How to solve mech pressure high alarm? Already checked discharge pressure and replaced dp switch also.once compressor will start within few second tripping with mech pressure high.this is daikin vfd system(aircooled 2system).can you please guid me as soon as possible
@HVACTechGuidebysreejith3 жыл бұрын
I didn't work vfd chiller. If you send me control wiring diagram maybe I can help you. If you have diagram send me I will check .my what's up number 0097339079784
@sahirpakkarakath3 жыл бұрын
@@HVACTechGuidebysreejiththanks for your reply. i will contact you.
@ramonvargas48822 жыл бұрын
I need help whats control microtech 3
@ramonvargas48822 жыл бұрын
Watser chiller i can on
@sabeelkhantech43663 жыл бұрын
how to chenge evaporate sensor?
@MohdAhmad-xo5ph3 жыл бұрын
Sem chillar def oil high alarm ata hdi
@mdafaquealam60703 жыл бұрын
Sir, mere mcquay cooled screw chiller me high discharge temperature alarm aa raha h, please give your valuable advise
@mdafaquealam60703 жыл бұрын
Reply
@mdafaquealam60703 жыл бұрын
High discharge temperature
@HVACTechGuidebysreejith3 жыл бұрын
Boss I was too busy. If discharge temperature high . 1) Check discharge temperature sensor 2) short of refrigerant 3) over charge refrigerant 4) liquid injection not working 5) condenser Air recycling 6) Check condenser fan motors 7) compressor working unload condition long time with high chilled water temperature 8) economizer not working
@mdafaquealam60703 жыл бұрын
Sir, give your what'sapp no
@mdafaquealam60703 жыл бұрын
Suction pressure 190 Kpa h, discharge pressure 1550 Kpa h aur expansion valve 30% open h, discharge temperature 90 c ja raha h
@ramonvargas48822 жыл бұрын
Help please
@mdafaquealam60703 жыл бұрын
Discharge superheat low alarm in aircooled screw chiller mcquay, how to fix it
@mdafaquealam60703 жыл бұрын
Reply
@HVACTechGuidebysreejith3 жыл бұрын
1)Check suction temperature and suction pressure transducer 2) check discharge temperature sensor and discharge pressure transducer 3) check expansion valve 4)check chilled water flow 5) refrigerant overcharged 6)too much oil in the evaporator