IMPROVE "F3" ERROR AC SPLIT DAIKIN INVERTER 1 PK

  Рет қаралды 62,717

Made Arsa

Made Arsa

5 жыл бұрын

"F3" error on split ac with an inverter due to the error of the exhaust pipe temperature in the outdoor. (outdoor thermistor sensor) there are 3 types of discharge pipe sensor, reverse pipe sensor, outdoor temperature sensor, of the three types of sensors that read the outdoor working temperature and provide a signal to the inverter module.
"F3" error can be caused by lack of freon, outdoor thermistor sensor is damaged / misread temperature, electronic expansion valve is broken, body valve expansion is broken, pcb inverter module is error / damaged.
Here I use a capillary pipe to replace the damaged valve expansion. Sy, don't recommend friends to replace it with capillary pipes, but so far there are no problems for its use, the AC still wants to cool at low, med, high comp speed.
Hopefully this will be useful for all my friends and if there are feedback or comments please write below the comments column.
Don't forget to like and subscribe, friends - thanks.

Пікірлер: 303
@bahribahri228
@bahribahri228 3 жыл бұрын
Trimakasih mas bagi bagi ilmu TUHAN BERKATI AMIN
@berbagitau1019
@berbagitau1019 7 ай бұрын
Ilmu yg bermanfaat..semoga tmbh mju dah berkembang
@bahribahri228
@bahribahri228 2 жыл бұрын
Trimakasih mas bagi bagi ilmu saya trimasih banyak
@iyanservice0556
@iyanservice0556 5 жыл бұрын
Okee mass terimasih atass videonya,, saya bertahun2 benam AC daikin inverter.. Kedip2 jg luar dlm,, saya bongkar2 vcb nya.. Gak jg
@aripazu3716
@aripazu3716 4 жыл бұрын
Coba mas kabel2 kontrolnya mungkin ada yg gak kenceng, sy jg ngalamin pusing n ribet.
@alphaservice191
@alphaservice191 2 жыл бұрын
Mantab kang,salam dingin dari indarung padang,terimakasih
@fajarnugroho646
@fajarnugroho646 5 жыл бұрын
Salam dari bali...ikut belajar bli
@ahmadjamil8818
@ahmadjamil8818 2 ай бұрын
Wah ini mah teknisi ac yg udah pro..ngerti cara kerja komponen ac..
@jovanoriechie8129
@jovanoriechie8129 3 жыл бұрын
Bli sy subcribe.., semoga sewaktu2 bisa share ilmu utk problem yg belum pernah sy atasi. Thxs
@jovanoriechie8129
@jovanoriechie8129 3 жыл бұрын
Bli., boleh minta kontak WA untuk tanya2 soal AC. Terima kasih
@irilhandoko1856
@irilhandoko1856 4 жыл бұрын
Mantab made .......
@kikikiki3941
@kikikiki3941 3 жыл бұрын
Trimakasih 👍👍
@sugiyono0661
@sugiyono0661 5 жыл бұрын
Ok makasih
@sugengsugeng9471
@sugengsugeng9471 4 жыл бұрын
mantab nas,nambah wawasan
@madearsa93
@madearsa93 4 жыл бұрын
Terimakasi mas sugeng
@imanueljulian6495
@imanueljulian6495 4 жыл бұрын
Made arsa..mau tanya, itu tadi motorized coil nya tidak dipasang ? Ndak pengaruh pada pcb outdoor..terimakasih
@bahribahri228
@bahribahri228 3 жыл бұрын
Trimakasih mas nambah sy ilmu sekali lagi trimakasih
@azenkmaulana2229
@azenkmaulana2229 5 жыл бұрын
Tquuuuu.. Brother !
@ariefyenny9959
@ariefyenny9959 3 жыл бұрын
Ok. Baik
@hlathein5558
@hlathein5558 4 жыл бұрын
Thank you sir
@madearsa93
@madearsa93 4 жыл бұрын
You are welcome
@mrdiycool2062
@mrdiycool2062 4 жыл бұрын
Udah subcribe mas
@torjackkaratan6081
@torjackkaratan6081 3 жыл бұрын
After your modification sir.. In several week or months no have problem afyer you change expansion valve to capillary? Tnx for your response..
@oscarrj.mataniari1658
@oscarrj.mataniari1658 4 жыл бұрын
Bli... mau tanya donk..sy lg service ac.. Metk LG, inverter 1 PK.. problennya, saat dinyalakan pertama, putaran compressor low ( 2,4 amper..sesudah 2 menit hidup, puteran compressor naik dan ampelr menjadi 3.4 amper..sesudah 2 menit kwmudian, puteran naik lagi jadi 5-6 amper..hampir 3x yg teryera di nameplate (name plate 3.3 amp).. apa penyebabnya bli..trimkasih.salam dingin dari tangerang
@vivo1269
@vivo1269 2 жыл бұрын
Bos Sayaa Mau Tanya daikin split duct 2.5 Pk..Fan outdooor nyala tapi compresskr Ga manggil..walaau indoor nyalaah.di cek remot kode error ga terdetek
@bobx1473
@bobx1473 4 жыл бұрын
👍 grande
@nazacom2152
@nazacom2152 3 ай бұрын
Thnkyu sob... itu Ac brp PK ya, dan brp panjang kapiler nya..? 🙏👍
@joeteknik4556
@joeteknik4556 2 жыл бұрын
Udah nyoba ini kelemahannya ko multi split, ga bisa 1 indoor aja yg menyala, harus 2 2 nya menyala karena freon mengalir ke indoor yg lainya jg.
@alfakrisbiantoro6718
@alfakrisbiantoro6718 3 жыл бұрын
Untuk info harganya bang . . .share dong harganya . . Dapet kasus sama untuk daikin inverter 1 pk model lama
@masukgenk3903
@masukgenk3903 3 жыл бұрын
Bli, Sepertinya kasusnya mirip dgn ac saya, Indoor tidak mau dingin, ketika baru ON, lalu outdoornya harus di semprot air dulu baru mau dingin indoornya, Apakah kasus demikian masalahnya di katup expansi jg? Kode error di remot ac tidak terdeteksi
@yulisudarwanto7341
@yulisudarwanto7341 5 жыл бұрын
@made arsa ada nomer g bisa di hibungi mas.mau tanya ilmu nya dan sedikit curhat tentang permalahan ac inverter 1 pk.saya baru belajar dari 0
@otangsetiawan5780
@otangsetiawan5780 8 ай бұрын
bang kalo sudah ganti ke kapiler apakah future Low watt nya masih bisa berfungsi atau gk?
@ediprayitno6946
@ediprayitno6946 2 жыл бұрын
Minta skema expasi valvenya om 6 kabel mana yg negati dan positifnya
@adicahyadi5803
@adicahyadi5803 2 жыл бұрын
Metaken pak de..kenapa tdk d vacum ya? R32 kan wajib vcum..apalagi itu invrter. Kmudian apa pipa kapiler bisa mengatur volume gas spt elektronik expnsi valp? Apa masih bisa hemat listrik klo sudah di modif spt nike?ampure masih belajar pak made.. 🙏
@madearsa93
@madearsa93 2 жыл бұрын
Divacum lebih baiknya...! Daya listrik masih hemat seperti biasa hanya saja jika seting low watt di remote dingin nya agak kurang sedikit seperti biasanya.
@andyziian5767
@andyziian5767 3 жыл бұрын
Colek.. suhu made Dulu...
@sarudiandika7567
@sarudiandika7567 4 жыл бұрын
Sahabat thenik info . AC emperter Daikin 1 pk Tdk eror .. Permasalahannya Compresor .hidup dlm watu pling lama 5 menit ..setelah dlm 5 MIT mati lgi tu compresor .nunggu smpi 20 mnt .baru bisa hidup .treus mati lgi ....aph tu kerusakannxa
@madearsa93
@madearsa93 4 жыл бұрын
Blum bisa di simpulkan apa kerusakannya, karena kurang detail pengecekan posisi outdoor ac hidup ampere berapa? Tekanan freon berapa? Sudah dpt cleaning ac indoor dan outdoor? Ada indikasi kode errornya apa? Trims
@filzafarzana2166
@filzafarzana2166 3 жыл бұрын
@@madearsa93 lo ac 1 1/5 ukran kapiler brp kh
@rendi.m.u1968
@rendi.m.u1968 4 жыл бұрын
AC inverter lebih ribet perbaikinya. Kalau bisa di ganti aja mas jangan di rubah rubah gitu GK baik.🙏😁
@Anadisty
@Anadisty 2 жыл бұрын
Kalo punya uang banyak gpp bang main ganti" aja tapi kalo masih bisa diakalin dengan nominal yg kecil kn gak salah juga
@iqbalagustina8440
@iqbalagustina8440 4 жыл бұрын
Kalo untuk ac 1.stngah pk pake pipa kapiler ukuran berapa
@ahmadaircon7818
@ahmadaircon7818 3 жыл бұрын
Bagaimana bisa tentu kan mana satu yg rosak..? Sensor? Eev atau pcb
@ubn4046
@ubn4046 3 жыл бұрын
Cara kerja anda sudah saya kerjakan ac suda ok tapi aneh nya setelah 3 hari ac daikin inverter 1pk kumat lagi yaitu out door mati lagi freon r.410a nya kondisi ok ga bocor.
@madearsa93
@madearsa93 3 жыл бұрын
Error f3 adalah kesalahan kontrol suhu deteksi pd thermistor pipa discharge. Bnyk faktor yg menyebabkan error f3 , bisa karena 3 sensor thermistor pd outdoor yg rusak, kebocoran freon, bisa juga pcb outdoor itu yg rusak. Perlu menganalisa kerusakan pd error f3 tidak semua kerusakan pd body expansi dan eletronic expansinya yg sudah di rubah dgn pipa kapiler. Perhatikan panas suhu pd pipa discharge kompresor. Perhatikan tekanan freon dan ampere pd saat start kompresor hingga running kompressor di posisi ngegas putaran tinggi, apakah ampere mengikuti kerja kompresor pada putaran bawah dan putaran atas tidak melebihi ampere yg di tentukan di putaran tinggi sampai 4,5 A, dan tekanan freon perhatikan pada jarum manifol dari putaran bawah kompresor stabil turun jarum manifol di 170-180psi hingga putaran tinggi di tekanan 140-150psi. Untuk ac freon r32 atau r410a
@joeteknik4556
@joeteknik4556 2 жыл бұрын
Mau tanya bli... Klo Daikin multi split bisa kah diganti kapiler jg? Soalnya ada 2 katup ekspansi/selenoid Valve.
@madearsa93
@madearsa93 2 жыл бұрын
Tidak bisa
@budiartotenosa5433
@budiartotenosa5433 4 жыл бұрын
Kalah profesor jepang sm oi😄
@madearsa93
@madearsa93 4 жыл бұрын
Hahaha, maaf sy juga baru belajar, memang bisa di gunakan ganti dengan kapiler bisa normal kembali, munkin pd setingan low watt agak kurang dingin sedikit tp tidak terlalu signifikan, dr pengalaman sy pribadi.
@wisnunaiu2777
@wisnunaiu2777 5 жыл бұрын
ijin bertanya master. jika ac matot apa bisa cek kode erornya?
@tigasekawan321
@tigasekawan321 2 жыл бұрын
dingin sih mungkin bisa maksimal,tapi pemakain itu kuat berapa jam??? karena dikasus yg hampir sama seperti ac ini pemakain yg saya uju ini hanya bertahan kurang lebih 5-6 jam setelah itu ac kembali ngetri lagi. mohon bimbingannya....
@madearsa93
@madearsa93 2 жыл бұрын
Cek termistor nya bisa jadi rusak.
@Dhirzky
@Dhirzky 4 жыл бұрын
Bli, tanya AC DAIKIN 1/2 PK SMILE INVERTER saya ketika di hidupkan 2mnt outdoor mati dan indoor tetap running setelahny LED power berkedip indikasi error' L5? Mohon bimbingannya?
@suyonouton9169
@suyonouton9169 4 жыл бұрын
Jika diganti pipa kapirel gitu kira"berbahaya ga,dan brpa lama bisa tahan
@Dhirzky
@Dhirzky 3 жыл бұрын
@@suyonouton9169 kalo masih 3 tahun mending manggil service resmi. Masih free
@siagaopspoldasumbar5579
@siagaopspoldasumbar5579 4 жыл бұрын
sekedar masukan bli... gak baik bagi kompresor ac inverter klo ekspansinya diganti dengan kapiler. karena desain ac inverter harus menggunakan katup ekspansi dimana fungsi ekspansi adalah selain pengganti kapiler pada sirkulasi freon tetapi juga menjaga tekanan pada pipa tekan dan pipa hisap agar berada pada tekanan yang seharusnya. karena ac inverter kompresornya bekerja secara variabel. maksudnya ketika kompresor berjalan pada medium speed maka ekspansi akan menyempit dan apa bila kompresor berjalan pada high speed maka ekspansi akan melebar agar perbandingan tekanan tetap pada takaran yang semestinya. jika diganti dengan kapiler maka penyempitan pada sirkulasi freon akan terjadi secara flat (tetap). alhasil kompresor pada kecepatan rendah sirkulasi freon akan mendekati loss di kapilernya yang mengakibatkan tidak terjadinya pengabutan freon dikapilernya dan tidak mengahasilkan dingin dan jika diukur tekanan pada pipa tekan pada kompresor akan turun dan tekanan pada pipa hisap akan naik dari yang semestinya. sementara jika kompresor berjalan pada high speed atau kecepatan tinggi maka tekanan pada pipa tekan kompresor akan naik tinggi sedangkan pada pipa hisap akan rendah dari yang semestinya, walau pada kecepatan high speed ac akan menghasilkan dingin tetapi akan mengakibatkan kompresor dipaksa bekerja diatas batas kemampuan semestinya untuk memompa dikarnakan debit aliran freon yang diterima kapiler sudah di atas yang semestinya. ini akan membuat kompresor tidak akan bertahan lama.... saran untuk ac inverter jika ekspansinya rusak, alangkah baiknya diganti dengan ekspansi yang baru ketimbang diganti dengan kapiler... karena ac inverter tidak sama dengan ac non inverter.. atau jika suku cadang tidak ada di daerah sekitar tempat tinggal atau terlalu mahal maka opsi kedua lebih baik ac nya dijadikan non iverter dulu baru di ganti dengan kapiler...
@alvinarmianto2792
@alvinarmianto2792 4 жыл бұрын
Mantapss mAs sarannya masuk akan dan Kerennn
@riyadigepeng1828
@riyadigepeng1828 4 жыл бұрын
Kalau inverter daikin eror L5 solusinya apa bos ku?
@deniindarto2989
@deniindarto2989 4 жыл бұрын
ciri" katup exspansi rusak gimna ya bang ?
@fianissa983
@fianissa983 4 жыл бұрын
punya saya di ganti kapiler sudah 3 tahun ke skrg ga masalah ampere normal,mau ganti katup ekspansi waktu itu harganya selangit.
@amirherisusanto8669
@amirherisusanto8669 2 жыл бұрын
Ter merubah kompresor inverter 3phase menjadi manual, apa kah cukup coneksi S,C,R L,N, dan kapasitor?
@ubn4046
@ubn4046 3 жыл бұрын
Bahkan pipa ac nya saya ganti baru 5m & sblm di isi freon nya saya vaccum dulu tapi yg saya bingung setelah 3 hari ac nya mati lagi 🤔
@saifulbakhari2105
@saifulbakhari2105 3 жыл бұрын
Error f3 .ekpansi valvenya di ganti kapilr. Untuk 2pk panjang berapa diameter berapa. Lalu selenoid nya dicabut atao di biarkan saja. Terimakasih.
@madearsa93
@madearsa93 3 жыл бұрын
2pk ukuran kapiler 80mm panjang 60cm , motorize expansi di cabut.
@berbagitau1019
@berbagitau1019 7 ай бұрын
Gan..klau utk 1/2 pk menggunakan pipa kapiler ukuran brapa?
@setia7723
@setia7723 28 күн бұрын
kalau ga ada masalah f3 apakah ac bisa lebih dingin daei eev ke kapiler
@agunghidayatullah1320
@agunghidayatullah1320 Жыл бұрын
Bli Untuk pastikan body expansi rusak/bagus bgaimana caranya ya bli?
@ariefudien7034
@ariefudien7034 3 жыл бұрын
apakah untuk ac samsung ,bisa juga di kasi seperti daikin
@zarifin46somayasulimanzari44
@zarifin46somayasulimanzari44 4 жыл бұрын
Om mau nanya nih AC Daikin 1pk invater saat di nyalahin di lampu indor nya kedap kedip lalu berapa menit AC nya mati lalu dinyalahin lagi tetap gak lm mati lg tp pake kode pan ttp menyalah pas kita kasih kode cool AC nya mati lg dan kira² apaan nya yg jd travel om.?🙏 Mksh sblm nya om.🙏
@madearsa93
@madearsa93 4 жыл бұрын
cek kode error di remote
@zarifin46somayasulimanzari44
@zarifin46somayasulimanzari44 4 жыл бұрын
Kode error' nya U4 om itu kira² apanya ya om.? Trabel nya komponen indor apa Autdor nya om.??
@midasumiarsa5911
@midasumiarsa5911 5 жыл бұрын
Pas AC Daikin Inverter 1PK saya krna F3. Terima service AC bli? Ada kontak yang bisa di hubungi?
@agustitimurti4814
@agustitimurti4814 4 жыл бұрын
Ada ..alamat nya di mana biar kita datangi .. khusus Medan ya .. 🙏
@madearsa93
@madearsa93 4 жыл бұрын
081 999 021 433 daerah denpasar - bali
@warsobaru7309
@warsobaru7309 3 жыл бұрын
Maaf bos, kl koder error' H6 ac Daikin inverter 1pk, kira2 ada kerusakan di komponen bagian mana bos..?🙏
@madearsa93
@madearsa93 3 жыл бұрын
Bisa modul pcb outdoor, dan bisa juga kompresor.
@andirizaldi2427
@andirizaldi2427 5 жыл бұрын
Apakah inverternya ttp berfungsi dgn normal?
@TheRonggo
@TheRonggo 5 жыл бұрын
kalau pakai ekpansi valve berarti gak pakai pipa capiler bos ?
@muhamadsaddam3845
@muhamadsaddam3845 2 жыл бұрын
Kalw katup exspansi d ganti dengan pipa kapiler, sensor.y delepas aja apa di pasang gan.
@madearsa93
@madearsa93 2 жыл бұрын
Di lepas saja
@Ariefindragunawan
@Ariefindragunawan 4 жыл бұрын
Bang mau tanya nih..ac sya daikin inverter 1/2 pk..habis ganti pipa elbow indoor gara2 bocor..usia ac baru 1 stngah thun..setelah seleasai servis..dah berjalan hampir sebulan lebih..dingin mash kurang nyess..tekanan freon normal di cek kode eror remote ga gak ada yg eror..dinginyya kurang nyess..aer pembuangan embun ac normal bgt klo di suhu 25..tpi klo di turun ke 24 atau 23 sma aja gak ada perubahan dinginya..malah aer pembuangan embun mlah jadi agak lambat..padahal sebelumny di suhu 25 aja dah dingin banget sebelum penggantian pipa elbowny...kira2 apa ya solusiny.. Mhon penjelasany..
@madearsa93
@madearsa93 4 жыл бұрын
Bisa jadi pada saat perbaikan kebocoran, sirkulasi pipa ac kurang dibersihkan dan tidak di vacuum, kurangnya tekanan freon, sirkulasi pipa pendinginan terhambat sedikit buntu jadi pendingin tidak normal kurang dingin.
@Ariefindragunawan
@Ariefindragunawan 4 жыл бұрын
Secara prosdur di vacum..tpi yah gtu saya suruh cek kembali tekanan freon sma besar ampereny smpe skrg teknisiny blm dtng2 jg krmh..
@almerkev
@almerkev Жыл бұрын
Halo mas, mau bertanya nih. Ac inverter daikin 1pk saya ada masalah di sensor magnet valve nya, kalau di pasang.. outdoornya mati, namun kalo di copot, outdoor nya nyala. Sudah beli magnet valve baru, namun tidak ada perubahan.. mau di copot tapi takut nantinya akan rusak merembet. Nah ada saran, pipa nya diganti menjadi kapiler.. apakah aman mas?
@arapaimagold8088
@arapaimagold8088 11 ай бұрын
AC kalau pakai EEV, maka di pcb akan ada IC stepper untuk ngatur EEVnya. Itu juga harus anda ganti.
@MELLKY_Si.AnakPejuangReceh
@MELLKY_Si.AnakPejuangReceh 5 жыл бұрын
Ac sy g bisa dingin apa s bang..
@heruhasriadi6185
@heruhasriadi6185 5 жыл бұрын
Kenapa gak ekspansinya aja yg diperbaiki, kan bisa di bersihkan pake r11
@haurakhansa7875
@haurakhansa7875 5 жыл бұрын
Luar biasa,,,,,berkah dan bermanfaat,,saya punya problem,Ac Daikin Tipe RKD 25GVM4, 1 pk,outdoor nyala,kompresor nyala,tapi sebentar dingin,sebentar hilang,,dinginnya cuman 1 menit,kemudian dingin lagi,,hilang lagi,dan seterusnya,apa penyebabnya ya mas? terima kasih,,,,,
@agusrevolusi1329
@agusrevolusi1329 10 ай бұрын
Pak eror u4 inverter daikin yg kerusakannya bagian apa ya.trim ksh.
@whoiam1070
@whoiam1070 5 жыл бұрын
ukuran kapiler dan panjang buat 2pk inverter brapa mas
@kayanbaztard13
@kayanbaztard13 3 жыл бұрын
Klo untuk ac ukuran 1,5pk brapa ukuran pipa kapiler dan panjangnya bli? 🙏 Ampura kari pemula.
@madearsa93
@madearsa93 3 жыл бұрын
Biasanya di gunakan ukuran 0,70mm panjang 60cm
@kayanbaztard13
@kayanbaztard13 3 жыл бұрын
@@madearsa93 oke, suksma bli 🙏
@wijoyochannel
@wijoyochannel 3 жыл бұрын
pipa kapiler 0,54 ini diameter luar apa diameter dalam ya om?
@fachmishahab2872
@fachmishahab2872 3 жыл бұрын
Persis sama spt AC Daikin 1 PK inverter saya.F3 error...kmd ..dibersihkan karat2 pd sensor2 itu....berhasil...kmd dingin...namun cuma bertahan 3 bulan...kmd F3 error lagi....kl begini apa solusinya Mas?
@madearsa93
@madearsa93 3 жыл бұрын
Ganti body expansi valve dan elektronic expansi nya kemungkinan rusak.
@ardypermadi2310
@ardypermadi2310 5 жыл бұрын
Pernah nangani error u2 bli AC seperti itu,jd klu di mode low watt ac jalan normal.tp klu di mode normal outdoornya mati hidup....
@ardypermadi2310
@ardypermadi2310 5 жыл бұрын
@@madearsa93 sudah pernah tp hasilnya sama cek teg input 220 normal,system kelistrikan jg normal pakai 4 kabel standart pemasangan daikin,kompressor jg tdk short. blm di cek bagian modulnya karena tdk punya skemanya.
@ardypermadi2310
@ardypermadi2310 5 жыл бұрын
@@madearsa93 oke terima kasih banyak bli made atas ilmunya,coba saya pelajari dl system kerjanya besok 🙏
@nobieanynomous2424
@nobieanynomous2424 5 жыл бұрын
Ardy Permadi biasanya u2 modul pcb outdoornya bermasalah.. cek sekring, kapasitor, biasanya kapasitor dc nya itu bang
@masmincoolteknik8033
@masmincoolteknik8033 5 жыл бұрын
Pcb noise filter dan fan motor outdorr
@raihanraqqilla3186
@raihanraqqilla3186 4 жыл бұрын
@@masmincoolteknik8033 ganti kapasitor VDC di outdoor
@wahyuardian9729
@wahyuardian9729 5 жыл бұрын
Itu kira kira bermasalahny apa ya om kalau termistor out sm exvansi dg error f3
@wahyuardian9729
@wahyuardian9729 5 жыл бұрын
Apakah ciri ciriny kompressor panas atau kompressor dingin
@zonatriono3612
@zonatriono3612 Жыл бұрын
kl untuk daikin 2pk ukuran dan panjangnya brp ya hu
@rudalsqud926
@rudalsqud926 3 жыл бұрын
Apa setiap kode error F3 seperti ini kerusakannya?.. mohon infonya, terima kasih
@madearsa93
@madearsa93 3 жыл бұрын
Penyebab error F3 bnyk indikasi bisa dari kebocoran freon, expansi valve rusak, elektronik expansi rusak, sensor thermis discahrge rusak, pcb outdoor rusak. Harus di cek dulu dan di pastikan di bagian mana yg rusak.
@budiarimbawa334
@budiarimbawa334 2 жыл бұрын
Mau nanya bli Ac daikin inverter stengah pk waktu ac hidup DinginNya hanya mau 15 menit Stelah itu compresor tambah panas jarum manipol naik terus dan Amper di compresor naik terus Stelah itu dinginNya hilang Kira "dimana rusakNya bli tolong solusinya bli,,🙏
@hendrakurniachanel8902
@hendrakurniachanel8902 11 ай бұрын
Kapasitor DC nya yang kotak sudah coba ganti?
@skychins107
@skychins107 4 жыл бұрын
sore gan,saya mau nanya nih,ac daikin inverter 1pk saya kalau dihidupin pada suhu 24'c 1jam kemudian suhu dinginnya ilang,tp kalau stel suhu 16'c bisa sampe 3jam baru hilang suhu dinginnya,tp indoor tetap hidup,kalau dimatiin pake remote n hidupin balik tetap gak mau dingin,tp kalau matiin kontak listrik dan pasang balik lalu dihidupin baru bisa dingin kembali.tp masalah tetap 1jam kemudian suhu dingin ilang lagi.kenapa ya kira2 n apa kerusakannya.tq
@skychins107
@skychins107 4 жыл бұрын
kelupaan,gak ada kode errornya,semua bagus stel sam00
@madearsa93
@madearsa93 4 жыл бұрын
Sudah dapat di cleaning indoor dan outdoor
@madearsa93
@madearsa93 4 жыл бұрын
Cek kode error pada saat ac error atau tidak dingin.
@nsixfamily6420
@nsixfamily6420 2 жыл бұрын
@@madearsa93 Ini juga sama dengan AC saya daikin inverter 15 menit setelah jalan dinginya hilang
@yogatanaka5544
@yogatanaka5544 4 жыл бұрын
Utk area jakarta ada? Saya kena f3 juga
@madearsa93
@madearsa93 4 жыл бұрын
Saya lokasi di bali mas
@A_dhit_a_m_a
@A_dhit_a_m_a 4 жыл бұрын
AC punya saya sensor yg diluarnya putus kayaknya bagian dalamnya, soalnya kegencet tutup atas. Waktu AC abis di cuci tidak memperhatikan ternyata kabel sensornya kegencet. Untuk menggantinya gimana ya? Atau bisakah kabelnya disambung? Saya belum coba liat daleman kabelnya seperti apa.
@madearsa93
@madearsa93 4 жыл бұрын
Pd outdoor ac sensor thermis putus ?
@A_dhit_a_m_a
@A_dhit_a_m_a 4 жыл бұрын
Iya, thermistor yg ada dibagian luar belakang AC sepertinya putus bagian dalam kabelnya, soalnya kegencet tutup atas casing outdoor. Itu kabel isinya tembaga atau apa ya? Kalo tembaga bisa disambung kan?
@madearsa93
@madearsa93 4 жыл бұрын
Ow, iya bisa di sambung kabel thermisnya.
@dentalexschanelmotovlog4044
@dentalexschanelmotovlog4044 5 жыл бұрын
Klw e5 knp gan?dan cara mngatasinya
@andieazhiez5934
@andieazhiez5934 Ай бұрын
Untuk AC 1/5 PK pipa kalilernya ukuran berapa yah?
@faisalsiregar6409
@faisalsiregar6409 3 жыл бұрын
Bagaimana kita tau kalau expansi valevnya rusak. Dilihat dari fisik atau ada bunyi2 atau bagaimana pak.
@madearsa93
@madearsa93 3 жыл бұрын
Di cek lewat manifold tekanan freon dan ampere nya. Kompresor hidup seiring jalan putaran speed kompresor tekanan freon turun sampai habis dan ampere kompresor tinggi melebihi batas ampere dan overload.
@agnisinatria3520
@agnisinatria3520 3 жыл бұрын
Mungkin maksudnya "fix" atau "repair"
@dominicxavier7384
@dominicxavier7384 4 жыл бұрын
Setelah di ganti kapilernya.ekspansi elektronik nya di ke mana kan yah mas?
@madearsa93
@madearsa93 4 жыл бұрын
Saya lepas, kalo dia protek di pasang aja pinggirin taruhnya
@hadipurwanto9447
@hadipurwanto9447 3 жыл бұрын
Made Arsa... Di lepas tanpa di jemper..? Atau di jemper..?
@theremacoofficial7045
@theremacoofficial7045 2 жыл бұрын
Maksudnya socket nya dilepas dari pcb ya bli, atau socket tetap terpasang di pcb
@redmi4a782
@redmi4a782 4 жыл бұрын
Itu dinginya bisa maksimal ga bro?? TRIms infonya
@madearsa93
@madearsa93 4 жыл бұрын
Bisa, normal dingin seperti biasa.., tapi kalo disetting low watt di remote agak kurang dingin karena kompresor pada low speed di putaran bawah, fungsi katup expansi sudah tidak ada jadi loss konstan menggunakan kapiler, jika kompresor ngegas pd putaran atas dinginnya normal seperti biasa.
@ipl5348
@ipl5348 3 жыл бұрын
Apa tandanya,dan bagaimana cara megetahui klo expansi palep xg rusak boss ku
@madearsa93
@madearsa93 3 жыл бұрын
Ampere naik, tekanan freon turun drastis
@antowijaya1585
@antowijaya1585 5 жыл бұрын
Bang klo panasonic inverter gak mau dingin knpa ya,,,freon 170 amper 1,4,,,itu ac nya 3/4 pk
@antowijaya1585
@antowijaya1585 5 жыл бұрын
Kode nya h 23
@putuagus999
@putuagus999 2 жыл бұрын
gmn cara kerja expansi valve itu?...trs posisi expansi valve di outdoor di mananya?
@arapaimagold8088
@arapaimagold8088 11 ай бұрын
Ngatur besaran sirkulasi freon. Lihat di bagian belakang kompre kalau Daikin. Ada benda bulat dengan magnet di dalam. Itu EEVnya.
@CakraLithium-jm7uy
@CakraLithium-jm7uy 7 ай бұрын
@@arapaimagold8088 kalau dibersihin atau diganti masih error berart pcbnya donk itu kan nyambung pcb yah,
@anakrumahan4172
@anakrumahan4172 4 жыл бұрын
Bli made, kalau kerusakan U0 apa yang harus dicek ya? Saya baca di web artinya tersumbat atau expansion valve. Mohon bisa dibantu spesifiknya bli
@madearsa93
@madearsa93 4 жыл бұрын
U0 = kekurangan freon, ada kebocoran freon.
@anakrumahan4172
@anakrumahan4172 4 жыл бұрын
@@madearsa93 freon sudah dicek nggak bocor bli, tekanan malah di 120. Ampere stabil, tekanan stabil, ac nggak dingin kadang suka mati dan lampu indikator kedip
@madearsa93
@madearsa93 4 жыл бұрын
Ac daikin inverter ? Cek kode error sudah tepat ? Ac sudah dapat di cleaning indoor dan outdoor ?
@anakrumahan4172
@anakrumahan4172 4 жыл бұрын
@@madearsa93 baru indoor bli, kode sudah bener berkali2 cek dapetnya U0. Nanti akan coba saya turunin outdoornya biar keliatan dan saya flush. Kemarin karena freon mau habis, jadinya tukang ac ngisi posisi tabung freon dibalik, takut gram2nya masuk bli. Apakah bisa dari situ penyebabnya bli? Karena setelah diisi freonnya selang 4 hari kejadian seperti ini bli
@madearsa93
@madearsa93 4 жыл бұрын
Freon jenis apa
@helmiwong9641
@helmiwong9641 5 жыл бұрын
cara mengetahui expansi valve yg bocor gmn mas??itu yg di ptotng
@setia7723
@setia7723 6 ай бұрын
bocor sih ga takutnya posisi tutup terus jadi freon ga lancar
@dominicxavier7384
@dominicxavier7384 4 жыл бұрын
Bli.yang mau saya tanyakan? Itu expansi nya di copot.tidak pakei atau gimana yah🙏
@madearsa93
@madearsa93 4 жыл бұрын
Expansi di lepas di ganti dengan kapiler
@meethos
@meethos 3 жыл бұрын
Bli made izin tanya , untuk kode error F6, Sudah pernah menqngabi kah?
@madearsa93
@madearsa93 3 жыл бұрын
Error F6 kontrol Tekanan Tinggi dalam Pendinginan Metode Pendeteksian Kode Error Kontrol tekanan tinggi (Operasi berhenti, penurunan frekuensi, dll) diaktifkan dalam operasi pendinginan jika suhu dirasakan oleh Termistor Penukar Panas outdoor melebihi batas. Kondisi Keputusan Error  Suhu dirasakan oleh Termistor Penukar Panas outdoor naik di atas 60 ° C.  Kesalahan menjadi jelas ketika suhu turun di bawah sekitar 55 ° C. Dugaan Penyebab  Ruang instalasi tidak cukup besar.  Heat Exchanger outdoor Kotor  Fan motor outdoor rusak  Stop valve rusak  Katup ekspansi elektronik atau kumparan rusak  Termistor Penukar Panas outdoor  PCB Unit Outdoor rusak
@bintankuchiha3374
@bintankuchiha3374 Жыл бұрын
Ngatasinnya gmn?
@Tonysiswadi
@Tonysiswadi 5 жыл бұрын
Kalo kapiler daikin 0,5 pk berapa mili ukuranya ya gan
@Tonysiswadi
@Tonysiswadi 5 жыл бұрын
R32
@carleswijaya1818
@carleswijaya1818 5 жыл бұрын
Bagaimana ac 1pk sharp tidak dingin,kompresor mati hidup,kipas jalan.ac dibeli sudah ada 5thn.thanks sebelumnya,bagaimana memperbaikinya.
@donyilham7285
@donyilham7285 4 жыл бұрын
Mau tanya dr jember jawa timur ,van hidup yg jalur konpresor mati hidup sebentar itu kira2 dari apa ya mas....
@madearsa93
@madearsa93 4 жыл бұрын
Ac apa bos
@donyilham7285
@donyilham7285 4 жыл бұрын
@@madearsa93 ac daikin 2pk inverter
@madearsa93
@madearsa93 4 жыл бұрын
Cek kode error nya apa
@donyilham7285
@donyilham7285 4 жыл бұрын
@@madearsa93 code eror 6h
@donyilham7285
@donyilham7285 4 жыл бұрын
Mas made posisi daerah mana
@fikrihudagrab571
@fikrihudagrab571 6 ай бұрын
Bli ac invrter saya set d suhu 24 mau dingin, ketika suhu sudah tercapai kan dia kerja nya melambat, tapi setela itu gamau naik lagi kerja nyq. Kenapa ya? Kalo di mtiin kemudian nyalain kembali dia mau dngin lagi
@setia7723
@setia7723 4 ай бұрын
yah suhu ruangan sudah tercapai kalau naik lagi kompresor hidup lagi inverter itu harusnya di ruang tidur tidak disarankan di tempat ruang kelurga bisa tapi harus rapat ruangan agar kompresor tidak gas terus
@setia7723
@setia7723 4 ай бұрын
tekanan brp psi daikin bukan
@lingkanpradana
@lingkanpradana 4 жыл бұрын
Pak itu klo diganti expansionya persis aslinya apa tidak ada djual?
@madearsa93
@madearsa93 4 жыл бұрын
Ada yg jual di dealer nya harga lumayan
@lingkanpradana
@lingkanpradana 4 жыл бұрын
@@madearsa93 boleh info dealer mna kebetulan saya tinggal dijimbaran, daikin mana, kisaran brp harganya?
@madearsa93
@madearsa93 4 жыл бұрын
Service center daikin di buluh indah harga sekitar 800an komplit body exvansi sm elektronic expansi nya.
@lingkanpradana
@lingkanpradana 4 жыл бұрын
@@madearsa93 oke makasih infonya pak sukses selalu
@madearsa93
@madearsa93 4 жыл бұрын
@@lingkanpradana iya sm2, trimksih kmbli.
@komangkariasa4761
@komangkariasa4761 2 жыл бұрын
Pak mau tanya apa expansi nya dicabut dari vcbnya atau dibiarin ?
@madearsa93
@madearsa93 2 жыл бұрын
Dicabut
@hasriasri6674
@hasriasri6674 3 жыл бұрын
klo compressornya yg rusak, apkah bisadiganti dngan merek lain yg sesama compressor inverter? mohon bimbinganya bang
@sitinurjanah7944
@sitinurjanah7944 5 жыл бұрын
Om klo autdornya mati hidup apa nya ya..ngk sampe 1 menit mati autdornya..punya saya daikin inverter 1pk r32
@sitinurjanah7944
@sitinurjanah7944 5 жыл бұрын
@@madearsa93 sapa cari kode dri remott ngk ada yang eror..aneh mas
@sitinurjanah7944
@sitinurjanah7944 5 жыл бұрын
@@madearsa93 iya mas..kode nya eror di L5..motor kompresor nya.mksh ilmu nya mas
@as_siam1209
@as_siam1209 3 жыл бұрын
apakah gk pengaruh di modul nya kalo gk pakai electronic expansion
@madearsa93
@madearsa93 3 жыл бұрын
Gk ada masalah, aman
@as_siam1209
@as_siam1209 3 жыл бұрын
@@madearsa93 jadi apakah tidak muncul kode eror lagi setelah melepas komponen ter sebut.. dan di terapkan di ac non inverter misal panasonic dan merk ac lainya..
@hobyserviceabalabal7670
@hobyserviceabalabal7670 3 жыл бұрын
kalo error E6 biasanya kompresor macet apa modulnya bli
@madearsa93
@madearsa93 3 жыл бұрын
Kompresor macet
@hobyserviceabalabal7670
@hobyserviceabalabal7670 3 жыл бұрын
@@madearsa93 trimakasi bli..
@iqbalteknik3589
@iqbalteknik3589 5 жыл бұрын
Maaf minta solusi saya bnerin AC daikin sama persis cuma 1/2pk gk dingin sy cek freon 200psi amper 0.8 itu knapa y mas
@iqbalteknik3589
@iqbalteknik3589 5 жыл бұрын
@@madearsa93 tapi hidup posisinya mas sya sampai gonta ganti tang amper bingung gmn caranya mas
@iqbalteknik3589
@iqbalteknik3589 5 жыл бұрын
@@madearsa93 tang amper posisi di 1 di tespen nyala.saya cek kode eror pake remot gk ad eror sampai terakhir ke 00 bunyi panjang.saya isi freon 80 pipa tekan dingin sebentar tekanan manifol naik ke 200 psi amper trun ke 0.8 trus gk dingin sama sekali.
@iqbalteknik3589
@iqbalteknik3589 5 жыл бұрын
@@madearsa93 posisi sting remot di temperatur terendah 18 derajat.
@iqbalteknik3589
@iqbalteknik3589 5 жыл бұрын
@@madearsa93 stat awal amper 1.2 mas itu ac daikin baru 6 bulan masih baru sy blom buka elektronik valvenya.ok sy cba mas mksh saranya
@iqbalteknik3589
@iqbalteknik3589 5 жыл бұрын
@@madearsa93 freon R32 mas..star awal kipas outdor kencang lama amper trun 0.8 tekanan 200psi kipas melambat apa itu normal mas
@ben096
@ben096 4 жыл бұрын
Tak boleh modified expenses valve begitu ,AC sudah hilang digital thermal energy control kalau Di ganti dengan capillaries. Warranty dari Daikin langsung void Di modified begitu .
@aditianugraha4712
@aditianugraha4712 4 жыл бұрын
Betul sekali otomatis system tidak akan bekerja dengan baik, di kemudian hari akan ada error tambahan
@dentalexschanelmotovlog4044
@dentalexschanelmotovlog4044 4 жыл бұрын
Om klw AC inverter 2pk E5 itu knp ya....apa bisa model kyk ini
@madearsa93
@madearsa93 4 жыл бұрын
Kerusakan thermistor pada outdoor
@happyudin7606
@happyudin7606 4 жыл бұрын
E5 inverter ac aux apa sama kerusakan nya d termistor outdoor ?? Trm ksh
@komangkariasa4761
@komangkariasa4761 2 жыл бұрын
Maaf maksudnya controlnya di lepas atau dibiarin ?
@madearsa93
@madearsa93 2 жыл бұрын
Dilepas
@user-ng1qc6xc9e
@user-ng1qc6xc9e Жыл бұрын
Terlalu cepat vidio di tekanan freon bos.jd gsk jelas tekenannya.
@AbdullahKing-rr3yb
@AbdullahKing-rr3yb 3 жыл бұрын
I.4
@anaketv
@anaketv 4 жыл бұрын
Saya service ac Kata orang servicenya beli part dan harganya mahal Nah saya di kasih saran modif, jadi dari mesin yg diluar itu ada kabel sama sklar bell.. Disuruh manual katanya biar ada freonnya, karna mesin yg diluar rusak otomatisnya jadi di buat manual gitu pake saklar Nah apa ya namanya alat nya itu yg mahal katanya..?
@madearsa93
@madearsa93 4 жыл бұрын
Maksudnya ? Pcb outdoor modul inverter.
@anaketv
@anaketv 4 жыл бұрын
@@madearsa93 mungkin itu ya
@anaketv
@anaketv 4 жыл бұрын
@@madearsa93 tapi gak paham saya begituan
@anaketv
@anaketv 4 жыл бұрын
Jadi selama ini saya ya kalo gak dingin saya tekan sklar bell itu, langsung dingin.. Nanti gak dingin lagi saya tekan lagi dingin lagi
@madearsa93
@madearsa93 4 жыл бұрын
@@anaketv ini ac biasa bukan inverter ? Munkin maksudnya yg rusak modul pcb indoor ac jadi gak bisa auto kontak power ke power ke outdoor, jadi di ganti manual hidupin dengan saklar.
SERVICE ERROR U4 AC DAIKIN INVERTER TYPE FTKD25GVM4
11:44
Made Arsa
Рет қаралды 48 М.
# AC DAIKIN Kurang Dingin || Hasil Dingin tidak Maksimal
17:39
FREON BALAP OFFICIAL
Рет қаралды 261 М.
Викторина от МАМЫ 🆘 | WICSUR #shorts
00:58
Бискас
Рет қаралды 3,1 МЛН
Sigma Kid Hair #funny #sigma #comedy
00:33
CRAZY GREAPA
Рет қаралды 37 МЛН
Эффект Карбонаро и нестандартная коробка
01:00
История одного вокалиста
Рет қаралды 10 МЛН
Amazing weight loss transformation !! 😱😱
00:24
Tibo InShape
Рет қаралды 62 МЛН
Apakah bisa Capasitor DC pada AC DAIKIN INVERTER diganti dengan Capasitor AC??
7:04
Cara flushing ac, supaya ac tambah dingin
16:07
sumber dingin teknik
Рет қаралды 392 М.
REPAIR AC DAIKIN INVERTER 1.5 PK ERROR U2
16:17
Made Arsa
Рет қаралды 21 М.
memperbaiki AC Daikin F3 eror kode
17:28
Maulana Chanel tutorial
Рет қаралды 9 М.
Cara pasang 2 pipa kapiler dan strainer ac split, agar ac tambah dingin
22:40
TRICK AIRCOND CHANNEL
Рет қаралды 68 М.
ciri dari AC mampet dan tidak lancar
13:25
Johan Teknik
Рет қаралды 65 М.
GAMPANG ,,,,AC DAIKIN ERROR F3
14:56
andre tatum
Рет қаралды 14 М.
CARA GAMPANG AGAR  KOMPRESOR AC HAMPA UDARA
7:20
id Tube
Рет қаралды 294 М.
Daikin inverter R32,10detik kompresor trip‼️ #DAIKININVERTERR32 #Daikininvertererror
8:07
Викторина от МАМЫ 🆘 | WICSUR #shorts
00:58
Бискас
Рет қаралды 3,1 МЛН