Hi, Thank you for your nice lectures ... To enhance this lecture technically more correct, we can go by taking industrial powersystem as an example (where it ll be YNd1/11 - step down trafo ... and Delta side will be grounded via grounding trafo... ) and to add one more point, Generating stations usually have YNd1/11 (step up trafos) :)
@cricketinformationcapsule4 жыл бұрын
Superb sir
@paulthompson58562 жыл бұрын
Good video. We have an 11kV earthing transformer with an earthed star connected primary winding and a secondary winding with a broken delta connection with a resistor that limits the primary winding current to 60A. How do you determine/model the zero sequence impedance of a broken delta connected transformer. thanks
@MANOJKUMAR-mb2uw4 жыл бұрын
Sir what happens if there is no path for circulating currents.
@gonencakcam43354 жыл бұрын
Hi, thanks for these kind of videos. 1- How can we calculate zero sequence impedance of zig-zag transformer ? As you mentioned, during phase to ground fault, only impedance that effect to our ground fault short circuit current is zero sequence of zig-zag transformer. Also other component will be effect on the path of that faulty line. System Voltage (L-L)=10,5Kv Irated/phase=100A Short Circuit current in neutral=1000A, 10sec Ohm/per phase = 18,2 ohm/phase 2- On ETAP program, below informations are needed. But I could not understand these value is ohm or pu values of zero sequence. Even I am not sure these values zero or not ? If I put ohm/per phase values, ground fault is going to limit from 15kA to 2kA. I do not know how it calculate ? Do you have any advice ? Impedance; Ohm= ..... --> Etap Help page said that ''Enter grounding resistor or reactor in ohms'' X/R= ...... --> Etap Help page said that ''Enter the grounding transformer X/R ratio''
@gonencakcam43354 жыл бұрын
Lectures in Electrical Engineering Let me ask different way. How can we calculate zero sequence impedance of zigzag grounding transformer ?
@mallikarjunayh63453 жыл бұрын
Hi Sir, its a very informative lecture. I have a question, can we convert IT Earthing network to TN using Zigzag transformer at LV side (415V), but we cant use Earthing resistor in neutral of Zigzag transformer. Is it possible?
@sanjibkumardas65214 жыл бұрын
Thanks a lot sir for the sequence diagram for earthing transformer..these kind of informative videos helps a lot in our work field....sir i have 1 more request..can u provide sequence diagram of autostransformer having delta as tertiary stabilising winding(YNyn0d11 as well as Yy0d11)?
@biswaljayanti6654 жыл бұрын
Sir can u provide a sequence network of 3 phase transformer consists of HV star,intermediate volatage star and lv voltage delta for example 220/132/33 KV transformer