LIGHTING CIRCUIT FAULTS FOR ELECTRICAL ASSESSMENTS and FAULT FINDING

  Рет қаралды 17,053

LEARN ELECTRICS

LEARN ELECTRICS

Күн бұрын

Пікірлер: 66
@danielteyehuago1633
@danielteyehuago1633 2 жыл бұрын
Watched it thrice for a deeper understanding... Asking questions takes you directly to problem easily...
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
That's the way Daniel. Thanks for the comments. Dave.
@Anonviewer97
@Anonviewer97 Жыл бұрын
3rd year apprentice here, very helpful video, I wish this was explained to me in this way when I first started as this would have been a catalyst to my learning. Thank you.
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Glad you've found the channel now. Spread the word and help others and thanks for the great feedback. Dave.
@jmohammad3762
@jmohammad3762 2 жыл бұрын
Absolutely brilliant video typical and common faults which you will find on a daily basis when being called out to fault finding on luminare circuits. Nicely explained and very methodical method which I follow. Thanks Dave keep these great video's coming much appreciated and wanted.
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
Absolutely we will, lots more to come, thanks for watching. Dave.
@BasebossSports
@BasebossSports 7 ай бұрын
Amazing video honestly. Clear and simple to understand. Thank you for this video. It has helped me loads!
@learnelectrics4402
@learnelectrics4402 5 ай бұрын
Glad it helped. thank you.
@danielteyehuago1633
@danielteyehuago1633 2 жыл бұрын
Wow! This is very informative, thanks for sharing it with us Dave. It worth it and the best tutorial on the topic for me.
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
You're very welcome Daniel. Lots more videos on lighting being made. Keep watching.
@NurCanastel
@NurCanastel Жыл бұрын
Thanks for your help very well explained best tutor thanks
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Thanks for watching, appreciated.
@maxwellmc9734
@maxwellmc9734 Жыл бұрын
Excellent 👌
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Thank you. Lots more to come.
@EdwardBretherton
@EdwardBretherton Жыл бұрын
awesome videos Dave, they all help fill up the knowledge, how about a video or two on prep for lvl3 exams on all subjects
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Its now on the list Edward. Thanks for watching and commenting, appreciated. Dave.
@AngelaPeters-fy1tc
@AngelaPeters-fy1tc Жыл бұрын
Hi Robert here not Angela lol, another excellent video especially the large easy to follow diagrams. One thing though am i correct in saying that on a1 way light switch the brown live wire on the switch cable terminates in the common but on a 2 way or 3 way lighting configuration that same brown wire terminates in L1 and the black strapper cable from the 3 core goes into the common and also either gets carried on through to the common on the either 2nd or 3rd switch depending on the set up. Its remembering this which is tricky i guess it comes with practise thankyou so much your videos are a godsend they really are.
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Yes Robert, it comes with practice. If you put the Line into common on the 2 way circuits, it would not work as required. Thanks for watching, Dave.
@markr452
@markr452 2 жыл бұрын
Awesome 👌
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
Looking forward to a decent pint of ale.
@three-phase562
@three-phase562 2 жыл бұрын
Very good video, well thought out scenarios thoroughly explained by the graphics in an easy to follow manner.
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
Glad you liked it, appreciated. Thanks. Dave.
@MMG_MoonManGuitar
@MMG_MoonManGuitar 2 жыл бұрын
Another great video. Always good for refresher training. Thank you as usual mate.
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
My pleasure, thanks for watching. Dave.
@ahmadtareqslamzadeh4656
@ahmadtareqslamzadeh4656 2 жыл бұрын
Thanks again for your very helpful video.
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
Glad it was helpful and thanks for watching.
@seandempsey7351
@seandempsey7351 2 жыл бұрын
Fantastic video Dave as always 👍 I have come across most of these faults at some point in my career. Mostly as a result of DIY . I don’t see them at all these days. Maybe that’s a sign the DIYers are leaving the electrics alone and sticking to putting shelves up . Thank you you reminding me with another good brain work out.👍👍❤️
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
Thanks Sean, great support, really appreciated. Dave.
@philrichmond7567
@philrichmond7567 2 жыл бұрын
Thank you for sharing. 👍🏼
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
My pleasure and thanks for the support.
@mohammadshirifeshki4018
@mohammadshirifeshki4018 Жыл бұрын
Thank you Dave. I have got a question about insulation resistance test on lighting circuit. When there is so many spotlight oncircuit, some electricians do the test bu 250 rather than disconnecting all light and doing 500v test. Some connecting line and neutral and just doing test between them and earth. Is it right way? Does it comply with regulation? Sorry if you find it irrelevant question.
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Mohammad, take a look at this video, some testing methods changed with Amendment 2 and this video will explain. AMENDMENT 2 - 18th EDITION - INSULATION RESISTANCE TESTING - CHANGES - click on the link kzbin.info/www/bejne/gZ3cXqRjebibrqM
@krazylad84
@krazylad84 2 жыл бұрын
Thanks Dave.
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
My pleasure my friend. Thanks for the support.
@Dibbo1979
@Dibbo1979 2 жыл бұрын
Great video👍🏻
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
Glad you enjoyed it Mr Dibbo. Thanks for the support. Dave.
@BelajarBaik855
@BelajarBaik855 2 жыл бұрын
It's a very interesting review.☺☺☺
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
Glad you think so, thank you. Dave.
@chalakfaris7437
@chalakfaris7437 2 жыл бұрын
can you make a video about testing motor in circuit
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
Good idea Chalak. We have videos on connecting motors so Testing is the next logical video. Thanks for the request. Dave.
@davidpatterson1574
@davidpatterson1574 2 жыл бұрын
Thanks Dave
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
You're welcome David. Thanks for the support. Dave.
@michaelrichard4162
@michaelrichard4162 2 ай бұрын
How would you fault find the neutral cable in the wring rcd fault
@learnelectrics4402
@learnelectrics4402 Ай бұрын
Under no load the RCD will not trip. As soon as you put any load, even a tiny light bulb, onto that circuit, the RCD will trip, possibly both RCDs in a dual system. Dave.
@KM-zm2iy
@KM-zm2iy 2 жыл бұрын
Thank you Dave for the detailed explanation. If possible, I can communicate with you to discuss some questions related to street lighting circuits, as I have been working in this field for a long time and I face some technical problems due to the inability to understand how to choose the appropriate method to protect these circuits and people from electrical hazards. One of the problems is, if the luminaires are LED type and feed by a 3phase (4by16mm2) cable system. Is it ok or not to use the armor of the (4by16mm2) cable as a cpc instead of a copper cpc to reduce the cost of materials?. The second question: is it a must to use an RCD in addition to the circuit breaker in these circuits?
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
Steel armouring has only about 12% electrical conductivity of copper. Generally, it is accepted that the armouring of a cable has an equivelant conductivity of the copper cores. So, 16mm cores, the armour is equivelant to 16mm copper. If you need a bigger size earth you will need to run a separate cable. If the regulations for street lighting say use an RCD then you should be using an RCD + MCB or RCBO. If something goes wrong and people are injured, you will have to explain why you did what you did. Thanks for watching.
@KM-zm2iy
@KM-zm2iy 2 жыл бұрын
@@learnelectrics4402 thanks a lot for the reply
@MS-Patriot2
@MS-Patriot2 2 жыл бұрын
I have found the trapped insulation problem and loose terminals within pre wired connector blocks on outdoor lighting accessories from the well known DIY suppliers. Check all screw connections, saves getting the ladder out twice!
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
Spot on advice there Mike. Check connections before mounting at height. Thanks. Dave.
@no_short_circuit
@no_short_circuit 2 жыл бұрын
Thanks again for the video. I may be wrong here, but at 3.09 you say "the current flows through the switch to the common terminal and up to the switch block". Your diagram shows the switching line coming from L2 to the switch block?
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
As long as it returns to the switch block, that is the main point. On one way lighting as long as one or the other is in common it will work. Dave.
@markdilley3918
@markdilley3918 6 ай бұрын
Odd one here, 3 core and earth on bathroom fan. After fan isolator, switched live only giving 130v, perm live happily giving 230v. Any ideas? Neutral fault???
@learnelectrics4402
@learnelectrics4402 5 ай бұрын
Remove the wiring from the fan (after drawing how it is wired) and check each conductor. If your earth is good, then a voltage check earth to each wire should show either zero volts or 230 volts ish. Flick the switch and see what voltages change.
@keirdavies
@keirdavies 2 жыл бұрын
My bedroom light randomly cuts out. I've had a sparky look at it and we've changed the pendant and switch, but couldn't find anything wrong and it is still happening and thoughts?
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
Check all the lighting circuit and the lamp. Process of elimination.
@BAYUMBE
@BAYUMBE 2 жыл бұрын
Hi, dave. During a consumer unit change and when doing a live test, I found out that the earth was live. I could test 14V coming from the earth but the RCBO did not trip. What can be the cause?
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
RCBOs work on current not voltage. Make sure all your earth connections are as they should be, this sometimes happens on some earthing systems.
@gordonr6532
@gordonr6532 2 жыл бұрын
I would like to understand how testing is completed after flood damage if the consumer unit is unaffected please.
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
We would test the same as any other testing. The priority is to get the circuits dry and replace any wiring as required. Hope this helps. Dave.
@zippymo672
@zippymo672 Жыл бұрын
I did a lighting circuit fault find 2 weeks ago. Customer complained of a burning smell and coming after he switched on the lights and then the lights tripping. After a few investigation we lifted up a floorboard to get acces to a joint which I couldn't get to from the light fitting, and saw a huge rat had clamped onto the switch wire. The burning smell was the rat cooking when the current was flowing through him. There were also live maggots eating him out 🤢🤢🤢🤢.
@learnelectrics4402
@learnelectrics4402 Жыл бұрын
Yep, it happens more than we realise. Not a nice job but its got to be done. Dave.
@highgatehandyman6479
@highgatehandyman6479 2 жыл бұрын
Can someone please fo a video regarding the blue wire. The fact that its earthed at points along points back to the power station. And that ac curent moves down the blue wite but doesnt short to earth?? Nor do the earthed parts of the installation become energized yet are connected to earth and thus to neutral and ac current flows 'back' up the wire on the negative peak of the sin wave?? Please coz its not looking safe on paper or logical to connect earth to neutral
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
Neutral and earth are physically bolted together back at the substation so the same electrical potential. There is (about) zero volts difference between them. But yes, maybe a video could be done.
@highgatehandyman6479
@highgatehandyman6479 2 жыл бұрын
@@learnelectrics4402 please do, no one has adressed this phenomenon. If the current changes direction ( alternating current) then at least 50 times a second the blue wire should behave excactly as the brown wire does. And thus energize all earth bonding if the flow is coming in from both live conductors . Why is the electrical pressure only registered on one wire if they 'alternate'??? Need to know. And thank you for sharing your knowledge in the community.
@eprohoda
@eprohoda 2 жыл бұрын
how is it going?,omg~ tota well edition, catch you later~ ))
@learnelectrics4402
@learnelectrics4402 2 жыл бұрын
Thanks for watching.
Une nouvelle voiture pour Noël 🥹
00:28
Nicocapone
Рет қаралды 9 МЛН
Tuna 🍣 ​⁠@patrickzeinali ​⁠@ChefRush
00:48
albert_cancook
Рет қаралды 148 МЛН
FAULT FINDING - RING CIRCUITS
15:38
LEARN ELECTRICS
Рет қаралды 44 М.
Nearly KILLED by a CRAZY fault! What on earth is going on? 💀
27:12
Artisan Electrics
Рет қаралды 804 М.
What is the Difference Between a Short Circuit and a Ground Fault?
16:18
Why I Hate Emergency Fault Finding Jobs - Electrician Life
22:12
Artisan Electrics
Рет қаралды 196 М.
Fault Finding Electrical Circuits - Electrician Life
24:57
Artisan Electrics
Рет қаралды 401 М.
Lighting Circuits Part 1
24:18
John Ward (jwflame)
Рет қаралды 1,5 МЛН
Verify R1 + R2 testing of a radial lighting circuit - covers fault finding and write-up. Part 1 of 3
19:03
Pure Electrical Training - by Adrian Davey
Рет қаралды 4,7 М.
Fault Finding - You Will Never Guess What It Was...
13:46
Artisan Electrics
Рет қаралды 156 М.
The Mysteries of AM2 and AM2S - End Point Assessment
55:23
Borrowed Neutrals & Old Lighting Circuits
11:02
John Ward (jwflame)
Рет қаралды 107 М.