Thanks for watching please LIKE & SUBSCRIBE - Be sure to watch the end where I dissect the breaker! - Amazon Store: www.amazon.com/shop/silvercymbal
@Ovahlls Жыл бұрын
Out of curiosity, what level of protection do those latex gloves add? Do they insulate your hands?
@bluesky90932 жыл бұрын
Good video, I would like to offer some feedback however. I spent an entire career in the electrical/electronic industry manufacturing these same type of products (different brands). Please, please always recommend that the main breaker of the panel be shutoff before replacing a breaker, the slightest contact with live bus bar will lead to disaster. Second, while I appreciate you are taking precaution to wear some type of glove, those are not the gloves to be wearing when working on this equipment. Even a tiny pinhole in the glove can lead to catastrophic results, made even worse by the fact your hands tend to sweat in latex gloves, therefore please use proper electrical gloves that are readily available at Home Depot or any of the big box stores. Third, that breaker clearly saw an overload condition for an extended period, not quite enough to trip the breaker but enough to cause the components to fail over time. It looks like you have a new appliance so I suspect the prior home owner had an old washer/dryer that were not operating properly. Fourth, always install a surge suppression device in your panel to provide whole home protection, the vast majority of surges are generated within the home vs. external sources. Every time an appliance, furnace, A/C unit kicks in they create surges in your system because they all contain electric motors. Electric motors have an initial inrush current of 6-8X their normal running amperage, for example if you have a 3 amp motor it will produce upwards of 24 amps or more during startup for a very brief surge period. Surge suppression on your panel will absorb those surges and extend the life of electronics and even light bulbs. PS: I really do like your channel and the quality of your videos, you get to the point and avoid gimmicks like AMSR sounds! Nice work
@SilverCymbal2 жыл бұрын
The gloves aren't there for electrical protection, its for visibility on camera. The other feedback is all very good.
@edprior28212 жыл бұрын
As an electrical engineer, I second all your recommendations, particularly the one about turning off the main breaker before touching anything. I felt this point was glossed over too lightly: "If you're really concerned, go ahead and turn off the main circuit breaker" Strongly disagree: There is no circumstance that a homeowner should work on a live panel, and even qualified personnel should only do so only if strictly necessary and wearing proper PPE. Electrical shock isn't a joke, even at 120 volts L-G, and an arc flash can be very dangerous.
@ewicky2 жыл бұрын
That is 100% not what a surge suppressor does. It does not limit inrush, start up, or LR current. For the sake of the industry and science, I really hope you aren't actually a life-long electrical engineer.
@bnasty2672 жыл бұрын
@@ewicky That was going to be my comment as well. The typical Type-2 SPD handles transient *voltage* spikes. They are typically just a couple of cheap metal oxide varistors, which function by acting like a voltage-based switch. Connected from hot to ground (for example), it normally sits there with high impedance (off) below the clamping voltage (usually 300V+.) If the voltage exceeds that set value, it 'switches on' and clamps the voltage by shorting it to ground. In doing so, it dissipates current (that's the current rating for the SPD), but it in no way clamps based on the current flowing in your panel or from any of your loads. (it couldn't, because it's not connected in series with any of the loads)
@paulmaxwell88512 жыл бұрын
@@edprior2821 'Qualified personnel' work on live panels every day. We can't shut down entire buildings just to work on one branch circuit. And 'the slightest contact with live bus bar will lead to disaster' is not accurate. The current needs a path, and unless another part of your body is grounded you'll feel nothing. I've shown this to folks many times.
@Quanticles2 жыл бұрын
I would definitely shut off the entire panel every time
@SilverCymbal2 жыл бұрын
Always a good idea for safety
@JRPW2 жыл бұрын
"And if your really concerned, go ahead turn of your main breaker" That is a funny sentence. I actually laughed when I heard them say it and immediately when to the comments to see if others did as well.
@Dextermorga2 жыл бұрын
Good for you
@egay862922 жыл бұрын
ditto. people don't because they have electric clocks. which kills them.
@KuntalGhosh2 жыл бұрын
Real men work with live wires. Last year it was raining so bad that my basement got flooded. And that wasn't the big deal cus i had a pump and it was keeping up with the inflow. At 4am a lightning hit an antenna that i had installed for internet. It blew basically everything that was connected through wired ethernet. And the lightning was so intense it blew apart the whole house gfci. So at 5am . I was handling live 240v mains 3 phase wire (415 across phases), taking each one of them off and then connecting it to the other side to bypass the gfci. It was a heck off a job to do with some pliers and screwdriver. I could not turn the live feed off cus the main braker panel was in the basement and that place was flooded . All in all that lightning had cost me 3000$ worth of equipment and had to replace everything. Now i have fiber optic isolation for the wireless bridge.
@nErfEr3082 жыл бұрын
Definitely very scary! Glad to see what happened on the inside
@SilverCymbal2 жыл бұрын
Definitely, at least I know my money was well spent on this repair!
@AMIAmigaman2 жыл бұрын
Had worked for 23 years as a major appliance tech. Always check the screws to make sure they are tight. Turn off the breaker first. Feeling the breaker to see if it's heating up is also a good way to check it. If it gets hot, replace it. As he said, check the appliance outlet. On a 220 volt dryer or electric stove, pull plug and see if blades on male side of plug are darkened, pitted or burned. If so you must replace the cord and the outlet. Just replacing the cord and not the outlet too will just ruin the new cord. Also make sure the cord connections are tight and not burned on appliance.
@wingallowingallomy3909 Жыл бұрын
Hey bud everytime I flick my breaker switch back on a spark happens can you tell me what's the problem and how to fix it. Please
@AMIAmigaman Жыл бұрын
@@wingallowingallomy3909 Where is the spark coming from. If it comes from the breaker, replace the breaker.
@ronjon2125 Жыл бұрын
@so I have a question, had a completely burnt out breaker for my A/C.. changed the breaker but I’m noticing it’s getting really hot and tripping out especially on the hot days. 1) can it be because the wattage on the a/c unit is different from the breaker inside? I just changed it to the same ampage as the previous breaker 2) what is causing it to be super hot?
@AMIAmigaman Жыл бұрын
@@ronjon2125 If that's a new breaker and the connection to it is tight, about all that's left is excessive current draw. Is the breaker the proper amperage? You need to find out what the current draw for your AC is to see if the breaker is sufficient. A malfunction in your AC could be causing excessive current draw.
@larsonfamilyhouse6 ай бұрын
What if it’s the ac?
@MrKen592 жыл бұрын
If I’d make a suggestion - the manufacturer lists a specific torque spec for each wire size used on the side of each breaker. Definitely use a torque screwdriver as you’ll be surprised at how tight they need to be. Nice presentation and my favorite part is the dissection of the old part.
@nevoyu Жыл бұрын
Eh just get it tight enough you strip out the screw head or the threads and you'll be fine. The torque specs are really just guidance based on some to satisfy people who have to ask how tight something should be. Most of the torque specs you legit see in the world are actually just made up.
@MrKen59 Жыл бұрын
@@nevoyu nice reply :). My only argument to your comment is that you can damage a device of too tight. The notion of torque spec is based on a design point of stress vs. too loose. My goodness, I have some Eaton breakers that will strip below the torque value.
@amg863 Жыл бұрын
@@nevoyu some people really go too far with the torque specs. If they need to ask for torque specs for something so trivial, I wouldn't even trust them to set and operate such a tool in the first place.
@robertbritton656 Жыл бұрын
@@nevoyu You legit just made that "fact" up.
@robertbritton656 Жыл бұрын
@@amg863 But this isn't trivial. The fact you see it is trivial leads me to believe you shouldn't be working with electrical equipment.
@Mr-Chris2 жыл бұрын
Yep, my old 50 year old Square D panel circits started to fail one after another. They never made a noise like this, but they would easily trip all the time on a light load. breakers don't last forever. I ended up doing an entire panel upgrade.
@mmi62802 жыл бұрын
The only thing i would add is check the load and verify that you're not drawing to much current. Great catch and video!!
@SilverCymbal2 жыл бұрын
That is a great idea and I agree I should have done that. I will double check that with my clamp on meter to make sure the dryer is operating correctly.
@someperson72 жыл бұрын
Great content as usual👍🏻 I will add my voice to the others that turning off the main shouldn't have been presented as optional. The failing of the wise is that they often forget the foolishness of the inexperienced.
@10p6 Жыл бұрын
Nice. Should really be using an insulated electrician screwdriver though, or wrap the one you have with electrical tape to prevent any accidental shorting.
@onecrazywheel2 жыл бұрын
Also one thing I would add is most or all manufacturers have in their specs to replace the breaker if it trips. 😜 I would not necessarily myself but that is what they recommend. You're video was great. One thing to note is to torque your connections to spec too and each breaker has the number of inch pounds. If you have a torque screwdriver 🪛 use it. It is a great tool. I bought a Neiko torque screwdriver off Amazon years ago. I like it. Great video. Happy New Year. Jeff - Licensed Journeyman Electrician Sunny Central Florida
@turbokatzenburg5732 Жыл бұрын
Partially correct. Many say to replace if subjected to REPEATED short circuit faults or extended overloads. They will be ok with several overload trips over extended time. The rule of thumb I use is if a breaker is tripped, I will reset it ONCE. If it trips immediately, (and especially if there is a pop or buzzing sound) I will not try it a second time and will consider replacement once the fault is fixed. If it trips on overload (usually will delay before tripping again) I will try removing loads then reset a second time. If it trips a third time after load shedding, will consider replacement if the breaker is old, or gets warm when holding load under 80% of rating.
@BeyondLimits3D Жыл бұрын
I hear your point about checking the wires are tight, but honestly I wouldn't even consider touching a screwdriver to those terminals while the breaker is attached to the bus. If something is wrong on the inside, (which it is for sure, and the new one could be defective) they could be scraping your body off the opposite wall. I personally recommend removing the breaker first, then using the widest blade slotted screw driver that will fit to loosen the wires, and then using that same driver to torque the screws down tight on the wires before placing the new breaker back in. Use an insulated needle nose on the insulation of the wires to check their snugness. If they are loose, pull the breaker again and re-tighten.
@Teh_Random_Canadian Жыл бұрын
Or use and insulated screwdriver and tighten it in place
@zilufuzi Жыл бұрын
I like to use a thermal imagery camera to inspect electrical panels to see if there is a temperature differential between the breakers. It’s an easy way to quickly determine if a breaker is failing and needs to be replaced.
@willmcgo8288 Жыл бұрын
A mechanical circuit breaker gets warm through normal functioning. You have to know the specifications to know what temperature would be abnormally warm. In normal operation a mechanical circuit breaker gets warmer as more current passes through it. In the breaker mechanism, a metallic part changes length with the increase in temperature. Once hot enough the length changes enough to trip the breaker switch off. A thermal camera will tell you which mechanical breakers are passing more current, versus the ones that have less load. To make the call that one is failing based on temperature would require knowing what temperature is too hot for normal operation.
@troyf1 Жыл бұрын
Thanks for opening up the old part. The visual was awesome! It drove home the point, and seeing the point visually will be hard to forget :)
@holtrussell2 жыл бұрын
Just fixed this exact same issue in my 50 plus year old panel. Issues presented itself as dimming and surging lights on one circuit. Trip to the breaker panel revealed the same noise in the video. Replaced the breaker and issues solved. I also performed a post mortem analysis on the problem breaker and it it looked like maybe there was some corrosion on the contact points inside the breaker.
@SilverCymbal2 жыл бұрын
Very good that you fixed it!. I am surprised how breakers really aren't sealed at all, while not needing to be waterproof if you live near the ocean they must take a beating.
@holtrussell2 жыл бұрын
@@SilverCymbal Exactly. Didn’t confirm corrosion was the root cause, but didn’t see much burning similar to what your breaker autopsy looked like. Also thinking maybe the internal contacts points became loose over time. All guesses, but drilled out the rivets on the breaker to get inside just as you did. A voltage test on the circuit reflected a range under increasing loads of about 85 volts to 122 volts. Dimming and surging grew worse under heavier load. Sounded like the breaker was cooking and popping at the panel!
@turbokatzenburg5732 Жыл бұрын
@@SilverCymbal Breakers cannot be fully sealed, as the arc formed at the contacts creates a very intense heat and a brief but very strong pressure spike. A totally sealed breaker could/would explode into shrapnel under a fault condition. Large power utiltity breakers that were oil filled had pressure vents to help minimize risk of explosions, the newer SF4 breakers are sealed pressurized gas that actually prevents or quenches an arc in milliseconds, so the pressure caused by the arc is reduced/eliminated.
@Brian-cr6rb Жыл бұрын
Sometimes the buss bar is arching with the contacts of the breaker. Definitely inspect that as well. Every time I have heard that sound, lights flickering etc, it's been a bad bar. Repairing it is sometimes a double breaker and cancelling the bad spot, but if that's not possible, it means a new panel.
@robertwest3093Ай бұрын
This was EXCELLENT! No wasted time, right to the point, and EASY to understand. I’m subscribed 👍🏻
@dirkhawn6602 Жыл бұрын
THANK YOU!!! YOU JUST SAVED MY FAMILY'S LIFE AND MY HOUSE!!!
@favour81942 жыл бұрын
I have heard a humming sound out my box for about 3 to 5 seconds and it's 24y/old, I will have to get this checked. 🤜🤛
@robertthomas5906 Жыл бұрын
I own houses that have breakers that are coming up on 60 years old. They still work. Bulldog pushmatic. There's nothing wrong with square D. I own houses with them as well and that's a fine panel. The only problem with modern breakers is the oil in them sometimes gets hard. It'll trip. Then you won't be able to reset it. You'll have to replace it.
@r4rq291 Жыл бұрын
My house's kinda old already, some times I can hear a louder humming sound than normally while walking past the electric board, anyway there are cables in there circled up kinda like reels, my father says it is because of that, he has more knowledge on this than me so I assume it's fine?
@KevW-z7z10 ай бұрын
How did you trace which one?
@landonferguson7282 Жыл бұрын
Just found a breaker making a similar sound as yours, since I had watched your video when it came out, I was able to remember that this was a problem and switched out the breaker. When I took the old one apart, it had the same discoloration on the wire as yours did.
@backinyourcommentsectionag3191 Жыл бұрын
Hey! this is the exact same failure of a breaker I saw in my own! First breaker I ever replaced actually. Made that same exact noise too. It worried me for awhile, but I shrugged it off at first, only for it to completely fail. I eventually mustered up the courage to learn as much as I could not just about replacing a breaker, but about the electrical system we use in the US too. But it was kinda cool too see what could've happened on the inside of the breaker. Might have to open mine up too (I kept the broken breaker) And I'm sure you have already heard from the other 143 commenters that's it's pretty ill-advised to work on a box like that with the main breaker open, one wrong move and it could've been game over! I already know you know this, but it's important to make sure that your viewers understand that fact, since novice me a couple years ago might've stumbled upon this and tried to do a breaker repair with the main breaker closed*. Also, you'd think they'd break more often being named "breakers", huh?
@backinyourcommentsectionag3191 Жыл бұрын
@@jovetj Oh whoops, I got mixed up there I meant to say closed there lol But I'm sure it is if you're comfortable with working with it and have proper safety gear
@markot99022 жыл бұрын
I've had exactly a same situation. One of the c. breakers was making buzzing sound when electric stowe was in use.... After cpl of years I've had it enough and replaced it by myself. At a time of replacement, that c. breaker was 20 yrs old. Others are still silent and in use ( abt 25 yrs at this moment).
@mariekrasch5032 жыл бұрын
You videos are really informative, and produced with excellence. You include many points in a short video, with clear images to exemplify what your are talking about. Thank you very much!
@SilverCymbal2 жыл бұрын
Thank you very much! I appreciate the nice words
@DelfinaKS Жыл бұрын
I agree with you. I also would try to not replace things if we can somehow make them work a bit longer but here safety comes first. We should not be taking any chances with circuit breakers!
@MrWolfSnack Жыл бұрын
there is no way to repair a circuit breaker. if it goes bad it goes bad. most people having them go bad are 50-60 years old or older, that's way beyond their service life. the reason people piss and moan about replacing them is each breaker will cost about $60-$100 each, it's a lot of money and people see this little chunk of plastic and can't understand it costs so much. i get all kinds of used and vintage ones for less than a quarter each at the junk store because I like to collect them and preserve the history, but i'd never in a million years install one in my house.
@VolksDude2 жыл бұрын
I think there’s a torque specs for the terminals
@briancnc2 жыл бұрын
That's pretty concerning, never seen this issue quite like you describe or show. Do you have a thermal IR gun to take a look for any hot spots elsewhere in the panel?
@tylernixon3657 Жыл бұрын
Thank you silver cymbal. I have literally the exact same problem, panel and breaker! Thank you for helping me with this problem!!!
@oddjobz9858 Жыл бұрын
QO’s are top of the class out of all the companies and styles I see more QO’s from the 50’s out there still there a robust panel
@jamescady7232 жыл бұрын
I really love your videos. All of them are well thought out and very useful. Many thanks for the channel and a happy and prosperous 2023 to you and your family.
@Marco9112 жыл бұрын
For single wire assignment, the wire should always be placed on the left side of the screw. This way it will be pulled in when tightening. On the right side it is rather pressed out.
@GaryT19522 жыл бұрын
🎯 I thought the exact same thing...in fact it looked as if they did twist out a bit as they were tightened
@wild90852 жыл бұрын
This, this and this. Dude is smart but even the smallest mishaps can cause a ton of damage.
@nefariousyawn2 жыл бұрын
He demonstrated placing the wire between the clamping plates, so I don't think that is the case here.
@r7boatguy Жыл бұрын
Makes no difference with these clamps. These breakers can have two wires on each terminal.
@brianharmeson3144 Жыл бұрын
It isn't pulled or pushed when the screw is tightened. It is secured by a hold down plate.
@WigWoo1 Жыл бұрын
What should you do for a manufactured home circuit breaker where the entire panel is fixed and you can't replace individual breakers?
@Teh_Random_Canadian Жыл бұрын
What is the make and model of your panel? Have never heard of this.
@johnc8112 Жыл бұрын
Going to be changing my garage breaker for it does the same as you said hums. Thank you for this video
@BR218fan Жыл бұрын
You could definitively hear the arcing inside that breaker and it was about time to change it. This was a good video, but I would recommend to turn off the entire panel before working on it, as other people also have commented (also look out for other sources like solar systems etc and turn them off). Then it is best to make sure there is no voltage anymore using appropriate tools. And most of all: if you are not absolutely sure what you do and how this works, get a certified professional to repair the panel for you. Bad connections for example can cause fire and electricity can be lethal if somethings goes wrong. There are some other comments explaining a little bit more things to consider. Be safe out there!
@IamNerfDart Жыл бұрын
I have a dimmer in my house that when it's turned on makes the panel buzz, but it's more of a high pitched whine. You can also have a low pitched buzzing noise if you have a lot of current draw through a breaker or panel. Zapping sounds like he had, are not normal though.
@Mike.D.8432 жыл бұрын
I had to replace a 30amp for my package AC unit in my square D panel a few months ago for the same reason. It was making similar sizzling noises, but it was also getting hot to the touch. Not hot enough to burn you, but hot enough to make you pull your hand away quick if you touched it while power was going through it. Non of the other breakers were even warm at all. That was the only one. I went and bought a new one, swapped it out. Took a few minutes. The peace of mind knowing that issue is fixed is great. I am fortunate enough to have a service disconnect outside by the meter, so I can shut off all power going into the house which makes it super safe to work in the panel if I need to.
@keithfadden7316 Жыл бұрын
Is it possible that this breaker issue was also consuming more electricity than necessary and inflating the electric bill?
@pofjiosgjsoges2 жыл бұрын
Invest in insulated screwdrivers. Yes they cost 20$ but you never know when your hand will slip and touch a shaft that may be live.
@lounar482 Жыл бұрын
Man! Great advice. I've got a 240 breaker that feeds a sub panel that makes a strange noise. Definitely going to check that!
@munozinni2 жыл бұрын
One of my customers said he is going to call the utility company to shut off the entire neighborhood so we can replace some receptacles and breakers in his house 🤣😂🤣😂🤣😂I laughed and I said step aside mister mom and get your check book ready 🤣😂🤣😂🤣😂
@n1umj Жыл бұрын
I had an electrician ask my power company to shut us off at the pole so he could move the meter a few years ago. They laughed at him, literally. It was an old house with the electric meter in the cellar, real PITA letting them in every month to read it. We had a fuse box replaced with breakers anyway, he figured he'd move the meter. He wound up doing it live but liek he said, he could leave it disconnected at the meter while he swapped out the fuse box for a breaker box and it would be the safest one he'd done then connect the meter when he was done. It worked out.
@munozinni2 жыл бұрын
Hola señor Silver Cymbal I just wanted to say hello 👋 and to let you know that I had enjoyed all your videos last year and this 2023 I will keep supporting your channel watching the videos to the end give like and comment sharing with friends and family and I want to share some with you that already happened in different times of my years working in remodeling and the last time was in my own house… long story short when you issued the noises in the breaker I had the same noises in my kitchen light switch and let me tell you what was causing it and the problem was 🐜 ANTS yep my teens have the problem of leaving cups with juice and you know ants love that well some how they found a way to get in the kitchen from the outside wall and somehow they got inside the switch box so I heard the noise and the lights were flickering and I remember that from the past I was remodeling a house and the kitchen had the same problem so when I removed the switch plate I found a cluster of tiny roaches 🪳 around the electrical conectora of the switch and that was the problem I guess the roaches arch the electricity and causing the lights to flicker and the switch to make those buzzing noises replaced with a new one pest control exterminated all the bugs and problems solved and the problem in my kitchen I removed the switch plate or cover and I found a cluster of black ants all over the switch connectors and I just cleaned it with the vacuum cleaner and let it air for few hours and it’s working properly perfect flickering stopped and the buzzing noise stopped and that’s what happened to me in my own experience I wish I had all that on video so I have proof of the problem so if you think you can give me a scientific answer for that I will love to hear you keep up the great work señor Silver Cymbal 😊
@N20Joe Жыл бұрын
That sound terrifies me. I once had a dryer cable burst into flame after making that sound, Luckily it was right next to the main panel and I was able to kill the breaker and stomp out the flame, then tore the whole circuit out. The wire was originally hanging loose way out of the wall and must have gotten damaged at some point. I later talked to the homeowner and he casually said that it's DONE THAT BEFORE!!!
@jack83562 жыл бұрын
Most of the time the wire needs to be tighten down. I found a wire that was just sitting on the breaker (like right on top of where its supposed to go in). Because they stripped out the screw
@lgoamity Жыл бұрын
Nice reminder thanks. Have a Buzz that seems related to my Water Heater and/or Dryer Circuits that I should investigate. On a related note, Recall a while ago after some "minor" Panel work noticing my Water Heater Timer (Time of Use Digital Timer) wasn't working anymore (No manual override). Thought for sure it was horrible timing it chose just that time to die. Apparently my "minor" work did somehow result in one of the Water Heater's wires actually coming loose from the Breaker. (Was likely sitting "loose" inside the breaker for a while, glad it didn't cause a more serious problem/surprise) Will definitely try and monitor for heat,buzz, and check the torque on any "suspect" breakers and replace accordingly.
@davefranz87667 ай бұрын
Il bet that the contacts were not fully pressed together iside the breaker, a manufacturing defect. This would be the cause of the arcing & overheating. I had the exact same breaker at my sisters house just drop one leg to the electric dryer. I went & got a new breaker & everything was ok. You were VERY SMART by checking these BUSBAR CONNECTIONS because on many panels the busbars are made of aluminum. Ive often seen where the connection between the breaker & the busbar is FRIED. This is when you would need a new panel. I was an electrician for 40 years. I used primarily Square D QO & when money was an issue a Siemens panel with the COPPER BUS OPTION. I ABSOLUTELY HATE ALUMINUM BUSBARS. Ive had to replace so many burned up panels because of this issue. I was most comfortable installing the two panels I mentioned above. Its always better to shut off all the breakers first before shutting off the main because every time you open the main under a load you pull an arc on those contacts which will weaken this master main breaker over time & it will start tripping for no reason at all. I had a customer that if she ran a vacuum cleaner the 100 amp main breaker would trip thinking it was overloaded. When I took it apart I could see that the CONTACTS were dirty from this breaker being turned off under a load way too often. This is why I recommend that you turn off all the smaller breakers first then the larger ones for subpanels ect and then last but not least then you can open the master main without causing harm to the contacts.
@lgoamity Жыл бұрын
Have a Sense Power Monitor installed which uses a set of Clamps to monitor the Wattage used @ the Main Breakers/Main Service Panel. Been thinking a "Buzz" I've been hearing is from those Clamps but then again they might be masking the fact that it could be that or a combination of various breakers reaching their end of life? Suspect my Water Heater and Dryer Breakers are two of the "Hardest Working" Breakers with almost daily regular heavy use year round... Even though the Water Heater is on a Time of Use Timer (meaning it is Off for maybe 12 hours a Day) I suspect it and the Dryer would be the ones to show the most damage from actual use. They tend to see heavy use at the same/similar times so because of their age it might not be a bad investment just to swap 'em out (or at least have a spare handy if needed when the day comes)
@cmendla Жыл бұрын
You said to replace the breakers with the same brand/model. I heard something about challenger breakers which, if I'm not mistaken, need to be replaced with a compatible model of another brand.
@SkylineFinesse Жыл бұрын
Hey everyone I’m a youngin in my first home, built just over a year ago and I’m hearing buzzing at the breaker, should I check elsewhere as well? Could a loose connection further a way lead to problems at the main panel? All help is greatly appreciated!
@Bendigo1 Жыл бұрын
If you are hearing a buzzing at the panel, there is most likely a problem in the panel, but there may be issues elsewhere because of or causing some problem within the panel.
@mr1pearl Жыл бұрын
Really good one sir thank you much !
@BrBill Жыл бұрын
I had one making that sound when we moved into a new house. Turns out the wires connected to it were loose. Tightened 'em up and the sound went away. 15 years later when we moved out it was still working fine.
@geneard639 Жыл бұрын
When buying a new house? Checking the age of the electrical panel and its breakers by the prospective home owner is a must. It helps if you have an IR camera for your cellphone so you can check the panel out to see if anything is overheating.
@30mAkills2 жыл бұрын
Question: Why terminal screws become loose? Answer: Creep (or cold flow) is the tendency of a solid material to move or deform under the influence of extreme loading or varying temperature conditions.
@pommy_the_mimic Жыл бұрын
2:30 - You're right about putting the wire between the two plates, but you're wrong about which side of the screw you put it on. ALWAYS put the wire on the left side of a screw. This will help guide the wire around the head of the screw when you torque it down which creates a better connection.
@Teh_Random_Canadian Жыл бұрын
This is a window clamp connection... it does not loop around the screw, it is held in place by compression, it does not matter which side it is on
@juanquinones2 жыл бұрын
You should make a video on how to install a sub panel.
@trueheritageinspections6354 Жыл бұрын
Fantastic explanation. Loved getting into the breaker. Just subbed.
@wmcomprev2 жыл бұрын
If not sure how tight to get the wires, the breaker should have a torque spec printed on it. It will probably be in in/lb. Use a torque screw driver to tighten the screws and you won't go wrong.
@robertthomas5906 Жыл бұрын
Could just make it German tight - Goodentight. Have to use the accent.
@wmcomprev Жыл бұрын
@@robertthomas5906 😂 True. My comment was only for anyone worried about making sure it met the spec. This would guarantee them that they had it correct. The rule I usually hear from electricians is to tighten the screw until you hear it squeak on the wire.
@JohnAbrahamCA Жыл бұрын
Don't you have to use an insulated screw driver even though the breaker is off? It could slide and touch any live wire or bar unless the main breaker is off which most won't do anyway. Also best practices are wearing proper gloves, not latex and keeping one hand behind when working on live breaker panel
@assassinlexx1993 Жыл бұрын
Outdoor breakers work different in really cold weather. 15 amp breaker supply enough to run a block heater ,battery heaters, interior heater. Plus the extention cord is warm enough to melt the ice and snow. So the cord is trapped in soild ice till spring.
@lyfandeth2 жыл бұрын
Thermal breakers are cheaper and more common, but magnetic breakers do last longer. Modern codes may call for GFIs AND Arc Fault protectors. The arc fault protectors cost more, yes, but they'll trip out and cut off power when that sizzling arc happens.
@charletonzimmerman4205 Жыл бұрын
Back in 1974, US Capitalism, ditched the "Magnetic" full size, MCB, for the 50%, cheaper, THERMAL, even though that "SHUNT" cable in this breaker, is "Listed" Magnetic, the action is fully "THERMAL.
@turbokatzenburg5732 Жыл бұрын
@Lyfan Deth Wrong, an arc fault breaker will NOT detect the arcing inside itself, as the contacts and that braided lead is upstream of the sensing circuits.
@turbokatzenburg5732 Жыл бұрын
@@charletonzimmerman4205 Also wrong. Except for GE and one other brand I can't recall at the moment, ALL SqD and other makes use a metal plate and lever type of construction that give them a true fully magnetic trip function. They just don't use a full coil of wire like the older makes (and many UK brands) do. And the switch had NOTHING to do with any sort of government or regulatory conspiracies. It was all about better engineering and cost savings.
@charletonzimmerman4205 Жыл бұрын
@@turbokatzenburg5732 Sorry , obviously You're not as old, as me. I was in electrical Contracting, 1972-1976. Yes Indeed, their was "Fully Magnetic" breakers, "Murry" and later "ARROW-HART", they folded as companys like - "Zinsco" & "Federal Pacific", came out with "Listed" UL, thermal, @ 1/2 price, I went out of Business, cause I "Refused" to Install those brands. "Cheap" defective wo0n, but I could sleep @ night as None of my Houses "BURN'T".
@turbokatzenburg573211 ай бұрын
@@charletonzimmerman4205 Am I supposed to be impressed by your FOUR years of "electrical contracting"? I have been an electrician for over 42 years, and worked for a few manufacturers of electrical equipment including breakers, as well as doing refurbs and testing of breakers of all kinds. You cannot even form coherent sentences in your comments. But whatever, at least you went out of business which saved a lot of people.
@Pete.Ty12 жыл бұрын
👍👍👍 Wishing a happy healthy and prosperous New Year to you and your family.
@BillsCountrysideAdventures2 жыл бұрын
In the UK we are not allowed to touch inside the consumer unit or used to be called fuse box. But your good to check this as that might have caused a fire. I'd say arcing might have been the noise. If it's that old, maybe complete board change, might put your mind at rest. Also always pen test before touching terminals and use vde screwdrivers. Noticed you used vde once, but not safe pratice.
@dsma20232 жыл бұрын
We have a bit more common sense in the US, so we can do our own light electrical repair without fear of government shunning.
@robertthomas5906 Жыл бұрын
We're not supposed to either. In fact, I was surprised to find out I can't even re-wire a lamp fixture. Some of this is state law, and others are county. I think most if not all of the country we're not supposed to be in that panel though it's done all the time. I'm surprised at how much is done by licensed businesses that never get a permit for things that require it.
@theelite1x721987 Жыл бұрын
@Robert Thomas must be just your area. In my state you as a homeowner can do whatever electrical work you want, even replace a panel. So long as you get proper permits and inspections. I've honestly never heard of any place in the US where you are strictly forbidden to touch the panel as a homeowner.
@theelite1x721987 Жыл бұрын
@Lucky Joestar but homes in the US are supplied 240v split phase so going into the panel will expose you to 240v just the same. Each hot to ground is 120 but if you cross between both hots you'll get 240v as they are split phase
@gtb81. Жыл бұрын
@Lucky Joestar we also have 240v in america, the breaker he worked on is 240v
@semibiotic Жыл бұрын
That sound from good breaker is the sign of triggered thermal protection on slight overcurrent. Thermal protection allow breaker to pass such current for minute or so, before circuit break.
@dXxSHAGGYxXb Жыл бұрын
People please do not loosen the wires on the circuit breaker before removing the breaker from the panel. Unless you are turning off the main power to your home before doing so. If you loosen the wires before removing the breaker, you run the risk of the wires bouncing around in the panel and making contact with the still hot connections on the inside of the panel.
@splatteredmoon7 ай бұрын
Thank you. I just bought a camper and nothing worked. The main will make a frying sound before tripping.
@johnross63142 жыл бұрын
Important video for recently or year old EV charging system. Go back in, check QC. Do this routinely.
@heroknaderi Жыл бұрын
Wow 😮 very informative video.
@Rebecca_The_Dragon2 жыл бұрын
excellent home safety video A++
@LBCAndrew Жыл бұрын
I highly suggest to anyone looking at doing this that they first purchase a non-contact voltage tester. It's a great fail-safe so you can be sure there is no voltage in what you're working on. Just press the button and point it at various places in the panel. its also handy for replacing switches, outlets, etc.
@jamessmoth8683 Жыл бұрын
What is with the red thinner wire wirenutted to the thicker wire on the left of the breakers
@dawn1berlitz Жыл бұрын
my moms circuit panel is old as heck and only i think it was conneticut electric makes replacement breakers for it the panel is a old ITE pushmatic panel...i know it should probably be replaced but we are to poor for that and as far as we can tell the panel has been working fine
@DanG85 Жыл бұрын
I had a breaker that was playing the exact sound of my washing machine running like a cheap radio speaker. I called an electrician. He barely touched one of my 220s it tripped and would not reset again. He ended up finding a third one that was also very weak. More recently I had other work done and while they were working I had the entire panel replaced. It was original in this house and would be 40 years old now.
@ronduz12812 жыл бұрын
Watching this guy with latex gloves in a panel, wow, so much for arc flash protection Even turning off the main , you need to confirm there is zero voltage Main breakers fail too. If your replacing your panel Stay away from push on style breakers, always use bolt on
@SilverCymbal2 жыл бұрын
I never said they were electrical gloves, they are for camera visibility. You wont be finding bolt on breakers for residential panels, commercial yes.
@ronduz12812 жыл бұрын
All manufacturers make single phase panels that can be used for residential applications In your video, you missed the most important step confirming zero voltage
@RandornCanis Жыл бұрын
4:26 Those are quenching plates. Not much to do with the circuit. That contact is quite far from the bimetallic slow trip. I think I'm seeing a missing contact pad on the entry side. That would definitely burn things up right where you're seeing.
@95dodgev102 жыл бұрын
First step: hope breakers are still available for the panel you have. I am one of those unfortunate ones that breakers are no longer made for my panel. Atleast this is what i was told when getting a quote for a geothermal system.
@rupe532 жыл бұрын
you can still get breakers for almost any older panel. The question is cost versus quality of the overall job. I worked with many electricians who might special order a replacement for a Wadsworth, Pushmatic, etc.... but the point here was as a repair instead of a $3k panel replacement in an older home. The current customer is 85 years old and not likely to make any changes to tax the system.
@95dodgev102 жыл бұрын
@@rupe53 i would expect them to be available but according to this guy they aren't and i haven't got around to researching myself. I have 2 westinghouse panels from 1965. Beyond that i don't have any part #s or anything readily available.
@theelite1x721987 Жыл бұрын
@95dodgev10 some of those really old panels truly dont have breakers available. Sometimes it's because for safety reasons (see stablok breakers by federal pacific...) other times it's simply obsolete. You may be able to get breakers but special order low production replacements will cost you a lot. If panel is that old just replace it.
@95dodgev10 Жыл бұрын
@@theelite1x721987 thats the plan. My brother is an electrician and can help me out and the house needs updated wiring as well. Nothing crazy old and dangerous but its not grounded. I'd also like to consolidate my 2 old main panels plus a small added on sub panel into a single new panel.
@BariumCobaltNitrog3n Жыл бұрын
You could have a sub-panel installed next to or near the main panel. Use an existing two-pole breaker to power the sub and run the orphaned wires (and all new circuits) to the sub with all new breakers.
@stuartgray5877 Жыл бұрын
At 2:47 you show the contacts for the wires on the breaker. The upper plate on the right is rotated ~20 degree clockwise and would not compress the wire correctly. Get the two plates to line up properly before tightening the screw.
@hunley40267 ай бұрын
What’s with the latex gloves?
@andrewphillips81982 жыл бұрын
Interesting. Thanks for info.
@jimmydawn823710 ай бұрын
The noise was driving me crazy! So I got on KZbin. Couldn’t find the correct answer until I found your video. I just cut my 13 off which was the heater and it stopped! But the thing is It cut my whole wall central electric box off!? What should I do
@jimmydawn823710 ай бұрын
Continue: No I can’t cut on air or heat. But the noise has stopped! Is there anything I can do before calling the landlord. But the noise did in fact stop after cutting off the #13 heater. It shut down my whole central heat and air and my wall box where I cut the air and heat off isn’t on. But it completely off. It’s electronically box
@The1realro7 ай бұрын
Did you ever get this worked out? I imagine replacing the breaker that was buzzing would be the remedy.
@gytano6430 Жыл бұрын
I don't mean to bring it up but this is really bothering me. If it helps 1 person, this complaint is worth it. At 2:40 in the video, your showing the "correct" way to place the wire between the plates. The way the plates are sitting with the wire, the wire is not in the hump created for the placement of the wires. The right wire is truly bad. When under load, the hertz vibration and the heating and cooling of the wire at that location will cause that connection to most likely become loose, create arcing and carbon buildup resulting in loss of power. This result often ends up with a melted wire and a damaged breaker (and possibly damaging the bus bar of the panel, including neighboring breakers). Overall, very positive video. Thank you.
@crazypete3759 Жыл бұрын
"you want to get the exact same breaker that is in your panel" ... YES and NO! Sometimes you get a breaker that is the wrong one that someone had previously replaced... Make sure the breaker you buy is the one the *PANEL* requires. They do have cross reference charts for other brands that will work in your panel but I always prefer using the one the manufacturer recommends.
@sarowie Жыл бұрын
3:06 did you notice, that you inserted the wires on the right (down in the video), while the wires on the others are on the left (top in video)? see also 1:50. It's a subtle detail, but there is a technical reason why one is "preferred": the turning of the screw slightly pulls in the wire when screwing tight. the way you put the wire in, the wire is slightly pushed out. It is no big deal when you carefully watch what you are doing, but it can be a benefit when you wire up breakers all day long.
@KevW-z7z10 ай бұрын
How can you figure out which one it is? Mine only hums for half a sec now and when when i walk by..... no clue which one it is. None of them are warm
@romeo24737 ай бұрын
It’s quite easy. Check them by elimination. Assuming it’s not continuous, just plug in different appliances in their appropriate plug and go to the panel or you can turn off the circuit breakers one by one.
@YourAverageReviews2 жыл бұрын
Why is the loop a bad idea? I am just curious.
@glasshalffull29302 жыл бұрын
The plate style connector is ‘not’ made to have the shepherd’s hook. If you look carefully, there is very little space to even get a loop in there even if you tried. Not just breakers, but some receptacles have this system of clamping.
@YourAverageReviews2 жыл бұрын
@@glasshalffull2930 thanks for the answer! I've never messed with my breaker box, but I wouldn't have known that information had I not watched this video and it just made me curious. I appreciate you answering!
@Junimybbyy14 күн бұрын
What if swapping the breaker doesnt stop the humming???
@rhondamatherne8557 Жыл бұрын
My mother is hearing a buzzing sound in every room in her home. It is keeping her up at night. This buzzing sound is the same frequency from one end of the house to the other. She has unplugged all her small appliances and the sound is still there. It’s been going on for almost 2 weeks. What could this be?
@Mobiltelekomnet2 жыл бұрын
How to connect the solar generator to the circuit breaker?
@SilverCymbal2 жыл бұрын
I have a video on exactly that coming in about 2 weeks. I am finishing these upgrades and then I will be showing exactly how it ties into my system
@Mobiltelekomnet2 жыл бұрын
@@SilverCymbal waiting for that, its gonna be great thanks :)
@ChiNguyen-wf1qt Жыл бұрын
Do new breaker rattle while being shaking?
@user-em6ie2be7x2 жыл бұрын
Question if a circuit breaker is broken NO power will go through wherever those wires are going to or the room itself will it?
@williamchachko3032 Жыл бұрын
There should be concern on using the breaker models specified by the manufacturer. The panelboard is tested with this panel/breaker combo to handle a dead fault, (SCCR or withstand). It is also important to reinstall the door/trim as these breakers shown are pushing in style (not much is holding the breaker in place) and the door helps keep the breaker in place when a fault occurs.
@Isimplydoes Жыл бұрын
Why do you have QO breakers in your house?
@RenatoLaporte2 жыл бұрын
Something out of curiosity. How many rooms does this house have? I always see American houses having panels with a load of circuits, I get that most houses are bigger, but that much? 😅 U guys separate 1 breaker per room?
@theelite1x721987 Жыл бұрын
Code requirements. Let me go with kitchen as an example. Counter tops need a minimum two 20a circuits. Dedicated 20a circuit for microwave. Dishwasher must be on own circuit. Garbage disposal isn't required to have its own but a high power disposal is best served with its own breaker so its normally done that way. Refrigerator gets its own circuit. The lighting will be on another circuit as you don't want kitchen to go dark when you pop a breaker. So in this very basic kitchen example we are already expecting to see 7 breakers just for the kitchen.
@RenatoLaporte Жыл бұрын
@@jovetj The whole ring circuit and fuses on plugs are a British thing, (or were, even in the UK they mostly opt for radial circuits now). My sockets are all connected to 16A breakers and a single breaker will feed multiple sockets and light circuits. Exemptions are “heavy duty” appliances like heaters, AC and a cooker, they will normally run in a separate circuit. I think that a combination of size of appliances and less regulations regarding energy uses might play a part in the difference in the panels and in the nr of circuits. A canadian friend that helped me with moving, was shocked when he discovered that a fridge, washer and dryer were all running from the same socket using a extension cord (mind you, even the cheapest cords will have a 3600w rating, and thats the max the circuit will handle the circuit maximum output anyways), a regular European fridge (small by American standards), a front loader high efficiency washer and a heatpump dryer will sip energy compared with similar appliances over the pond.
@mabbaticchio2 жыл бұрын
My breaker for my kitchen microwave hums a little when the microwave is on. Definitely not sizzling like yours. Would you change that breaker?
@SilverCymbal2 жыл бұрын
That is likely normal. But I would keep an eye on it to make sure it doesn't change.
@rickyparrish8310 Жыл бұрын
When my auxiliary heat on my heat pump come on the breaker would trip i didn't think about that so when the tech told me that is what was wrong and i would have to get an electrician to replace it i went to one of the big hardware stores didn't one like it went to the other ones found one replaced it after a few months it tripped again replaced it and this one has been going well since the first replaced must have had a problem in it but the 2nd has done well cut the main breaker off for safety
@bubbatime Жыл бұрын
The side of the breaker has a inch pound rating that you are supposed to torque your screw terminals down too. Almost no one ever does. But if you finally do break out a proper torque wrench, you would be shocked to see just how tight the specification is. Most are under-torqued.
@loveeveryone8057 Жыл бұрын
I had a problem with a 15 amp breaker that was humming, tripping and eventually burning out the breaker. What the problem was, ...I tracked the wire from the panel to the various junction boxes. In the first junction box, two (neutral) white wires were loose and not making a full connection. So arcing was happening. Once I tightened the wires by twisting the wire marret the problem was solved. Lose Wires not fully making contact in the circut.
@mydogpeaches1 Жыл бұрын
good old square D these are good but for some reason they like to do this on the 230 240 volt breakers most of the time i have seen you shut them off and they don’t turn back on or they lose one side and you only have half off your voltage i believe you were having this problem but found it before you lost one leg of power any manufacturer can have problems but i see it more on these breakers most of the time it’s a dryer or a/c condenser or air handler almost always a 30 amp breaker it’s strange i wish they would look into why it happens but i will say this it’s always been a safe contained failure within the breaker i have never needed to do anything but replace the breakers so i guess its a good design and it just happens
@NeneExists2 жыл бұрын
Breaker out of panel: uses insulated screwdriver Working inside live panel: non-insulated screwdriver Don't count on those thin nitrile gloves to save you
@BariumCobaltNitrog3n Жыл бұрын
Neither was insulated.
@NeneExists Жыл бұрын
@@BariumCobaltNitrog3n you see that red coating on the shaft at 2:18? That's plastic insulation to stop you touching the metal bit whilst you're using it
@BariumCobaltNitrog3n Жыл бұрын
@@NeneExists I missed that one oops. Never seen one so shiny and clean. No need for the dig though. I was looking at the last shot of him dismantling the breaker.
@patricknedz Жыл бұрын
Guess this won’t be an issue for me, still running off a fuse box. It just sucks if a fuse blows and needs replaced.
@The333Wanderer Жыл бұрын
Thank you for the information
@DREKOWICK696 ай бұрын
it's weird, I recently replaced two breakers and worked for about a day and then the next day ( today) it started acting up again. and it's only happening when the dryer is going
@glenmartin2437 Жыл бұрын
Thank you for your video. Yeah, turn off the mains. Safer.
@davidpatriot10822 жыл бұрын
good valuable video, thanks bud
@randytorboli Жыл бұрын
I've always heard a small buzzing sound from the circuit breaker feeding my electric furnace in my mobile home and apparently it's normal but recently I've had the breaker trip randomly for no reason now would that be something I should be concerned about
@randytorboli Жыл бұрын
@@jovetj so far it's not getting hot or anything but I've been keeping an eye on it
@randytorboli Жыл бұрын
@@jovetj not like it was but I did notice that the cover for the circuit breaker box was loose so I tightened the screws holding it on and ironically the noise is gone so it might have just been that causing the noise and it hasn't tripped anymore either so it might have just been a power surge that caused it to trip like it did