Master Siemens VFD V20 Parameters for Ultimate Control!

  Рет қаралды 42,440

Ruchi electrical

Ruchi electrical

Күн бұрын

Пікірлер: 71
@muhammadasghar2762
@muhammadasghar2762 10 ай бұрын
EXCELLENT WORK DONE SIR.
@Ruchielectrical
@Ruchielectrical 10 ай бұрын
Thank you kindly
@MdSamir-wc8ts
@MdSamir-wc8ts 2 жыл бұрын
Very good vfd setting simple tarika sebsamjhaya sir thanks god bless you
@MdOsman-zk9zy
@MdOsman-zk9zy 2 жыл бұрын
Bahut Acha Bhalo ❤️
@Dines100
@Dines100 7 күн бұрын
Hi friends
@ekblogs4279
@ekblogs4279 2 жыл бұрын
Nice electronic vfd havc draive
@Dines100
@Dines100 7 күн бұрын
Hello friends
@electricandelectronic3746
@electricandelectronic3746 2 жыл бұрын
very good video electrical vfd setting program 👍 👌 👏
@haiderali-jb1vd
@haiderali-jb1vd Жыл бұрын
Very good information sir
@Ruchielectrical
@Ruchielectrical Жыл бұрын
Thanks and welcome
@switchgearsknowledge8669
@switchgearsknowledge8669 10 ай бұрын
Nice from Dubai
@Ruchielectrical
@Ruchielectrical 10 ай бұрын
So nice
@akblogs3618
@akblogs3618 2 жыл бұрын
Very useful information about electrical engineering 👏
@electricaltips4621
@electricaltips4621 2 жыл бұрын
Thanks sir full details video in one video great sir 👍 👏
@kztechautomation426
@kztechautomation426 5 ай бұрын
Best video sir
@Ruchielectrical
@Ruchielectrical 5 ай бұрын
Thanks and welcome
@arthur_1046
@arthur_1046 Жыл бұрын
Mera pass seimens v20 Hai, ye auto mode me nhi chl rha hai , hand se on/ off krna pd rha hai vfd ke button se , Mai vfd to Pressure transmitter se control krna chahta hu , iske liye konsa programming krna pdega ..
@Ruchielectrical
@Ruchielectrical Жыл бұрын
Aap auto mode ka prameter same use karo video dekh ke.apke pressure transmeter ya duct valve se output 0 to 10 volt milega. Usi hisab se vfd .pressure measure karke .speed control hoga.apke sath pid control enabled karna hoga vfd me ok Apke sath plc hai ya directly pressure transmeter se chalana chahte ho. Give me full details. Your logic. Thanks for watching this video
@Ruchielectrical
@Ruchielectrical Жыл бұрын
Phir bhi apko kuch problem ho to.mujhe dusre video ke description me Mera Watsaop no.hai app mujhe contact kijiye ok
@ChandanKumar-pr9us
@ChandanKumar-pr9us Жыл бұрын
Alarms f72 ko solution bata sakte hai
@Ruchielectrical
@Ruchielectrical Жыл бұрын
Set the prameter p2014 =0 set P2000 =0 set Than full power off and restart. Vfd . Thanks for joining my ruchi electrical team
@Ruchielectrical
@Ruchielectrical Жыл бұрын
Phir bhi kuch problem ho mujhe batana ok sir
@ChandanKumar-pr9us
@ChandanKumar-pr9us Жыл бұрын
@@Ruchielectrical abhi rs485 communication hmi se on karne pe on nahi ho rha hai manual running hai but rs485 ka full parameters kya kya chenge karna milega kya
@qaiserabbas8753
@qaiserabbas8753 2 жыл бұрын
Nice
@Dines100
@Dines100 7 күн бұрын
Hello friends
@Uttam07630
@Uttam07630 Жыл бұрын
P 003 ko set krna jaruri hai kya
@ssssa2447
@ssssa2447 10 ай бұрын
V20 me runing rpm kis code me ayega
@Ruchielectrical
@Ruchielectrical 10 ай бұрын
Apke logic ke hisab se alag alag prameter hai. Analog input prameter p1080
@poojatomar7464
@poojatomar7464 Жыл бұрын
Sir slow and fast dono speed me kaise chalega
@Ruchielectrical
@Ruchielectrical Жыл бұрын
kzbin.info/www/bejne/bpivZ5JjebGaj7M Please watch full video
@ramachandranmvk454
@ramachandranmvk454 8 ай бұрын
👍👍👍
@saminmiyaansari5675
@saminmiyaansari5675 Жыл бұрын
Superr
@gurpreetsinghpadda6919
@gurpreetsinghpadda6919 Жыл бұрын
Sir meri v20 vfd output supply Nahi Nikal rahi to me kaya setting karu
@Ruchielectrical
@Ruchielectrical Жыл бұрын
All prameter reset karke dubara set kijiye sahi ho jayega .apka output voltage problem. Phir bhi kuch problem ho mujhe massage kijiye. Thanks for watching and joining my ruchi electrical team
@dilawarkhan4838
@dilawarkhan4838 Жыл бұрын
Sir v 20 vfd fult coming F3 .. please make video
@indiancricket6547
@indiancricket6547 Жыл бұрын
Under voltage Incoming supply of vfd is failed Please check incoming supply of vfd
@shubhambhardwaj2687
@shubhambhardwaj2687 Жыл бұрын
Sir Which rs 485 communication parameter
@Ruchielectrical
@Ruchielectrical Жыл бұрын
P1000 Select 5 set.ok sir Enable RS 485 Fixed speed
@Ruchielectrical
@Ruchielectrical Жыл бұрын
Contact me on Instagram for more information or contact on whatsapp
@rentelisrentelis3340
@rentelisrentelis3340 Жыл бұрын
Подскажите,часто частотный преобразователь выдает ошибку f23 Error f 23 .в мануал данной ошибки не могу найти . подскажите что делать?!
@Ruchielectrical
@Ruchielectrical Жыл бұрын
Home Support Knowledge base Products & Services Support mySiePortal Cart Entry type: FAQ Entry ID: 109766987, Entry date: 05/16/2019 (1) Rate SINAMICS V20: Why do you get fault F23? Entry Associated product(s) Cloning a drive with firmware before 3.9.5 to a drive with firmware 3.9.5 may cause F23 to occur. With firmware version 3.9.5, the parameter p291 has got two additional bits added. Bit 3 and bit 4. These two additional bits were for development use and the added functions are disabled from default.  However, it has been found that if cloning from an earlier version, bit 4 can inadvertently get set to "0", activating an additional detection. So with certain motors or with loads, F23 can be generated due to the ripple seen on the DC link. Disabling the F23 Trip Due p291 is service mode protected p3950 must be set first to 46 for access. If access is done from the BOP then this parameter will be saved automatically. If access is done from the Smart access module the settings will need to be saved manually. In p291 there are now the bits 0 to bit 4. The bits 0 and 4 needs to be "1". The bits 1, 2 and 3 needs to be "0" So the binary bit pattern is "10001" and p291 will this will show "11" in Hex So setting p291 to 11(Hex) will disable the trip with F23. Security information In order to protect technical infrastructures, systems, machines and networks against cyber threats, it is necessary to implement - and continuously maintain - a holistic, state-of-the-art IT security concept. Siemens’ products and solutions constitute one element of such a concept. For more information about cyber security, please visit www.siemens.com/cybersecurity#Ouraspiration. DetailPages.ToPageTop Also available in the following languages: German
@Ruchielectrical
@Ruchielectrical Жыл бұрын
Thanks for watching this video sir.
@rentelisrentelis3340
@rentelisrentelis3340 Жыл бұрын
@@Ruchielectrical Tell me, often the frequency converter gives an error f23 Error f 23 .I can't find this error in the manual. tell me what to do?!
@Ruchielectrical
@Ruchielectrical Жыл бұрын
Ok wait please
@Ruchielectrical
@Ruchielectrical Жыл бұрын
Prameter p3950 set 46.if your vfd bop mode Than Prameter p291 set 3&4 Or 1and 2 .check Your f23 fault is ready now
@abhishekholla2323
@abhishekholla2323 11 ай бұрын
How to view all parameters im not getting all parameter only few its shows
@Ruchielectrical
@Ruchielectrical 11 ай бұрын
P0003 Set 3 After all prameter showing
@abhishekholla2323
@abhishekholla2323 11 ай бұрын
@@Ruchielectrical Thank you
@niravthaker2581
@niravthaker2581 Жыл бұрын
Simence drive g120 ruining by terminal parameters p700 not show in display
@Ruchielectrical
@Ruchielectrical Жыл бұрын
Prameter P0003 set 2
@dkblogs6743
@dkblogs6743 2 жыл бұрын
sir apki video me pura details me batate ho
@Dines100
@Dines100 7 күн бұрын
Hello friends
@satpalkayhrya4511
@satpalkayhrya4511 11 ай бұрын
F 20 ka falt kya h
@majidkhan-ku8cf
@majidkhan-ku8cf 10 ай бұрын
Alarm Aaya to Mai reset KR Diya ab run and trip both indicators show kr rha h please help me
@Ruchielectrical
@Ruchielectrical 10 ай бұрын
Full power off karke 10 mint bad on kijiye sahi ho jayega ok
@majidkhan-ku8cf
@majidkhan-ku8cf 10 ай бұрын
@@Ruchielectrical ok sir
@majidkhan-ku8cf
@majidkhan-ku8cf 10 ай бұрын
Nhi ho rha h
@majidkhan-ku8cf
@majidkhan-ku8cf 10 ай бұрын
WhatsApp no. Dijiye
@majidkhan-ku8cf
@majidkhan-ku8cf 10 ай бұрын
@@Ruchielectrical can you give me WhatsApp no
@baikunthalenka2776
@baikunthalenka2776 5 ай бұрын
F-72 fault show how solve?
@Ruchielectrical
@Ruchielectrical 5 ай бұрын
Cause : USS/MODBUS setpoint fault comes when no setpoint values from USS/MODBUS during telegram off time. When an inverter displays a "USS setpoint fault," it typically indicates a problem with the setpoint value provided via the USS (Universal Serial Interface) communication protocol Check and reply me Thanks for watching and joining my ruchi electrical
@baikunthalenka2776
@baikunthalenka2776 5 ай бұрын
@@Ruchielectrical how to solve fault explain available in manual but how solve what check
@shamsularfeen2576
@shamsularfeen2576 2 жыл бұрын
Ap nak sdakte h ur khakhare h zeyada
@Ruchielectrical
@Ruchielectrical 2 жыл бұрын
Sir ji dardi jada hua tha.us time.video upload ke time.so sorry 😔😔
@charlesmwangi164
@charlesmwangi164 Жыл бұрын
Translate in English
@Ruchielectrical
@Ruchielectrical Жыл бұрын
Please wait ✋️
How to Program Siemens Sinamics V20 VFD in Hindi Tutorial
11:59
Ruchi electrical
Рет қаралды 3,2 М.
Quilt Challenge, No Skills, Just Luck#Funnyfamily #Partygames #Funny
00:32
Family Games Media
Рет қаралды 53 МЛН
Арыстанның айқасы, Тәуіржанның шайқасы!
25:51
QosLike / ҚосЛайк / Косылайық
Рет қаралды 651 М.
[Tutorial] Siemens V20 VFD Setting
8:24
plc247 Automation
Рет қаралды 48 М.
SIEMENS VFD Sinamics V20 parameter settings for auto and manual mode
10:42
Purvanchal electrical automation & entertainment
Рет қаралды 6 М.
Master Siemens G120 Drive Parameters | Ultimate VFD Tutorial
17:09
Ruchi electrical
Рет қаралды 7 М.
How to Program Sinamics V20 VFD in Hindi! Must Watch!
28:59
Ruchi electrical
Рет қаралды 23 М.
Siemens SINAMICS V20 Comissionamento Rápido
6:15
Siemens Knowledge Hub
Рет қаралды 231 М.
Siemens Sinamics V20 VFD 3Wire and Parameters
6:36
Gourav singh king
Рет қаралды 13 М.
#SINAMIC V20 VFD Drive Commissioning Part 3 / #Siemens V20
6:18
Controls and Systems
Рет қаралды 22 М.