Quick tip on those horizontal blowers. Use your level, more specifically the side with indentation, after putting some decent tension on it. Put it on the belt edge....helps with alignment of the sheaves. It's not spot on perfect....but it gets you close as heck. Love the videos as always, brother
@EverythingHVACR3 ай бұрын
Great tip! Thanks, Jason
@Jon.Rushing3 ай бұрын
Mason line and line level works too. If you want to be real fancy they make laser pulley alignment tools too.
@EverythingHVACR3 ай бұрын
@Jon.Rushing, yeah, those alignment tools can get expensive, too. A good eyeball works great for this small stuff. Thanks, Jon
@jaymartin50953 ай бұрын
Even the easy ones to you are informative to us newbies. Thanks for all the effort to produce the videos
@EverythingHVACR3 ай бұрын
Thanks, Jay!
@ccthepope3 ай бұрын
I love this, "take care of the little things that you can control"
@EverythingHVACR3 ай бұрын
Thanks, r aeronca
@stevencossaboon32373 ай бұрын
Good work Steve. Thank you for the knowledge as always.
@EverythingHVACR3 ай бұрын
Thanks, Steven
@sbingr53133 ай бұрын
Always enjoy your videos. I appreciate that you make them.
@EverythingHVACR3 ай бұрын
I appreciate that sbingr5313, thank you
@somewhatcurious30853 ай бұрын
Had a newly installed York package unit with the belt alingment so far out it would shred a belt in 2 days. Ended up shimming the front mount mount bolts and moving the blower sheave out about an 1". I think, York and Carrier are running a race to the bottom.
@EverythingHVACR3 ай бұрын
Thanks, Somewhatcurious. Quality control is non-existent these days. With the shaft and key, the way I found them on this one, I think someone had their hands on this after installation and just did a poor job.
@jfrancis983 ай бұрын
Lennox is right there too. Misalignment and super loose set screws…
@EverythingHVACR3 ай бұрын
Yeah, they're all right there.
@helmsajr3 ай бұрын
Great job Steve stay safe.
@EverythingHVACR3 ай бұрын
Thanks, Jr
@subcoolHVAC3 ай бұрын
Nice job Steve, give em something to talk about in the break room 😂💪🔐
@EverythingHVACR3 ай бұрын
Thanks, Subcool! 💪
@audaz_firme3 ай бұрын
Great video Steve...you have great attention to detail...e g identifying all the potential rubouts, putting the brass cap to get a good seal on it..."Leave it better then you found it"- Everything Hvacr Greetings 👋🏼
@EverythingHVACR3 ай бұрын
Thanks, hvac_audaz_firme!
@rcf83672 ай бұрын
👍 Great assessment & fixes Steve, in defense of York those weren’t factory issues. However, the wire routing & dress out is rough, that’s classic JCI/York’s lack of controls engineering & workmanship..
@EverythingHVACR2 ай бұрын
Thanks, RCF
@Paul-IE-Repairs3 ай бұрын
it looks like the motor pulley moved, you can see the shiny spot on the shaft
@EverythingHVACR3 ай бұрын
Everything had been messed with, I think someone replaced one or both pulleys at some point. Thanks, Paul
@mrbugenhagen33643 ай бұрын
This is just my guess. The misalignment wore the belt out prematurely and as the belt gets worn down the adjustable pulley pinched the belt and broke it. I have seen that happen with adjustable pulleys because the belt just keeps on digging until it gets snagged. Great video as always