Ap bht acha prhate ho aisi videos bnate rhee... Respect from pakistan
@solarfacts4242 Жыл бұрын
Thanks
@FahadMukhtar-d2z9 ай бұрын
@@solarfacts4242 Brother the values which i get from soil report is in ohm.meter for example 87 ogm.meter, how i will convert it to Kelvin.meter/watt?
@sourabhsharma99853 жыл бұрын
Great vedio sir, I have'nt seen this type of content on this particular topic in which any industry can actually calculate their cable size and will no longer be dependent on assumptions.
@solarfacts42423 жыл бұрын
Thanks 🙏
@mohammadumer37 Жыл бұрын
Informative sir ❤
@solarfacts4242 Жыл бұрын
Thank you 🙏🏻
@shikshasolanki89032 жыл бұрын
Thankyou bhaiya I’m a working professional nd I’m really suffering alot in corporate world because no one is ready to tell me
@solarfacts4242 Жыл бұрын
😊
@tejasshirke1267 Жыл бұрын
Can feel you... seniors do tell but bcoz of work pressure, most of the times they're rude🙃 but that's how we learn.
@FahadMukhtar-d2z9 ай бұрын
@@tejasshirke1267 Brother the values which i get from soil report is in ohm.meter for example 87 ogm.meter, how i will convert it to Kelvin.meter/watt?
@khaledshaikh49722 жыл бұрын
Helpful videos for Industrial projects Thank you
@solarfacts42422 жыл бұрын
You are welcome
@chandrakantchaudhari76792 жыл бұрын
Very very nice video Sirji
@solarfacts42422 жыл бұрын
Thank you
@SONUSAINI-lz6qs2 жыл бұрын
This video is very important every electrical field. Thank you sir.
@solarfacts42422 жыл бұрын
Many many thanks
@Jsr735 Жыл бұрын
well done sir,from long time need for such a good explanation..I LIKED UR VDO
@solarfacts4242 Жыл бұрын
Thank you so much 🙏🏻
@gallwailaydi39765 ай бұрын
Excellent information
@shoaibahmed8947 Жыл бұрын
Superb bro u r awesome keep it up n thank u soo much ❤
@rajkandari50697 ай бұрын
Gajab video
@sumitjambhulkar8875 Жыл бұрын
Very helpful video sir.... thanks
@solarfacts4242 Жыл бұрын
Most welcome
@sanjutambhale58022 ай бұрын
very good sir
@Amazingsolar77533 жыл бұрын
Nice video
@solarfacts42423 жыл бұрын
Thanks 🙏
@anmol_ashu1822 Жыл бұрын
Good 😊❤
@solarfacts4242 Жыл бұрын
Thank you 🙏🏻
@abusalehAbir Жыл бұрын
Very nice Sir . keep up the good work Sir :)
@solarfacts4242 Жыл бұрын
Thanks 🙏🏻
@nisark.v6010 Жыл бұрын
Great❤❤
@surajbk10203 жыл бұрын
Sir thanks. Very useful 😇😇
@solarfacts42423 жыл бұрын
👍
@sohampise2603 жыл бұрын
Proper explanation ; thank you for such good video.
@solarfacts42423 жыл бұрын
Thanks 🙏
@FahadMukhtar-d2z9 ай бұрын
@@solarfacts4242 Thanks for your videos. Brother the values which i get from soil report is in ohm.meter for example 87 ogm.meter, how i will convert it to Kelvin.meter/watt?
@Shailendra_singh_81 Жыл бұрын
Thank you for the good information i think need to some more calculation like Derating Factor of Cable ?
@electricalengineer-ey4fe Жыл бұрын
Good work
@solarfacts4242 Жыл бұрын
Thank you
@deepakkyadav2381 Жыл бұрын
Source ? Reference Book or any National Indian Standard ?
@asispuri85808 ай бұрын
Hey bro! Did you got any reference book or standard? If yes can you share it to me and if you are experienced in this field can you tell I should go by this video?
@pushpendrakumar27362 жыл бұрын
Sir 3/3.5/4 core cable ke liye kis size ka gland or holesaw cutter use hota iski info share kariye
@solarfacts42422 жыл бұрын
I will make one video on it
@sayedmustaffa22962 жыл бұрын
Ok Thank you for detail video Kindly requesting to provide details for Multiple cables running in ground Multiple cables running in air through cable tray
@solarfacts42422 жыл бұрын
ok i will make video on it
@akm45902 жыл бұрын
great video
@solarfacts42422 жыл бұрын
Thanks for the visit
@vinodmenariya34712 жыл бұрын
Sir it great please made single phase wire size selection
@solarfacts42422 жыл бұрын
Ok sure I will
@mohamadsafwan45752 жыл бұрын
Lot of thanks.....
@solarfacts42422 жыл бұрын
thanks
@XYZPIANOTUTORIAL3 ай бұрын
Single phase ke liye yehi formula chalega kya voltage drop ka
@Mikku7Vlog Жыл бұрын
Dear Raman ji this is for aluminium cable or copper cable ? For both these same formula will be applicable or different if different formula then please tell
@solarfacts4242 Жыл бұрын
Same formula only values will change
@mahidavilas91602 ай бұрын
Hi, thank you for this video. I have a quick question for you, instead of using 95sqmm size cable, can we route two run of 70sqmm cable or not??? Please tell me the reason. Once again thank you.
@mehadimonjurkhan8506 Жыл бұрын
bhai iska internation rules reference de sakte ho kya?? ye rules kaha se liya apne please send us reference
@solarfacts4242 Жыл бұрын
Ok
@SONUSAINI-lz6qs2 жыл бұрын
Very helpful videos sir
@solarfacts42422 жыл бұрын
Thanks and welcome
@fahadmukhtar11242 жыл бұрын
100 kider sey aya?
@ayushshortvlogs3499 Жыл бұрын
Hello sir....generator voltage too low ... inverters main issue hai ..?
@solarfacts4242 Жыл бұрын
You have to keep the voltage In range of inverter
@vinayff24612 жыл бұрын
Excellent video
@solarfacts42422 жыл бұрын
thanks
@umaid-nungshatpa Жыл бұрын
Voltage drop me system full load current lena tha ya nahi?
@kashmirengineeringvision4 ай бұрын
this is very good but i have a small doubt let's consider the 80kw load is inductive so the starting current will be more don't we have to consider that in it ??
@Jehangir.e Жыл бұрын
For Home wiring we also find voltage drop?
@solarfacts4242 Жыл бұрын
Yes you can find the voltage drop for home also
@Jehangir.e Жыл бұрын
Same method?
@ArmanBehura2 күн бұрын
Sir how cos theta is 0.8???
@mohdanjum2672 жыл бұрын
Regarding voltage drop calculation Are you sure about considering current value 139.12 amps . Why not used current rating 142.28 ?
@solarfacts4242 Жыл бұрын
Let me check
@soorajsharma4694 Жыл бұрын
Sir mujhe 1.5ton non inverter technology 4 AC chalana he mcb box se electricity pole Tak main line 25 mtr Lambi Ho Jayegi to bataiye 2 core aluminium wire kitne mm ka lagaen
@solarfacts4242 Жыл бұрын
Replied on phone 😊
@fidhabashir81494 ай бұрын
But sir i have 1 confusion is this for almunium cabels or for copper
@mehadimonjurkhan85062 жыл бұрын
@solar Facts thanks a lot for this video. can u share the book name about k factors table u have used in this calculation???
@swapnilshiyaniya5306 Жыл бұрын
K factors are given by manufacturing company. You can follow them
@solarfacts4242 Жыл бұрын
That you can get from the manufacturer whose cable you are going to use
@kanagarajayyappan7690 Жыл бұрын
wher u apply value in formula there please clarified mean where divided the value u r put 415 x1 x100 instead of 1000
@solarfacts4242 Жыл бұрын
That is 1000 there is written error
@allrounderrk73414 ай бұрын
👍👍👍
@skmgamer8214 Жыл бұрын
Would the calculation be the same for the cable from Inverter to the LT panel?
@asharkhan14643 ай бұрын
From where did u get k value as .9
@ankushpatil3451 Жыл бұрын
Why you taken current as 139 while calculating voltage drop ???
@adnansafi23326 ай бұрын
As depth of cable ur selecting from chart 1050 Meter and that sqmm of cable how can we decide that 70 sqmm. after correction factor calculation only we can decide sqmm of cable on wht basis or consideration we are taking 70 sqmm before calculating correction factor
@looserregrets36232 жыл бұрын
Can we use simple polycab 4sqmm ac wire in 3kw solar ongrid system?
@solarfacts42422 жыл бұрын
Yes But you have to check cable length
@looserregrets36232 жыл бұрын
@@solarfacts4242 90 ft. Approximately
@gulsherahmad6198 Жыл бұрын
Plz share the link of the Tables which you are used .
@solarfacts4242 Жыл бұрын
Sure
@asfaquealam9086 Жыл бұрын
K6 ka value aapne consider ni kiya hai. What about that?
@solarfacts4242 Жыл бұрын
By default it is 1
@shrikantvaze28372 жыл бұрын
Sir, cable selection me short circuit current nahi consider karte hai kya ?
@solarfacts4242 Жыл бұрын
Karte hai
@solarfacts4242 Жыл бұрын
Will make a separate video
@syedahsanahmad780611 ай бұрын
how did you select 70sqmm=164Amp
@thakurmanoj70204 ай бұрын
Ye 👍 baat Hui na sir
@rano.rajawat2 ай бұрын
Sir could you please help me our load ism1500kw so how many cables of 300mm aluminium would we need from transformer to load , cable length approximately 50m
@RaganiG2 жыл бұрын
Sir fault level pr cable size pr kya effect h please elaborate the fualt level effect
@solarfacts4242 Жыл бұрын
Yes will make a separate video on it
@kv8483 жыл бұрын
Good brother,.But to finalize cable, you must check the short circuit capacity of cable also...
@solarfacts42422 жыл бұрын
yes
@vaibhaodnyaneshwarkelzarka61539 ай бұрын
Thank you
@aalamraza32132 жыл бұрын
Good explain
@solarfacts42422 жыл бұрын
thank you
@nimeshmandal76062 жыл бұрын
Sir, Inverter always work on unity factor, so why you. Have consider .8 PF Can you explain ?
@solarfacts42422 жыл бұрын
Inverter power factor is unity but as per my consideration power factor always depends on load that why I have take 0.8
@singhdevendra8027 ай бұрын
One question I have is that for calculating full load current will the current be divided by k factor value or will it be multiplied by k factor value beacuse k factor is correction factor means it is derating the cable current depending on certain parameters so full load current should reduce and for that we should multiply the current by k factor. This is my assumption, please correct if I am wrong.
@Mikku7Vlog Жыл бұрын
Sir in this video you didn't calculate power loss. So can you tell or describe the power loss finding according to this calculation?
@solarfacts4242 Жыл бұрын
That will be a separate video
@keyable2 ай бұрын
Where can I find K factor tables? and why sin(fi) 0.6?
@शिवाy10 ай бұрын
Hi bro in last while calculation of voltage drop you write 139 amp but while adding "k" factor this is 142 so what is correct ?
@ASIFAKBARKHAN3 ай бұрын
Hi sir, Kindly guide I have to take connection from electric pole which is 500 meters away for bunglow Existing cable which i am using voltage dropps from 220 to 170 while starting motor, Meter connection i have got for 2kw. This is overhead connection, Without any other wire. Kindly advice the wire to choose
@sanketbhangeofficial2531 Жыл бұрын
Great vedio sir. How can we put values of k factor like air temp.
@solarfacts4242 Жыл бұрын
There is a sheet from where you can find out the values of K
@kavinraj63882 жыл бұрын
Hi sir,fantastic explanation,kindly make video for current carrying capacity of particular armoured cables size(without knowing power) ,like 4 core 240 sqmm armoured cable.
@solarfacts42422 жыл бұрын
Ok Good Topic thanks 🙏
@fahadmukhtar11242 жыл бұрын
@@solarfacts4242 bahi jaan 1000 & 100 kider sey aya?
@skmgamer8214 Жыл бұрын
sir voltage drop me 100/1000 kiss chiz k liye hai?
@neutral67782 жыл бұрын
Sir kindly make a video of wire size calculation for normal house wiring and what point need to keep in mind whenever we will go for solar in future
@solarfacts42422 жыл бұрын
ok sure thank you
@allinonewithshyamjeedwived4606 Жыл бұрын
Sir can u send selection chart of cable
@solarfacts4242 Жыл бұрын
Sure
@Abdulghaffar-hw8nu Жыл бұрын
Sir end mea jo ap nay calculation keya hy 6.26" ye answer nai ah rah kindly explain me
@Abdulghaffar-hw8nu Жыл бұрын
Ya kisi Bhai ko pata ho kindly tell me
@engrasad2965 Жыл бұрын
Aoa dear your video is very helpful... Kindly give just one answer... If I use the 4 core 70mmsq then it's means that number of cable run = 1...or 4
@whydoyouwannaknowmyname651011 ай бұрын
1 run 4 core
@keyable2 ай бұрын
Could you pls do videos also in English? So it will be accessible for much bigger audience. thnx
@danishalam10612 жыл бұрын
Ye aluminium cable ka hai ya copper cable ka
@solarfacts42422 жыл бұрын
Al
@sanaparveen96422 жыл бұрын
Sir 4 core cable ya sirf single core cable
@solarfacts42422 жыл бұрын
You can calculate for both
@sanaparveen96422 жыл бұрын
Sir 4 core cable me nutral current kitna flow karega or agr humara system pura sirf unbalance ho 3phase and nutral ko hum sirf single phase and nutral use karrahe ho to kya nutral wire 3 phase wire ka sum hoga
@pradeeppoojari278611 ай бұрын
How derating factor to be devided instead of multiplying..can you clarify..
@mwncc65282 ай бұрын
Sir sorry, I have question in cable sizing. What is the meaning of no of runs? Example: 5R/3.5C/240sqm/XLPE and 1R/3.5C/25sqm/XLPE Thank you Sir
@kanagarajayyappan7690 Жыл бұрын
i have a comments against your subject , final calculation which your apply instead of 1000 u r putting 100 , please clarified this , and over all v.good
@solarfacts4242 Жыл бұрын
That is 1000 there is written error
@amarnathmishra1461 Жыл бұрын
Good endeavor. But, to calculate voltage drop, why current be multiplied by root three? In star mode, phase voltage equals line voltage.
@solarfacts4242 Жыл бұрын
No Sir in delta phase voltage is equal to line voltage
@amarnathmishra1461 Жыл бұрын
Right. My mistake. In star mode, phase current equals line current.But here we are calculating voltage drop making use of current. Is it still required to be multiplied by root three?
@sapnatripathi6658 Жыл бұрын
There are different type of gauge of wire available in market in same category like 2.5mm wire different companies has different gauge you don't even mention a single time about gauge i want some information about it how can i contact you
@digvijaybarge2 жыл бұрын
Which cable Cu or Al for 95 sq.mm ?
@solarfacts42422 жыл бұрын
Al
@trilochanpanigrahi36812 жыл бұрын
I can't understand value of jsinφ because you take R = 0.6 and sinφ=0.6 both reading value are same so I confused. which parameter value putting in the place of sinφ
@solarfacts42422 жыл бұрын
Cos @ = 0.8 You can calculate @ Then when you will do sin @ you will get value = 0.6
@Anjalidas1999 Жыл бұрын
Fault current consideration?
@solarfacts4242 Жыл бұрын
Yes should do we will make a video where we will do that also
@UveshMohd-c3g10 ай бұрын
Why you consider current valve 139 intead of 142.12 amp ? I think there is some mistakes?
@shahidhassan7869 ай бұрын
It is because the full.load current flow is 139 amp not 142amp.
@sapnatripathi6658 Жыл бұрын
How can i contact you
@minujha82143 жыл бұрын
👍👍👍👍
@solarfacts42423 жыл бұрын
Thanks 😊
@sherrydreaming59872 жыл бұрын
Some industry is maintaining a power factor of 0.95 and if we are to choose wire size then we take solar load into consideration. e.g. if we have a 50 kw solar project then Solar load will be at a max not more than 50kw and power factor will be maintained. So can we chose the wire size on that basis or we will have to consider PF as 0.8 for all cases. Plz clear.
@solarfacts42422 жыл бұрын
generally we consider power factor 0.80 for the wire calculation
@SK-iv2fc Жыл бұрын
Plz sir relay setting calculation per video banaye
@SamarthDwivedi-tl6hm3 ай бұрын
Sir apne resistance, reactance ka value galt le liya he . Apne Resistance liya he 0.6 jabki multi core aluminum cable ka Resistance he 0.568 ohm he . Reactance apne 0.1ohm liya he jabki aluminum multi core cable ka Reactance 0.07 he. Please explain if I am wrong
@prakashmathad55632 жыл бұрын
Thank you for the good information. I would like to know regarding the K ratings.. On which basis we should we take the K ratings.. I mean do we have any BIS Or ISI to prove.. If ask someone..
@swapnilshiyaniya5306 Жыл бұрын
K ratings are given in evry company's Wire catelogue. You can find K rating as per your need
@solarfacts4242 Жыл бұрын
You can get this from manufacturer or for normal calculation I will share the link in the description
@ranjan14362 жыл бұрын
why have you taken 139 A in the voltage drop calculation whereas the current after the K factor is 142A?
@solarfacts42422 жыл бұрын
That is typo mistake
@solarfacts42422 жыл бұрын
Sorry
@raman5409 Жыл бұрын
please explain cable size of 300kw load
@Jehangir.e Жыл бұрын
Please share data sheet of current carrying capacity of cable
@solarfacts4242 Жыл бұрын
You can download for google it is easily available
@avradeepdas16062 жыл бұрын
Sir, why Value of k1,k4,k6,k7 are not considered ??
@solarfacts42422 жыл бұрын
i have considered 1
@faizuddin74892 жыл бұрын
Respected sir, Jo apne 6% ka loss calculate kiya end me wo kitni length par jakay hoga or length ko formula me kese put krengy pls sir help
@solarfacts42422 жыл бұрын
this will happen at 200 Meter already mention in Video
@whydoyouwannaknowmyname651011 ай бұрын
Correction : for voltage drop It is( 1.732*I*R*L*100) / V3ph * NO.of Run * 1000
@theemperor__ Жыл бұрын
You took sin& =0.6 Can you pls explain how
@solarfacts4242 Жыл бұрын
We know cos @ = 0.8 from here you can get @ value then you can calculate sin @
@surekhapise8978 Жыл бұрын
@@solarfacts4242 Didn't get calculation Cos(@) suppose we put 0.8 then value get 0.99 Sin(0.99)=0.0172
@rishikeshsali4753 Жыл бұрын
Can u please explain why u choose 70 sqmm directly and started selectin gparameters as per that , u didn't give any contex or explanation over there , 9.47 minutes
@solarfacts4242 Жыл бұрын
This was random selection just to check whether it is ok or not I will also share one video where you can find the calculation for the cross section of wire
@kousikchatterjee74908 ай бұрын
How to find K1= cable in Air.
@vnmbnaidutvnmbnaidut1969 Жыл бұрын
Why using 1.732x somexcable length x 100...in this why multiple with 100 ??