3 PHASE LOST NEUTRAL - WHAT HAPPENS - WHY IS EQUIPMENT DAMAGED - A LOOK AT THE THREE PHASE WAVEFORMS

  Рет қаралды 17,500

LEARN ELECTRICS

LEARN ELECTRICS

Күн бұрын

Пікірлер: 105
@Jim804
@Jim804 Жыл бұрын
Dave thank you very much. When you make explanations like these with diagrams it’s like I’ve just saved weeks if not months of time trying to work it out for myself or from other experienced electricians trying to explain what’s going on verbally.
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Thank you for the great feedback. I try my best and its nice to know that its appreciated. Thanks again, Dave.
@Jim804
@Jim804 Жыл бұрын
@@learnelectrics4402Have you made any video’s on reversed polarity Dave? Again an electrician was trying to explain to me how it works with the example of If the earth becomes live & so on. But I didn’t get it.
@Ibrahim-vt2tz
@Ibrahim-vt2tz Ай бұрын
This video was useful as always and very informative. I want to say my gratitude and best regard and thanks to you very knowledgeable man. You’re actually teaching people lots of things that they never learn in colleges especially in fast track courses and people learn nothing there. you never become Electrician in four weeks time unless you are the Moses is so difficult. It’s so difficult. It’s so difficult really to become a Electrician you have to sacrifice a study work very hard and isolate yourself with so many things and it takes time. I will say it takes at least 10 years for somebody to be confident to touch three phase Electric and understand the fault finding character characteristic understand how everything work understand Danger and makes the installation safe according to regulations so I have been studying this videos over the five years and each videos I have been listening maybe 20 or 30 time and every time I learn even extra point so I want to say thank you and show him my best respect in regard for the knowledge you’re having and also sharing with people for freeYou are a very generous man and I wish you the best in life and God bless you.❤
@learnelectrics4402
@learnelectrics4402 Ай бұрын
Thank you for the great feedback. You are doing the right thing, learning a little every few days. This will help to build up your knowledge in a great way. Supplement this with practical activities and you will have a good career. Dave.
@CbrigBear87
@CbrigBear87 Жыл бұрын
You are a gentleman and a scholar, sir. Keep educating! I'm sure many apprentices (and myself ha!) appreciate your lessons/explanations.
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Thanks, will do. If we don't pass on our skills and knowledge who's going to fix my lights in the future. Thanks for watching. Dave.
@alinili5569
@alinili5569 Жыл бұрын
when loosing N On supply side It’s best to switch off the main switch To Avoid damaging single phase Equipments- very helpful video as always thank you Dave
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Thank you, really appreciated comments. Dave.
@michaelcostello6991
@michaelcostello6991 Жыл бұрын
Great information. We have a few single phase VFD motor controllers in a sub panel that have different power requirements on each phase due to motor ratings so the same could happen here if neutral lost .
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
That's a good point Michael. Thanks for the info and thanks for watching. Dave.
@tomm856
@tomm856 Жыл бұрын
Only seen it once at a public swimming baths where there was a underground cable neutral failure many years ago. Lights glowing very bright and poping and a washing machine motor speed fluctuating wildly
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Fantastic information. Really useful for our viewers to know. Appreciated and thanks. Dave.
@CreepyCrawly-xy1iw
@CreepyCrawly-xy1iw 7 ай бұрын
Perfectly explained. Good job.
@learnelectrics4402
@learnelectrics4402 5 ай бұрын
Glad it was helpful, appreciated.
@user-qi8tv2sj4m
@user-qi8tv2sj4m Жыл бұрын
Very very good. It has answered a lot of questions
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Glad it helped, thanks for watching.
@shiamjad
@shiamjad Жыл бұрын
Another great informative video, please upload more 3 phase videos
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
More three phase! I'll put it on the list. Dave.
@aranfairozi1331
@aranfairozi1331 Жыл бұрын
Love ur channel well done mate
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Much appreciated, thanks for watching.
@Seve-id8jp
@Seve-id8jp Жыл бұрын
Really helpful and well explained. Thanks for sharing.
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Glad it was helpful, thank you.
@Dog-whisperer7494
@Dog-whisperer7494 Жыл бұрын
I found this very interesting, but it brings up a question? If the loss of a neutral on a three phase supply and is dangerous to the end user as well as damaging equipment, then why are new builds starting to have three phase supply’s as standard.? Surely this will put home owners at a higher risk of fire and injury or death. Great video as always 👍
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Now that is an interesting question. Thanks for raising the subject. Dave.
@30mAkills
@30mAkills Жыл бұрын
Here in India we have 3 and 1/2 core service cables. 1/2 core is the neutral. Means neural size will be half that of phases. This is a cost cutting strategy. Electrically this is ok, but lacks mechanical strength.
@TheYohtube
@TheYohtube Жыл бұрын
Thanks Dave another interesting video in your usual straightforward style.
@elc-miscellanea
@elc-miscellanea Жыл бұрын
Dave, thanks for the insightful video. I have a question about the diagram at 07:37. What happens if N is connected to the local earth system (with an Earth Resistance below 4 ohms) and then downstream separated into N and PE at the distribution board level? This approach is quite common where I'm from. Does this practice mitigate overvoltage issues or exacerbate the risks in case of losing N upstream?
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
I've deliberately left earth of the drawings. In the UK we separate the earth and neutral at the intake position and do not run earth and neutral together in the installation. Without seeing how your wiring systems work, its difficult to say. Hope this helps.
@elc-miscellanea
@elc-miscellanea Жыл бұрын
@@learnelectrics4402 Dave, thank you for your response. It's interesting to learn about the UK's approach to separating earth and neutral at the intake position. In my country, we typically have (in aerial power line): L1, L2, L3, and PEN - that has the combined function of providing the neutral and protective earth. PEN is grounded at the intake position and at each 2 consecutive poles. At the customer's first distribution board, PEN is joined with the local earth system provided by the custemer (having no more than 4ohms) and then separated into PE and N.
@lllCANDYMAANlll
@lllCANDYMAANlll Жыл бұрын
Great explanation, this was made easy to understand.
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Thank you, and thanks for the feedback.
@johnkiran3306
@johnkiran3306 7 ай бұрын
Hi, You have given a case. A 3 phase transformer present which drives 8 houses. Each phase has a fuse before reaching the house, inside house thorough MCBs home appliances are connected. Few appliances are running in few houses. Suddenly a bird hit one of the phase of transformer and it's link blown. In house 3, AC got blown which in running state. House 4 - 3 fans blown 2 running state 1 off state. Seen that neutral wires are blown and inside windings are blown. 1. Why not all devices blown in other houses? 2. in house 4, why all devices not impacted? 3. How does the devices affected which are in off state also ? 4. Good to hear the detailed analysis report explaining the cause and internal behaviour. 5. Tell the exact precautions which are needed to handle such situations in future. 6. How can we test the neutral and earthing fine at transformer and at home
@learnelectrics4402
@learnelectrics4402 7 ай бұрын
This is why we install protective devices, to limit the damage and impact on other devices. Have a look at this video on fuses. kzbin.info/www/bejne/h6a3lIuIo9qarLM
@30mAkills
@30mAkills Жыл бұрын
We call this phenomenon as Floating Neutral. India.
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Yes, that's another useful expression for it. Its a long time since I worked in India, Thanks for contributing. Dave.
@davefuntilon5591
@davefuntilon5591 11 ай бұрын
😊
@michaelsimpson6603
@michaelsimpson6603 Жыл бұрын
Great information, excellent.
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Thank you. and thanks for watching.
@markobosnjak810
@markobosnjak810 8 ай бұрын
I , unfortunately, learned it the hard way. Thank you for your lessons sir!
@learnelectrics4402
@learnelectrics4402 8 ай бұрын
Sorry to hear that, put it down as a training session. Thanks for watching. Dave.
@tadesselijalemmekonnem3855
@tadesselijalemmekonnem3855 6 ай бұрын
Very smart explanation,this is the types of fault I experienced
@learnelectrics4402
@learnelectrics4402 5 ай бұрын
Glad it helped. Dave.
@raimondtracar8703
@raimondtracar8703 Жыл бұрын
Something similar happened to me when I connected earth together with neutral, instead to the grounding pole clamp. Had to change the old three fase cable with just a neutral going in to the house, to a new one with added earthing. The main distribution board was outside, on the electric pole, the box was old and a seperate clamp to the ground was missing, so I connected earth to neutral. 2 mysterious weaks of dropping/jumping voltage and some damaged equipment. Thankfully the house didn't burn down and most of the equipment was repaired.
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Lucky, glad you got it sorted. Thanks for the info, and thanks for watching. Dave.
@hvacrwrld1402
@hvacrwrld1402 Жыл бұрын
Thanks, always explained well.
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
You are welcome, appreciate your feedback.
@johng.1703
@johng.1703 Ай бұрын
when you lose the neutral on the supply side you lose the set neutral point so you have a floating neutral, the neutral is normally a centre tap voltage divider with reference to ground, when you lose that you have multiple properties connected to that same neutral and one or more of those properties will also have a connection to another phase, so instead of having a clamped 240v supply you have a floating voltage divider based on resistance that is split between L1 and L2, the lower resistance property gets the higher voltage. the voltage will very with the load on each line, the resistance on each line is the load on each line, the higher the resistance the lower the voltage on that line, the lower the resistance (lower the load is) the higher the voltage is.
@learnelectrics4402
@learnelectrics4402 Ай бұрын
Brilliant contribution, thanks. Dave
@tresslerj1985
@tresslerj1985 2 ай бұрын
Your videos are amazing, also 100.
@learnelectrics4402
@learnelectrics4402 2 ай бұрын
Glad you like them, thank you.
@DH-tv2yw
@DH-tv2yw 9 ай бұрын
Would an AFDD provide protection against this fault as they have overvoltage protection? Thinking more in a single phase residential setting where the neutral fault is more likely to be with the DNO?
@learnelectrics4402
@learnelectrics4402 9 ай бұрын
In my opinion, no. Not unless you have loose connections and arcing. With single phase, things will just stop. hope this helps. Dave.
@DH-tv2yw
@DH-tv2yw 9 ай бұрын
Many thanks Dave
@TitchgamerRG
@TitchgamerRG Жыл бұрын
Great vid as always Dave! Thankfully never come across this personally. Did discover a over voltage on a certain warehouse once where for some reason the Transformer started out putting 300v per phase though. Amazingly only killed a few PCs.
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Thanks for the feedback Andy. Yes, it doesn't take much to knock a PC over. Catch you soon.
@markwienands
@markwienands Жыл бұрын
Is there an Over Voltage Protection device at the Mains Distrtbution Board? What are they generally called?
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
There will always be an over-current device and sometimes a surge protection device (SPD) too. Take a look at thois video on SPDs, hopefully it helps. kzbin.info/www/bejne/eXS9e2N5hbSFaLc
@b787900
@b787900 Жыл бұрын
Thank you for the lesson. I have a question. My house is 3 phase but can be changed to single phase with change over switches, this is because of unstable electricity. Last night after a blackout the incoming voltage was 360v. I thought it was because the neutral was lost. I then changed everything over single phase (all load on 1 line and the “lost” neutral. The voltage went to 200v. Why is it that if the neutral was lost did the single phase work, did the 1 used phase use the other 2 non used phases as a neutral?
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Without actually seeing this type of problem as it happens, its difficult to say. But thanks for watching and I hope all is ok now, Dave.
@b787900
@b787900 Жыл бұрын
​@@learnelectrics4402not sure as an electrical engineer you actually want to see the wiring in the house. Phases are changed over by wall sockets where all pins are live. You have a total of 9 sockets 3 phases with 3 lines per phase and a neutral line. Africa is scary
@AndrewBaker-z9r
@AndrewBaker-z9r Жыл бұрын
Great video, always the best, thanks mate
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Thanks for watching. Lots more to come. Dave.
@danielteyehuago1633
@danielteyehuago1633 Жыл бұрын
Thanks for sharing it with us
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
My pleasure Daniel. Thank you.
@ditlofj3280
@ditlofj3280 Жыл бұрын
Great explanation
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Glad it was helpful and thanks for watching.
@Roq-stone
@Roq-stone Жыл бұрын
Again, well done.
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Thank you, appreciated comments and thanks for watching. Dave.
@saleemqazi8921
@saleemqazi8921 9 ай бұрын
If the natural is disconnected, will the circuit breaker in the distribution board activate and save the electrical appliances ?
@learnelectrics4402
@learnelectrics4402 9 ай бұрын
The circuit just will not work. No current flow. The breaker will not operate unless there is a significant earth fault.
@pauldow1648
@pauldow1648 4 ай бұрын
Recently I had 240 v neutral failure probably due to tree branch on service pole . Voltages were not correct at panel. Lights dimmed, some lights blew, some lights when turned on turned other lights on. The Aluminum frame of our screened porch carried, variously, 40 to 70 volts. I think our bonded fuse box sent voltages to the screen porch ground, causing my dog to yip when she brushed against the aluminum doorway. Best advice if lights (power voltages) act crazy.... Cut power and call power company to repair. An electrician does not work on power company side of meter.
@learnelectrics4402
@learnelectrics4402 4 ай бұрын
Great contribution, thanks for watching, Very similar to my Mother's brush with a storm. Dave.
@karamathussain3488
@karamathussain3488 Жыл бұрын
Thank you for the information very helpful indeed. Please continue doing a great job. Karamat
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Thank you Karamat, I will. Thanks for watching.
@anthonyfindlay466
@anthonyfindlay466 Жыл бұрын
Well done, Dave anther well explained and important topic your effort and time most appreciated thank you.
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Much appreciated feedback Anthony, and thanks for watching. Dave.
@mohammadshirifeshki4018
@mohammadshirifeshki4018 Жыл бұрын
Thank you Dave.
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
My pleasure, hope you enjoyed it.
@uaungmyint6387
@uaungmyint6387 9 ай бұрын
Very Good
@learnelectrics4402
@learnelectrics4402 9 ай бұрын
Thanks. Appreciated comments.
@AvoElectrical
@AvoElectrical 10 ай бұрын
exceptional
@learnelectrics4402
@learnelectrics4402 9 ай бұрын
Great feedback. Thank you. Dave.
@uaungmyint6387
@uaungmyint6387 9 ай бұрын
How to calculate unbalance voltage for 3 phase each phase when lose neutral at unbalance load. Because that problem some time happen for people used over head 3 phase 4 wire power line.
@learnelectrics4402
@learnelectrics4402 8 ай бұрын
As the video shows, the voltages can vary quite a lot. It depends just how unbalanced it is, what else is on the circuit etc. Thanks for watching. Dave.
@30mAkills
@30mAkills Жыл бұрын
Useful
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Glad you think so and thanks for watching.
@JamesgeraldWard
@JamesgeraldWard 3 ай бұрын
Brilliant
@learnelectrics4402
@learnelectrics4402 3 ай бұрын
Thank you, much appreciated.
@michaelheraghty9321
@michaelheraghty9321 7 ай бұрын
top job
@learnelectrics4402
@learnelectrics4402 4 ай бұрын
Thank you, appreciated.
@vioreltanasa988
@vioreltanasa988 Жыл бұрын
When we disconect a thre fase circuit first disonect the fases after neutral when we conect we connect first neutral
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Always make sure that you have safely isolated the circuits. Thanks for the input, and thanks for watching. Dave.
@stanleytaylor6484
@stanleytaylor6484 8 ай бұрын
Overvoltage due to a lost neutral is bad news for any equipment. There is more bad news: if the voltage supplied is 230 V rms, then the voltage amplitude swings between -1.41*230=-325 V and +325V, which results in a (momentary) voltage of close to 600V.
@learnelectrics4402
@learnelectrics4402 8 ай бұрын
Thanks for the comments. Dave.
@brianhewitt8618
@brianhewitt8618 Жыл бұрын
👌👍
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
As always, thank you Brian. Your support is very welcome. Dave.
@ELECTRICLIFE4U
@ELECTRICLIFE4U Жыл бұрын
❤👍👍👍👍👍👍
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Great feedback, appreciated. Dave.
@nittaberi
@nittaberi Жыл бұрын
Not so important, but no "Kirchoff", correctly it's Kirchhoff. Thanks the video! ✌️😉
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
It is, thanks for putting me right. You guys never let me get away with anything! Your feedback appreciated, thanks. Dave.
@okaro6595
@okaro6595 11 ай бұрын
The electric company covered it? Here they would not, it would be up to your own insurance to cover it.
@learnelectrics4402
@learnelectrics4402 11 ай бұрын
They did in my mother's case, and all her neighbours. Thanks for watching.
@learnelectrics4402
@learnelectrics4402 11 ай бұрын
They did in my mother;s case. And all her neighbours.
黑天使只对C罗有感觉#short #angel #clown
00:39
Super Beauty team
Рет қаралды 36 МЛН
小丑教训坏蛋 #小丑 #天使 #shorts
00:49
好人小丑
Рет қаралды 54 МЛН
BAYGUYSTAN | 1 СЕРИЯ | bayGUYS
36:55
bayGUYS
Рет қаралды 1,9 МЛН
We Attempted The Impossible 😱
00:54
Topper Guild
Рет қаралды 56 МЛН
What is a Lost Neutral? Lost Neutrals demonstrated
12:21
Morgan Inspection Services
Рет қаралды 111 М.
Three Phase Mystery Solved, No Neutral Required in a Balanced Load?
13:33
Joe Robinson Training
Рет қаралды 121 М.
Single Phase vs. Three Phase: Simplifying Electrical Power!
3:02
The Neutral Conductor and What Happens When it Breaks
6:25
Zack Hartle
Рет қаралды 23 М.
TT SYSTEMS - WHY MUST THEY BE RCD PROTECTED
17:09
LEARN ELECTRICS
Рет қаралды 38 М.
Overcurrent, Overload, Short Circuit, and Ground Fault
6:54
Dave Gordon
Рет қаралды 936 М.
What Will Happen if Transformer Neutral Supply Brake @TheElectricalGuy
7:19
黑天使只对C罗有感觉#short #angel #clown
00:39
Super Beauty team
Рет қаралды 36 МЛН