 жыл бұрын
Thank you sir sa video another learning for earthing system
@francisrayang8053 жыл бұрын
Hi sir. You did a very informative video thanks. I've a question for you.In the video you did the test on a big compound. I'm in a terrace house and the compound is very limited. I can't pull the yellow and red cable that long..only 3-4 meters to the nearest soil. Will it affect the reading? Please advice thks.
@rictorrictor8883 жыл бұрын
In that situation ..You can try nearest area to ground the spike ..
@rictorrictor8882 жыл бұрын
in that situation ..yes..
@30mAkills Жыл бұрын
You have to maintain distance. Please read my other comments. Get permission from neighbours.
@ahmedbelazi2318 Жыл бұрын
Thank you for the effort made in the video.... I have a question... Is it true that the yellow wire is supposed to be an extension of the red wire, meaning on one line to give the reading... Why change in yellow only and should it be changed in red? ??
@yghiduppastimatikelak88543 жыл бұрын
Good job ...thanks for sharing..
@marchomeautorepairs2 жыл бұрын
Keep up the good work
@ohhappyday15483 жыл бұрын
thanks to your efforts, it is very helpful .. thank you..
@wazzer5293 Жыл бұрын
Sir, how 1). If earth got voltage, what is the next action.. 2). When to use the setting mode 200 & 2000? Apprecite ur answer
@ofwj-ddah Жыл бұрын
Thanls for sharingbthis video. It helps me a lots
@niezam17293 жыл бұрын
Jika persekitaran rumah tamn agak sukar nk ambil bacaan,sb permukaan tanah @ berturap simen Dan jalan tar. 1- minutes 6.15 mase kita clamp wayar di electrod bumi.yg seeloknya copper tape @ cable incoming perlu ditanggalkan @ tidak semasa nak ambil bacaan.klu sye lihat Tuan x buka ..
@nasrulhelmeihalimppksistem74323 жыл бұрын
kalau kawasan tar @ bersimen, boleh guna metal screen @ earthing mat. letak pada jarak yg ditetapkan & siram dgn air jd blh buat measurement
@VlogSidah4 жыл бұрын
Mantap tuan,done support ya,maaf lewat.. 🙏🙏
@noelfaithfulkari28573 ай бұрын
Please could you explain the operation of the meter and the readings.
@MrOner072 жыл бұрын
very easy to follow... you earned a subscriber!❤️😊
@30mAkills Жыл бұрын
Shifting potential spike towards right and left is wrong.
@akilagayan65332 жыл бұрын
Good work 👍
@30mAkills Жыл бұрын
Shifting potential spike towards right and left is wrong.
@michaelisongekwere14023 ай бұрын
It was beneficial
@lonedragon44103 жыл бұрын
Below 5ohm is acceptable right?
@rictorrictor8883 жыл бұрын
Yes
@william56242 жыл бұрын
Very good👍🏻
@iranweranga225 Жыл бұрын
Is there a specific number of times that earth resistance testing should be done for a specific area? (like number of times per meter squard)
@fauzibafana90893 жыл бұрын
Can i know whether before the individual earth rod being tested you have to remove the connection of the earth rod from the rest.
@gniraj85012 жыл бұрын
I am also have same question.
@30mAkills Жыл бұрын
Yes it should be disconnected from service. If the voltage is more than 10 it will destroy the meter and also give false reading. Please read the user manual reg the max voltage limit that the meter will work safely in energised service without disconnection.
@robertotrinanes17444 ай бұрын
What about the grounding rod resistance?each rod shall be tested and removed all connected cable before the test of total resistance grounding.
@mohamadasriabdulazid47842 ай бұрын
Not really it depends on the situation and regulations of the country. We usually do it at the installation state, we check each time the rod is inserted to the earth. These guys in the video are doing inspection for application form.
@neilblenkinsop2613 Жыл бұрын
To individually test the earth rod disconnect tape from earth rod
@gohpoikheng60302 жыл бұрын
May i know why the cable for current is longer than the voltage?
@raemondbradford16292 жыл бұрын
When current is injected into the earth, then the voltage will change around the location of injection. The voltage reference cable spike needs to be some distance from the points where current is injected or removed, in order to try and find a location with minimal disturbance of earth voltage potential.
@yusufsupyan99404 жыл бұрын
Luar biasa kawan Videonya. Sudah saya kirim Bungkusan komplit dan,paten, durasipun Aman. Sesuai undangan. Ditunggu Amanahnya ya..
@rictorrictor8884 жыл бұрын
Ya udah juga..terima kasih..
@igorsmirnoff85782 жыл бұрын
Будьте любезны,выложите такое же видео с прибором KEW 4106,спасибо!!!
@GUDANGLAMPUSURYA2 жыл бұрын
Om untuk mengetahui brp kedalaman grounding rod yg di tanam bagaimana ya ? 🙏
@GUDANGLAMPUSURYA2 жыл бұрын
Apakah bisa di test dgn ohm meter tersebut
@rictorrictor8882 жыл бұрын
Kedalam nya sehingga rod gak bisa masuk lagi..baru di uji..jika masih tidak mendapat kan bacaan yg dikehendaki..buat point baru sehingga mendapat bacaan yg paling rendah
@fidelcatsro6948 Жыл бұрын
if we had no access to such equipment will adding more grounding rods to the ground all connected together potentially reduce the earth resistance?
@rictorrictor888 Жыл бұрын
Yes.
@fidelcatsro6948 Жыл бұрын
@@rictorrictor888 🐱👍🏿
@muhammadaresyamilbinazman79352 жыл бұрын
Tumpang tanya, kan ada 20ohm, 200ohm, dan 2000ohm. Yang tu nak laraskan berdasarkan faktor apa ye?
@fidelcatsro6948 Жыл бұрын
dasarkan 20ohm setting
@gabus19562 жыл бұрын
Thank from Hungary
@30mAkills Жыл бұрын
Shifting potential spike towards right and left is wrong.
@joselitodupaya20923 жыл бұрын
Thank you sir sa video
@azleeman3 жыл бұрын
Saya nak tanya, bukankah testing dibuat semasa pemasangan rod sahaja (sebelum kita sambungkan dengan earth DB atau sebelum sambung ke perlindungan kilat)
@rictorrictor8883 жыл бұрын
Kedua2 nya boleh ..sebelum dan selepas ..Sebenarnya Cooper tape itu bukan utk pelindung kilat..
@pankajraina4832 Жыл бұрын
Good sir 👍
@30mAkills Жыл бұрын
Shifting potential spike towards right and left is wrong.
@bundaajhalah4 жыл бұрын
Hadir nyimak 👍
@rictorrictor8884 жыл бұрын
thank you so much
@haseebali4992 ай бұрын
One more thing what's the distance between two consecutive Earth Pit what's the exact standard if you can please explain this the the minimum distance between two consecutive Earth pits
@mohamadasriabdulazid47842 ай бұрын
20 meter center spike 20 meter end spike from center spike
@CrisBoy410 Жыл бұрын
video excelente parabens , abraços do Brasil .
@solomonnyaga7018 Жыл бұрын
Does it mean now the earth resistance is perfect?
@KGL1012932 жыл бұрын
Hi, I have a Kyoritsu 4105A unit too, and I am getting "1. . ." reading at 20 ohm dial, who do you think is the problem, and how to fix this? Thank you.
@deutroitcity2 жыл бұрын
It's over limit. U need to dial up the limit. Cannot use 20ohm. Because the reading is above 20 ohm
@nasiadomary48932 жыл бұрын
How about if the reading is 25ohms What can i do to get less than 5Ohms?
@30mAkills Жыл бұрын
@@nasiadomary4893 1. If possible increase the depth of electrode. 2. Insert another electrode at a distance of at least twice the buried depth of 1st electrode and link both at top. Eg.: If 1 st electrode buried depth = 3 M then second electrode should be installed at a distance of minimum 6 M away and both should be linked with wire or strip at the top. 3. Wet the pit by watering because dry earth is a bad conductor. Note : Chemical electrodes are fraud work. Hope all this helps.
@nasiadomary4893 Жыл бұрын
@@30mAkills Thanks🙏🙏
@bruce.bchannel90463 жыл бұрын
Macam mna kalo erathing buat ats tnh bacaan bukit tu tnh...
@rictorrictor8883 жыл бұрын
tetap kena dapat kan bacaan bawah 10 ohm juga...tapi ada kaedah2 untuk menurunkan bacaan jika di buat atas tanah berbukit..tq
@bruce.bchannel90463 жыл бұрын
Sa lbih 15ohm bgtu
@bruce.bchannel90463 жыл бұрын
Nnti whatapps kmi 0138724857 mhu tnya kaedah lain
@rictorrictor8883 жыл бұрын
@@bruce.bchannel9046 boleh tambah point lagi tu..atau guna wayer tembaga bogel gulung jadi kan coil...tanam terus dlm tanah.hujung nya sambung ke electrod yang sedia ada..
@bruce.bchannel90463 жыл бұрын
Mcm mna cara ti
@prabhus41373 жыл бұрын
Hi sir I have a doubt. Could you please tell me the difference between 2 point, 3 point method. In megger it has 4 terminals C1, C2, P1, P2. how to measure earth pit resistance?
@30mAkills Жыл бұрын
Short C1 and P1 and connect to electrode under test. P2 is for potential and C2 is for current spike. This is known as 3 point or Fall of Potential method. 4 terminals method is for testing soil as per Wenner method. This is for civil guys and not for electrical guys. Reg 2 point earth pit resistance testing: In India we don't/cant use this method because our public water supply is thru PVC pipes which is non conductor. Hope this helps.
@AutodidactEngineer2 жыл бұрын
The test should be done preferably during the driest season to prevent moisture from ruinning your values!
@File-Transfer8 ай бұрын
I have a question, engr. Why is it required in the earth resistance tester manual to damp the surroundings?
@AutodidactEngineer8 ай бұрын
@@File-Transfer I don't know about that
@TheElectricianOnHisMission2 жыл бұрын
I have to perform this same test but outside of the building is all concrete, a shower room will be built in the basement but first the neutral to earth voltage needs to be tested, so how would I go about this?
@frankkennedy78312 жыл бұрын
you silly person. what sort of system are you on?
@30mAkills Жыл бұрын
Check with normal clamp or multimeter in volts mode between earth and neutral of any 3 pin socket connected to that service. The voltage value should be below 2. Hope this helps.
@fje1948 Жыл бұрын
@@frankkennedy7831 Perhaps you are the silly person making such an inappropriate comment! 🤢
@nagarajah89302 ай бұрын
Sir ummmmmmmmmmbu
@japhethm610310 ай бұрын
What readings should tell me that the resistance is not okay please
@rictorrictor88810 ай бұрын
depend on local regulation ..as lower as possible. .below 10ohm
@stanleyozoilo15872 жыл бұрын
What is the accurate value for best low resistance using Megger machine
@rictorrictor8882 жыл бұрын
0 ohm
@30mAkills Жыл бұрын
@@rictorrictor888 Practically not possible. Is earth full of gold?
@fje1948 Жыл бұрын
@@rictorrictor888 I wish 😂
@wilsonloo85763 жыл бұрын
Hi Rictor , may i know how to know the result is good or bad? Many Thanks
@rictorrictor8883 жыл бұрын
low in reading is the batter .must below 10ohm.some time we can get 0 ohm. that the best..
@octaviohurtado27793 жыл бұрын
It depends on your country standards. But the Best is the nearest to 0 ohms which is imposible to get 0 ohms. Also there are many methods to make the measurraments, it depends on your country standards too.
@redbirdgaming79053 жыл бұрын
Thank you very much sir Many Thanks
@angelosrcayabyab69522 жыл бұрын
thanks for sharing
@castertroycabillar28633 жыл бұрын
Sir what is the porpuse for higher ohms setting.is it same result as 20ohms setting.thanks
@rictorrictor8883 жыл бұрын
Yes..same.
@30mAkills Жыл бұрын
For soil testing and also in hill areas.
@leomarbecilla27852 жыл бұрын
hi sir. how do you perform it in a building where there is no earth ground to put the spike?
@rictorrictor8882 жыл бұрын
Extent green wire..
@rictorrictor8882 жыл бұрын
For condo there should have main electrical grounding
@kennedymutuku89502 жыл бұрын
Hello Sir,what if the result is above 10,let say 50..how can you improve this to 5?
@AutodidactEngineer2 жыл бұрын
Use a combination of vertical and horizontal grounding! My tip would be get copper/or in poorer countries galvanized pipe works well enaugh and install it in conjunction with galvanized steel bar/ or do the same but with copper if you can afford it!
@fidelcatsro6948 Жыл бұрын
add more earthing rods all around the place the more the better🐱👍🏿
@neilblenkinsop2613 Жыл бұрын
All earth rod supplies these days are carbon steel with copper coating add to and go deeper using brass connection.
@sahayaxaviersahayaxavier32173 жыл бұрын
Salute sir
@aubreynorkee68543 ай бұрын
Thanks again
@FabioHM713 жыл бұрын
the operator wears the helmet because there are suspended loads?
@rictorrictor8883 жыл бұрын
He worries falling mango fruit..hahaha
@FabioHM713 жыл бұрын
@@rictorrictor888 hahahaha ;-)
@fidelcatsro6948 Жыл бұрын
there are flying cats around in the neighborhood
@johnhayhurst58843 жыл бұрын
Very Very different to how it's done in the UK, In the UK those reading wouldn't be satisfactory but the method is way different so I don't know. Interesting though
@azleeman3 жыл бұрын
Maybe the humidity in UK is different if we compare to Malaysia. The water in soil can effect the meter reading.
@nasrulhelmeihalimppksistem74323 жыл бұрын
@@azleeman biasanya ada 2 jenis earth tester yg selalu diguna measure grounding resistance. yg dlm video ni guna kyoritsu & location potential spike tu ditengah2 antara ground rod & current spike. yg satu lg jenama megger tapi jarak potential spike tu 62% dari jarak antara earth rod & current spike. & potential spike tu kena ubah 10% ke depan % 10% ke belakang dari kedudukan asal & diambil average dr 3 reading td. mungkin kat uk guna jenama megger sbb tu dia ckp different dgn kt sini.
@30mAkills Жыл бұрын
All over the world FOP (Fall of Potential) method is same.
@johnhayhurst5884 Жыл бұрын
Incorrect@@30mAkills
@30mAkills Жыл бұрын
@@johnhayhurst5884 then tell the correct. Here our earthing is TT.
@wtnyambizi98762 жыл бұрын
What about the distance btn the spikes does it matter !?
@anthonykihanga28812 жыл бұрын
5 meters up to 10 meters it depends on soil type
@30mAkills Жыл бұрын
Thumb rule for current spike distance from electrode = Minimum 8 to 10 times the buried depth of earth electrode. Eg., If earth electrode is 3 M long then C spike should placed about 24 to 30 M distance. This is to avoid '"zone of influence"' factor. Most manufacturers wont tell this because the distance will affect their tester sales in city and town areas where space is congested. So they suggest 5 M and 10 M which will not yield correct value. I challenge Kyoritsu in this matter.
@fje1948 Жыл бұрын
@@30mAkills Thank you for this comment - can you please provide some formal references to confirm y you our comment - Thank you!
@junsmackalbos4565 Жыл бұрын
Sir the result you shown is that good or bad grounding
@rictorrictor888 Жыл бұрын
Good ..under 10 ohm
@junsmackalbos4565 Жыл бұрын
Thanks sir......
@nathan37141 Жыл бұрын
Thank you Engineer
@yumon65153 жыл бұрын
Sir, can I set the tester 200ohm? Should I take that result? Thank you 🙏
@rictorrictor8883 жыл бұрын
yes..
@HENRYFANUELPHIRI5 ай бұрын
Why the leads are in same line? pliz assist me sir.
@dakwahislamcn63904 жыл бұрын
Lanjutkan
@matsetizar657 ай бұрын
when lightning strikes the earth doesn't the surge enter the house via the earth wiring? If so isn't it dangerous, probably better not to have any earthing system at all?
@aruquest253 жыл бұрын
The green wire is for?
@rictorrictor8883 жыл бұрын
electrode wire..
@olegkotletov78573 жыл бұрын
green wire is for grass. grass is green. make sense right? put green wire on grass and see resistance of grass. grass is green, green wire is green too. make sense right? right.
@siralexivan20063 жыл бұрын
well done
@rictorrictor8883 жыл бұрын
Tqvm
@surendrakverma555 Жыл бұрын
Good 🙏🙏🙏🙏🙏
@30mAkills Жыл бұрын
Shifting potential spike towards right and left is wrong.
@arturotakuma47422 жыл бұрын
excelent ¡¡¡
@yosuaabimo937911 ай бұрын
Test ini apakah harus saat listrik off?
@mohamadasriabdulazid47842 ай бұрын
Kalau tak ada bocor ke bumi tak perlu off. Sebab tu dia check voltage dulu.
@MNor-nb8sp2 жыл бұрын
What we do if earth volt not zero
@rictorrictor8882 жыл бұрын
Find another location for grounding the rod..
@30mAkills Жыл бұрын
De-energize that service and procced if the voltage is more than 10.
@islammaidul69992 жыл бұрын
Overall resistance how is it calculation sir
@rictorrictor8882 жыл бұрын
Total of test 1 ,2 ,3 then / by 3..it show on video min 13.20
@jillferrer61352 жыл бұрын
thank you sir..
@johnvillellegunas1862 жыл бұрын
Hi sir. If floor is concrete, how to insert voltage and currrent spikes?
@fidelcatsro6948 Жыл бұрын
break concrete and place into the soil below?
@30mAkills Жыл бұрын
It need not be inserted. Wrap the spikes in wet towel and place them horizontally on the concrete floor with weights (stone) placed on the sack. Wet the whole area by watering.
@fje1948 Жыл бұрын
@@fidelcatsro6948 Jesus, what planet are you on…..
@fje1948 Жыл бұрын
@@30mAkills Excellent explanation….
@fidelcatsro6948 Жыл бұрын
@@fje1948 planet Kittygystan 🐱 of the 23rd Constellation, why do you ask amigo?
@قصيعليعبدالهادي3 жыл бұрын
Thank you, sir
@ahmadwahab16413 жыл бұрын
untuk apa select ke earth voltage?
@rictorrictor8883 жыл бұрын
kita uji dahulu jika terdapat voltage dalam tanah.. terutamanya di kawasan kediaman yang berdekatan dengan sub station
@fidelcatsro6948 Жыл бұрын
kalau ada voltage baguslah pasang diode boleh charge bateri kereta anda🐱👍🏿
@MdSultan-u4e5t3 ай бұрын
good
@thanhthoangngo25913 жыл бұрын
hi sir, if the screen will perform "1 . " , what's wrong?
@rictorrictor8883 жыл бұрын
show me photo..
@octaviohurtado27793 жыл бұрын
The valor is over the Range selectionated in the istrument or the cables are not conected correctly to the Spikes You should to check again all the conections. If the problem continue changue the Spikes of place.
@thanhthoangngo25913 жыл бұрын
@@octaviohurtado2779 Thank you! I'll check carefully. Good day!
@thanhthoangngo25913 жыл бұрын
@@rictorrictor888 Sorry, I don't know how to share a photo via a youtube comment. Anyway, I'll check my device. Thank you for your guidance.
@ericmunkanta29647 ай бұрын
Why is the leads in the same line
@Bestofthebest3836 ай бұрын
I had an exams question in college how to do earth rod test . I didn’t pass it 😢
@ervingjonaj908210 ай бұрын
music is shocking
@Mike-ry4ti2 жыл бұрын
Your value of 1.63 ohms is a little high. Ideally less than 1 ohm is what you want...
@anthonykihanga28812 жыл бұрын
Thanks alot
@30mAkills Жыл бұрын
Shifting potential spike towards right and left is wrong.
@lenslens73792 жыл бұрын
I think 1/RT = 1/R1 + 1/R2 + 1/R3
@SpecialVeloce Жыл бұрын
Sorry your Appying the wrong formula, it's average, not resistances in paralel
@svh61953 жыл бұрын
Thanx!!
@daspecialist1220 Жыл бұрын
Attack of the silent explanation vid strikes yet again
@rictorrictor888 Жыл бұрын
Hahaha..Mr bean vers 2
@bornstar98973 жыл бұрын
thanks
@aruniimalka61233 жыл бұрын
what is this aim?
@rictorrictor8883 жыл бұрын
Protect human and electrical equipment from electric short