Hydrostatic Testing of Stored Pressure Fire Extinguisher Final

  Рет қаралды 39,531

IowaFireControl

IowaFireControl

Күн бұрын

Пікірлер: 47
@alvagood2693
@alvagood2693 6 жыл бұрын
Test pressures are not all 3 times operating pressures but by the pressure on the label. Not all extinguishers are under USDOT requirements.
@robcampbell1056
@robcampbell1056 Жыл бұрын
I own a Fire Prevention Company and have been testing Fire Extinguishers for 30 years. This is exactly what a testing room looks like. Powder everywhere. There are many other videos out there, usually by manufactures of equipment that show a perfectly clean shiny room with no yellow powder anywhere... Yeah, right... The only thing this video didn't show you is the holes in the walls because you get mad when an extinguisher goes off and the technician throw the thing against the wall. and then rights NFG on it.
@oldmech619
@oldmech619 Жыл бұрын
I have a bunch of old fire extinguishers. A couple were partly discharged. What should I do with them. 5pound
@stevecraighead4816
@stevecraighead4816 11 ай бұрын
My shop looks nothing like that and I’ve been doing fire extinguishers for over 20 years myself. I also have SOP’s in place to control the powder versus what I see in this shop. Dumping chemical into an open bucket instead of having a bucket lid on the top with a hole cutting it so just the mouth of the extinguisher cylinder fits in it. That cylinder vacuum thing from Getz is a piece of garbage. I came up with something my first week in fire protection that I’ve been using ever since 1995. Also, I don’t DOT test Ansul extinguishers because they’re not DOT cylinders
@madaneoulix1312
@madaneoulix1312 2 жыл бұрын
I work for big company that does this.. we always pressure to the end of the green just before so people can get as much use out of it as possible during an emergency.. and the hydrostatic testing in my state's only 30 seconds I find that interesting you guys have to do it for a minute
@alexrodriguez8714
@alexrodriguez8714 6 жыл бұрын
Thank you so much for this video. I just start a new job like this one.
@daveynorman4979
@daveynorman4979 Ай бұрын
why when I do a 6yr maintenance sometimes it’s leaks out even when I change the o ring need help?
@yoz1967
@yoz1967 11 ай бұрын
When a unit calls for 585 test pressure but the working gauge sets on 586 or 588 what gets recorded on the data sheet? What gets punched out on the sticker label for the hydro reading?
@joshuahandy2002
@joshuahandy2002 3 жыл бұрын
You are using the wrong Lube for Ansul Sentry Dielectric silicone compound, I like your low pressure hydro machine.
@jeffiscool1805
@jeffiscool1805 6 жыл бұрын
Good video. Thank you. Long ago I had a relatively small fire get away from me because of an extinguisher that stopped spraying long before it was empty. I honestly never paid much attention to extinguishers before that. Losing most of your possessions, your dog, and almost losing your wife and young son because of a faulty extinguisher is NOT something anyone should ever go through. Just because the gauge is in the green does *NOT* guarantee that it will function as you expect. Buy the biggest extinguisher(s) you can afford, keep it serviced and/or replace it as required. Fire is cruel, lightning fast and unforgiving.
@khawk7365
@khawk7365 5 жыл бұрын
I'm in Alabama. I am a nicet 1 and 2 alarms and level 1 inspection. What is the certification that I would need to do hydro and 6 year maintenance on extinguishers?
@bigtodd6609
@bigtodd6609 3 жыл бұрын
In Australia they don't put a verification of service collar on them after testing - They only stamp the bottle. Makes you wonder if they're Hydrostatically testing them properly.
@Krajorg
@Krajorg 2 жыл бұрын
I doubt it the majority of people probably just stamp it without doing anything that’s why we use service collars because you have to take the head off in order to put it on
@ghermansizer
@ghermansizer Жыл бұрын
They stamp the co2 bottle with the date and their R.i.n. #.
@StephenOkwara
@StephenOkwara 6 жыл бұрын
THANKS FOR THE TRAINING....I Need your Assistance on hydrostatic testing kit for gas cylinders
@williamwiwczaroski3598
@williamwiwczaroski3598 4 жыл бұрын
My questions to this video... Per NFPA 10 IS IT NOT MANDATORY TO CHANGE ALL PARTS EVERY 6 YEARS? NEW VALVE STEM NEW ORING I mean technically by the video the proper services were not completed due to that nature. If going to show on youtube shouldn't you be 100%?
@IowaFireControl
@IowaFireControl 6 жыл бұрын
Thank you for your comment and good luck to you and all your endeavors Alex
@alvaalgood9393
@alvaalgood9393 4 жыл бұрын
Also determine if the extinguisher is or is not regulated by DOT Code of current USDOT regulations.
@ernie5187
@ernie5187 6 жыл бұрын
So the powder gets discharged into the hopper. But what about the nitrogen going into the air in the room? At work we recharge 30-40 5lb. Extinguishers in 6 hours. Is it safe to breath in all that nitrogen? Thanks
@justanotherguy8791
@justanotherguy8791 5 жыл бұрын
By volume, dry air contains 78.09% nitrogen, 20.95% oxygen, 0.93% argon, 0.04% carbon dioxide, and small amounts of other gases.
@ernie5187
@ernie5187 5 жыл бұрын
Greg Dinert....never new that, So is it safe? Is it ok as long as their is good ventilation?
@chasermanx77
@chasermanx77 5 жыл бұрын
Is there a name or band of the device used at the 1:45 mark that blows out the excess powder? Or is that Custom made? I work for a Fire Extinguisher Service company in Maryland and are building out a new room for servicing extinguishers any help would be much appreciated thank you!
@joshwoodsmusic7979
@joshwoodsmusic7979 5 жыл бұрын
Chase Castle they make a vacuum device that you tip the extinguisher over and it sucks the remaining powder. He was using it in the beginning
@firealarm3915
@firealarm3915 3 жыл бұрын
What is the purpose of doing a hydrostatic test when you could just replace the extinguisher completely for a fraction of the cost?
@user-wq4qm8nj2u
@user-wq4qm8nj2u 3 жыл бұрын
A hydrostatic test is a 1/4 of the price of most new extinguishers unless your buying a junk extinguisher. Secondly it's better for the environment to reuse a perfectly acceptable extinguisher.
@firealarm3915
@firealarm3915 3 жыл бұрын
@@user-wq4qm8nj2u Ah, thanks!
@schnoodle3
@schnoodle3 3 жыл бұрын
@@user-wq4qm8nj2u I wish that were the case for CO2 extinguishers.
@ashleywhatsittoya9345
@ashleywhatsittoya9345 Жыл бұрын
Didn’t show drying process
@user-wq4qm8nj2u
@user-wq4qm8nj2u 3 жыл бұрын
He didn't replace the o ring and there's a lot of wasted movement in this demonstration. Is this how you normally do your tear downs ?
@joshuaborem7063
@joshuaborem7063 4 жыл бұрын
I'm going by memory here but I think the Parker O lube is not the correct one for that extinguisher...
@jamiemitchell8746
@jamiemitchell8746 3 жыл бұрын
Great video thanks for posting. Recently started my own business here in Canada Looking for guidance on forms for a 6 and 12 year maintenance
@talhamian
@talhamian 2 жыл бұрын
im in Canada as well and i started this business last year and ive been doing so well. very niche business
@talhamian
@talhamian 2 жыл бұрын
@@ricardovega6252 you just need insurance. I don't think you need a business license
@tarassu
@tarassu 4 жыл бұрын
What is the cost compared to new extinguisher?
@bertlarsen3202
@bertlarsen3202 4 жыл бұрын
I reckon it's about the same price
@gmc1966
@gmc1966 2 жыл бұрын
We sell new 10 pounders for around 110 bucks or more depending on the brand. A hydro/recharge with new valve and O ring,about 52 dollars
@samuelarney9224
@samuelarney9224 2 жыл бұрын
I've always wanted to do this for a living just don't know how
@prlee1
@prlee1 3 жыл бұрын
bravo colleague
@corywilliamson61
@corywilliamson61 5 жыл бұрын
nice job!
@faridulislamsardar
@faridulislamsardar 2 жыл бұрын
I am tacnichian of fire extinguisher I need a job
@على.المصرىابوابراهيم
@على.المصرىابوابراهيم 6 жыл бұрын
نبي ترجمه للطفايات فوروتش
@StevenTYates
@StevenTYates 2 жыл бұрын
2:50 do not exceed 30 seconds during pressure testing. Its not 1 minute
@gmc1966
@gmc1966 2 жыл бұрын
According to NFPA 10 standard, you are required to hold the pressure for one minute
Pipeline Safety: Hydrostatic Pressure Testing - Short Version
3:19
Fire Extinguisher Hydrostatic Pressure Test
22:22
Erick Hernandez
Рет қаралды 42 М.
Synyptas 4 | Арамызда бір сатқын бар ! | 4 Bolim
17:24
Who’s the Real Dad Doll Squid? Can You Guess in 60 Seconds? | Roblox 3D
00:34
버블티로 부자 구별하는법4
00:11
진영민yeongmin
Рет қаралды 19 МЛН
How to Hydro Test a scuba tank
5:51
ScubaTech Key Largo
Рет қаралды 22 М.
Massive Fuel Tanker Fire on I-25 Near Denver, Complete HD Fire Department Footage
54:50
Inspection and testing of fire extinguishers
26:32
Axiom Compliance Learning
Рет қаралды 19 М.
Yearly Fire Extinguisher Inspection
5:53
BYUI Fire Safety
Рет қаралды 81 М.
Hydrostatic Testing: Pressure Vessel Inspection
6:07
Mister MHW
Рет қаралды 6 М.
Monthly Fire Extinguisher Inspections | September
8:36
The Fire Extinguisher Enthusiast
Рет қаралды 500
How To Do Hydrostatic Testing Or Pressure Test For Valves | Gate Valve
10:22
Paul servicing a fire extinguisher
13:27
AllAmericanFireProtectionUSA
Рет қаралды 6 М.
Synyptas 4 | Арамызда бір сатқын бар ! | 4 Bolim
17:24