The EV-AD2-EXT address programmer is used to set the address of analogue addressable device using the Evolution communication protocol.
*How to Set the Address?
1. EV-AD2-EXT require two 9v batteries. Insert the batteries with correct polarity.
2. Turn the power switch ON. For one second, all the LED's are lit and the buzzer sounds.
3. Plug the device/ detector on the base.
4. Press the search key. The buzzer sound.
5 The 7 segment LED reads Customer code, Type of detector , Address in turn.
6. Use +100, +10, +1 keys to select the new address.
7. Press the Set key and wait a while the display will show the New address and ok LED lit Green.
*Function Key:---
Ok LED (Green): Lit when the programming of new address is completed.
ERROR LED (Orange): Lit when the programming of new address could not be completed.
7 segment LED: This display the address, customer code or type code.
Power LED ( Green): When the power is switched ON, this LED will be lit. If “Low Battery”, it will blink.
SEARCH SW: To start transmission and find the address of the detector/module.
+100 SW : Increased address by one hundred.
+10 SW: Increased address by ten.
+1 SW: Increased address by one .
SET SW : To set device address.
Base: For connecting the detector.
RJ45 Socket: For connecting the module.
POWER SW : To turn the device ON or OFF
Plug Adaptor: For the AC Power Unit.